LUTRON RMJS-PNE-DV Vive Phase Selectable Dimming Module Installation Guide
- June 5, 2024
- Lutron
Table of Contents
RMJS-PNE-DV Vive Phase Selectable Dimming Module
Vive Installation
Vive Phase Selectable Dimming Module
Vive Emergency Phase Selectable Dimming Module
Part of the Vive Family
041769 Rev. A 11/2020
RMJS-PNE-DV RMJS-PNE-DV-EM
120 / 277 V~ 50 / 60 Hz
450 W Incandescent / Halogen 450 VA LED (reverse-phase) 3 A Lutron Hi-lume A-series LTE (13 drivers max) 200 W LED NEMA SSL 7A-2015 450 W ELV 400 VA MLV 400 VA Fluorescent
Important Notes: Please read before installing.
For installation by a qualified electrician in accordance with all local and
national electrical codes. · Note: Use copper conductors only. · Check to see
that the device type and rating is suitable for the application. · DO NOT
install if product has any visible damage. · If moisture or condensation is
evident, allow the product to dry completely before installation. · Operate
between 0 °C and 40 °C (32 °F and 104 °F) ambient. · 0% to 90% humidity, non-
condensing. · For indoor use only. · For spec submittal, see
http://www.lutron.com/TechnicalDocumentLibrary/3691150.pdf
· Operation of a low-voltage circuit with lamps inoperative or removed may
result in transformer overheating and premature failure. Lutron strongly
recommends the following: a. Do not operate low-voltage circuits without
operative lamps in place. b. Replace burned-out lamps as quickly as possible.
c. Use transformers that incorporate thermal protection or fused transformer
primary windings to prevent transformer failure due to overcurrent.
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
· Do not use outdoors. · Do not mount near gas or electric heaters. ·
Equipment should be mounted in locations and at heights where it will not be
subjected to tampering by unauthorized personnel. · The use of accessory
equipment not recommended by the manufacturer may
cause an unsafe condition. · Do not use this equipment for other than its
intended use.
SAVE THESE INSTRUCTIONS
English 10 m (33 ft)
All Wireless Transmitters must be installed within 9 m (30 ft) of the Dimming Module.
Dimming Module
Install in center of room to maximize RF coverage.
Radio Powr Savr Occupancy Sensor
9 m (30 ft) max
RMJS-PNE-DV 120 / 277 V~ 50 / 60 Hz
50019498a
lutron.com
Dimming Module
Pico Remote Control
12 m (40 ft)
Default Functionality
Occupancy Sensors
Occupied: All lights 100%.
Unoccupied: All lights off.
Daylight Sensor
All lights dim in response to daylight.
Link
Cal.
Test
Wireless Controls
On
All lights 100%
Favorite All lights 50%
Off
All lights off
Required Components
For each system, ensure that you have:
One Dimming Module
Indicator LED
At least one Wireless Transmitter
RMJS-PNE-DV 120 / 277 V~ 50 / 60 Hz
Raise
Toggle
Lower
50019498a
lutron.com
Link
Cal.
Test
Customer Assistance www.lutron.com/support
At least one phase dimmable lighting load (incandescent, halogen, LED,
fluorescent, ELV, or MLV) Consult third-party fixtures installation guide for
fixture-specific wiring.
Dimming Module (1 maximum)
Start Here
Radio Powr Savr Occupancy / Vacancy Sensor Pico Remote Control Radio Powr Savr Daylight Sensor Note: All drivers and ballasts used with Vive wireless controls must comply with the
(10 maximum)
(10 maximum)
(1 maximum)
limits pursuant to CAN ICES-005 and the FCC rules.
1 Mount, Wire, and Install Phase Dimmable Devices and Lighting Fixtures
Consult third-party device installation guide
WARNING! Shock Hazard. May result in serious injury or death. Turn off power
at circuit breaker before installing the unit.
A Connect mains wiring (switched hot, neutral, dimmed hot) to each fixture.
Green / Yellow Neutral
Dimmed Line / Hot
Fixture Earth
NEU HOT
MAINS
Sample ballast shown
To additional fixtures NOTE: Output must NOT be used to control receptacles. Output must be directly connected to the load. Output breakers or switches must not be used.
