solis Export Limit Settings Using Export Power Manager Instructions

June 3, 2024
solis

solis Export Limit Settings Using Export Power Manager

solis Export Limit Settings Using Export Power Manager fig
\(2\)

INSTALLATION STEPS

  • STEP 1: Press Enter on the EPM.

  • STEP 2: Scroll down to ‘Advanced Settings’ using the Up/Down keys. Press Enter.
    Type the password – <0010> and click Ent.
    You will see the following options.solis Export Limit Settings Using Export
Power Manager fig 3

  • STEP 3: Set the inverter quantity by selecting the ‘Inverter Qty’ option. Press Ent to save.

  • STEP 4: Select ‘Backflow Power’ and Press Enter.
    Define the Backflow power as per your requirement using the Up/Down keys. Press Enter to select and save.

  • STEP 5: Select ‘Set Meter CT’ to define the CT ratio parameter. For example, if your CT clamp rating is 100A/5A then the ratio is 20:1. Press Enter to select and save.

  • STEP 6: Press ESC twice to exit.

‘ALL DONE’ HAVE A GOOD DAY!