ELKO SHT-6G Time Switch with GPS Control User Guide

June 3, 2024
ELKO

SHT-6G
Time switch with GPS control

Characteristics

Time switch with GPS control is used for the automatic real-time controlling of appliances. The timer operates all year round without the need for continuous maintenance, with minimum operating costs and maximum savings of electrical energy (for example for turning on heating, pumps, ventilators, public lighting etc.). Appliances can be controlled in regular time cycles or based on a pre-set programme.
Time switch SHT-6 is synchronized by a GPS signal using external receiver GPSR-1. Time switch can operate independently without a GPS receiver.
In the case of a power supply interruption, the timer retains all set values required for its reliable activation after power is restored.

  • Switching modes:

  • Auto – automatic switching mode:

  • Programme – switching based on a programme (astro or time).

  • Random – switches randomly in a 10-120 minute interval.

  • Holiday – holiday mode – option of setting up a period for which the timer will be blocked, i.e. will not switch based on the set programmes.

  • Manual – manual mode – option of controlling the individual output relay manually

  • Options of the automatic switching programme:

  • Time programme – switching based on a pre-set time programme

  • Memory capacity for 100 time programmes.

  • Programming can be performed both when power is on or in backup mode.

  • Output relays only operate with a supply voltage of AC 230 V.

  • Menu display selection – CZ / SK / EN / ES / PL / HU / RU (default factory setting EN).

  • Selection of automatic switching between summer / winter time based on location.

  • Backlit LCD display.

  • Simple and easy setup using 4 control buttons.

  • Sealable transparent cover on the front panel.

  • The timer has a backup battery that preserves data in case of a power supply failure (reserve backup time up to 3 years).

  • Supply voltage: AC 230 V.

  • 2-module, mounted onto a DIN rail, clamping terminals.

  • After plugging the timer in for the fi rst time, the current time, date and geographic location must be set for correct operation of the clock.
    Settings can be done:

  • manually: only if the GPS signal is disabled

  • automatically: if the receiver GPSR-1 is connected and GPS signal is enabled.

Description

1. Supply voltage terminal (A1)
2. Display with back-light
3. Place for seal
4. Plug-In with battery backup
5. Supply voltage terminal (A2)
6. Connectors for the GPSR-1 receiver
7. Control buttons
8. Output – channel (16-15-18)
9. Indicates the day in the week
10. Indication| 11. Indication of date / setting menu *
12. Time display **
13. Control button PRG / +
14. Reset
15. Control button MAN /
16. Operating modes indication
17. 12/24 hours format /
18. Indication of the switch program
19. Control button MAN2 / ESC
20. Control button OK
---|---

Symbol

Connection

Mode precendence

Mode precedence Display Output mode
mode with the highest priority ON  / OFF manual control
ON  / OFF holiday mode
ON  / OFF time program Prog

Technical parameters

SHT-6G

Supply terminals: A1 – A2
Supply voltage: AC 100-240V; DC 140-340V (AC 50-60 Hz)
Burden (max.): 5 VA / 2 W
Max. dissipated power (Un + terminals): 4.2 W
Supply voltage tolerance: -15 %; +10 %

Output

Number of contacts: 1x changeover (AgSnO2 )
Rated current: 16 A / AC1
Switching capacity: 4000 VA / AC1, 384 W / DC
Peak current: 30 A / < 3 s
Switching voltage: 250 V AC / 24 V DC
Mechanical life: 30.000.000 ops.
Electrical life (AC1): 100.000 ops.

Time circuit

Real time back-up: up to 3 years

Accuracy
– without GPS receiver:| max. ± 1 s / day at 23 °C (73 °F)
Minimum interval:| 1 min.
Data stored for:| min. 10 years

Program circuit

Number of memory places: 100
Program: daily, yearly (up to year 2099)
Data readout: LCD display, with back light

Other information

Operating temperature: -10.. +55 °C (14 to 131 °F)
Storage temperature: -30.. +70 °C (-22 °F to 158 °F)
Electrical strength: 4 kV (supply – output) 3.3 kV (supply – receiver)
Operating position: any
Mounting: DIN rail EN 60715
Protection degree: IP10 terminals, IP40 from the front panel
Overvoltage category: III.
Pollution degree: 2
Max. cable size (mm2): max. 1x 2.5, max. 2x 1.5/ with sleeve max.1x 1.5
Dimensions: 90 x 35 x 64 mm (3.5˝ x 1.4˝ x 2.5˝)
Weight 114 g (4 oz.) – without battery
Standards: EN 61812-1

Warning

Device is constructed for connection in 1-phase main alternating current voltage AC 100-240V or DC 140-340V and must be installed according to norms valid in the state of application. Connection according to the details in this direction. Installation, connection, setting and servicing should be installed by qualified electrician staff only, who has learnt these instruction and functions of the device. This device contains protection against overvoltage peaks and disturbancies in supply. For correct function of the protection of this device there must be suitable protections of higher degree (A, B, C) installed in front of them. According to
standards elimination of disturbancies must be ensured. Before installation the main switch must be in position “OFF” and the device should be de- energized. Don´t install the device to sources of excessive electro-magnetic interfe rence. By correct installation ensure ideal air circulation so in case of permanent operation and higher ambient temperature the maximal operating temperature of the device is not exceeded. For installation and setting use screwdriver cca 2 mm. The device is fully-electronic – installation should be carried out according to this fact. Non-problematic function depends also on the way of transportation, storing and handling. In case of any signs of destruction, deformation, non-function or missing part, don´t install and claim at your seller it is possible to dismount the device after its lifetime, recycle, or store in protective dump.
No product circuits, including sensor circuits, can be considered as ELVs.
Cable shield to the sensor, fulfills a functional purpose in terms of EMC does not fulfill any protection or safety function and it is not associated with any EP protection. It is not possible to touch the shield as well as the other product wiring circuits!
Security against electric shock is ensured by reinforced insulation product, cable, sensors and their correct and professional installation.

Control description

Device diff ers short and long button press.
In the manual marked as:
– short button press (< 1s)
– long button press (> 1s)
After 30s of inactivity (from the last press of any button) will device automatically returns into starting menu.

Language settings

Battery replacement

You can change the battery without disassembling the device.

  • remove the plug-in module with the battery
  • replace the original battery
  • enter a new battery so that its upper edge (+) lines up with the plug-in module
  • slide the plug-in module in the device and pay attention to polarity (+ up)

ELKO EP, s.r.o.
Palackého 493 769 01 Holešov, Všetuly Czech Republic
Tel.: +420 573 514 211
e-mail: elko@elkoep.com
www.elkoep.com

Made in Czech Republic