Wire Connector Information
Red
13 mm (1/2 in):
(1-3) 4.0 mm2 (10 AWG)
4.0, 2.5, & 1.5 mm2 (1-3) 2.5 mm2 (12 AWG)
(10, 12, & 14 AWG) (1-3) 1.5 mm2 (14 AWG)
16 mm (5/8 in): 1.0 & 0.75 mm2
(16 & 18 AWG)
(1-2) 4.0 mm2 & (1) 2.5 mm2 (10 & 12 AWG) (1-2) 4.0 mm2 & (1) 1.5 mm2 (10 & 14 AWG) (1-2) 2.5 mm2 & (1) 1.5 mm2 (12 & 14 AWG) (1-2) 4.0 mm2 & (1) 1.0 mm2 (10 & 16 AWG)
(1-2) 2.5 mm2 & (1) 1.0 mm2 (12 & 16 AWG)
(1-2) 1.5 mm2 & (1) 1.0 mm2 (14 & 16 AWG)
(1-2) 4.0 mm2 & (1) 0.75 mm2 (10 & 18 AWG)
(1-2) 2.5 mm2 & (1) 0.75 mm2 (12 & 18 AWG)
(1-2) 1.5 mm2 & (1) 0.75 mm2 (14 & 18 AWG)
3 Phase Selection
Proper phase selection depends upon load type. See Side 2 of this sheet for
selecting the phase. Default phase is reverse-phase. MLV: Change to forward-
phase. Fluorescent ballasts: Change to forward-phase (consult specific
manufacturer’s literature) LED: Consult manufacturer’s literature. Some LED
drivers require forwardphase, some require reverse-phase. Lutron LTE drivers:
Change to forward-phase. Load will fade to full ON. PHPM-PA-120, PHPM-PA-DV,
and PHPM-PA-277 / -DV: change to forwardphase.
Troubleshooting
Fixtures cannot be controlled locally from Dimming Module.
Lights do not dim as expected. Lights do not respond to Wireless
Transmitter(s) (Pico remotes and RPS sensors). Lights are unstable at low-end
(or high-end) or flash/flicker at turn-on or turn-off. Wireless Transmitter(s)
cannot be associated to Dimming Module.
2 Install Dimming Module
Suggested Installation Location: Center of room to
ensure proper RF coverage of area.
For optimal RF performance: Module must not be fully
enclosed in metal. No metal should exist anywhere
within 200 mm (8 in) in front of the front plate of the
module. Mount a minimum of 0.6 m (2 ft) away from
the controlled fixture. Ensure the junction box is well
grounded
(preferably
via
a
metal
conduit
between
the3.94 (100.1)
controlled fixture and the module junction box).
A Dimming Module must be installed in a metal 101.6 mm x 101.6 mm (4 in x 4
in) junction box (minimum depth 54 mm (2.125 in) with mounting screws
(provided). Please consult local and national electric codes for proper
installation. Lutron can provide a barrier, if required, to provide separation
in the junction box between Class 1 and Class 2 wires. Note: if module cannot
be fully seated into the junction box, try rotating the module 90, 180, or 270
degrees. Or move conduit hardware to a different knockout hole. If neither
option works, an extension ring may
be required.
B Connect bare copper wire from junction box to green ground screw.
C Once installed, energize the Dimming Module.
D Use the Toggle button “u” to toggle between high-end and OFF to verify ballasts or LED drivers wiring.
200 mm (8 in)
200 mm (8 in)
200 mm (8 in))
RMJS-PNE-DV 120 / 277 V~ 50 / 60 Hz
50019498a
lutron.com
200 mm (8 in)
Keep metal at least 200 mm (8 in) away
200 mm (8 in)
200 mm (8 in)
200 mm (8 in)
E Use the Raise “” and Lower ” ” buttons to verify control wiring.
4 Programming with a Vive Hub
The Vive hub can be set-up easily with any Wi-Fi enabled iOS® or Android® compatible device. A Download the Lutron Vive app.
B Open the app and follow the instructions.
vive.lutron.com
X
Junction Box Line / Hot (Black) Neutral
Dimmed Line / Hot (Red) Neutral (White) To Fixtures
RMJS-PNE-DV 120 / 277 V~ 50 / 60 Hz
50019498a
lutron.com
Note: RMJS-PNE-DV-EM requires the use of an automatic transfer switch to change from normal to emergency power. Refer to 048628 for wiring diagrams on www.lutron.com If installing an emergency Dimming Module and the wiring needs to be verified, follow “Reset Factory Defaults” procedure to exit emergency mode. Please note that any programming will be lost and will have to be reprogrammed. Only perform this step during initial installation and wiring verification. Note: For periodic testing and maintanance of emergency systems, use the toggle button to ensure proper operation. Make sure buttons remain accessible. Note: Momentary power outages can envoke emergency mode on the dimming module. SeeTroubleshooting section for details.
Note: For further information on set up, programming, and troubleshooting with
a Vive system, please refer to the installation instructions included with the
Vive hub or visit www.lutron.com/vive
Note: For programming the Dimming Module without a Vive hub see reverse side.
www.lutron.com/support
· Ensure that the breaker(s) to the Dimming Module are energized. · Ensure
that the Dimming Module dimmed hot lead is wired to the lighting fixture(s). ·
Dimming Module may be in emergency mode.
Reset to factory defaults.
· Ensure that dimmed hot line is wired properly. · Dimming Module may be in
emergency mode.
· Ensure that the breaker(s) to the Dimming Module and any connected ballasts
or LED drivers are energized. · Ensure that Wireless Transmitters are
associated to the Dimming Module.
Reset to factory defaults.
· Adjust low-end (or high-end) trim.
· The maximum number of Wireless Transmitters have been associated to the
Dimming Module. To remove a previously set up Wireless Transmitter, tap a
Wireless Transmitter button three times; on the third tap hold for three
seconds and then tap three more times.
Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 USA
Installation Programming without a Vive Hub
Dimming Module
Part of the Vive Family
Start Here
1 Associate Wireless Transmitters to Dimming Module
Before beginning this step, make sure that there are no other Dimming Modules
being set up within the same building. It is possible that wireless
transmitters from other systems can be incorrectly associated to this module.
A On Dimming Module, hold Toggle button “u” for 6 seconds until lights flash.
The indicator LED will begin flashing twice per second.
RMJS-PNE-DV 120 / 277 V~ 50 / 60 Hz
50019498a
lutron.com
B Hold the indicated button on each transmitter for 6 seconds. Lights will flash to show that wireless transmitters have been associated.
Link Test
C On Dimming Module, hold Toggle button “u” for 6 seconds to save association.
Lights will flash and LED will quickly blink for 2 seconds.
D Permanently install wireless transmitters (consult individual component
installation guides for information).
Reset Factory Defaults
Note: In some instances, it may be necessary to reset the Dimming Module and
connected devices back to factory default settings. Before beginning, make
sure that all devices are connected and powered. A Triple-tap the Toggle
button “u” on the Dimming Module and hold until the LED begins to flash
slowly; release button. B Within 3 seconds of the start of flashing, triple-
tap the same button again and the LEDs will flash rapidly indicating that the
unit has been reset to factory defaults. Note: Any associations or programming
previously set up with the Dimming Module will be erased and will need to be
re-programmed.
Customer Assistance www.lutron.com/support
2 Calibrate the Radio Powr Savr Daylight Sensor
Daylight Sensor will control all wired fixtures equally. A Press and release
the “Cal.” button on the Daylight Sensor. B Set lights in room to desired
light level. C Press and hold the “Cal.” button for 6 seconds.
Link
Cal.
Test
D Exit room for 5 minutes to complete calibration. Note: When calibration has completed, all lights will flash and begin to respond to daylight.
Multiple Daylight Rows (Optional) For every row of daylighting, a separate
Dimming Module must be used. For detailed setup refer to the tuning section of
the Radio Powr Savr Daylight Sensor installation guide.
· Select the Dimming Module that you want to adjust by pressing the toggle
button.
3 Set a Favorite Light Level (Optional)
For Pico remote controls with a Favorite Button.
Raise
Lower
A Adjust lights to desired level:
Use the Raise button ” ” or Lower button ” ” on the Pico remote control.
B Save favorite level:
Press and hold the Favorite button for 6 seconds. The load will flash 3 times to confirm that the Favorite level is saved.
Favorite
4 Phase Selection
To change to forward-phase: A Press and hold Raise” ” & Lower ” ” buttons for
12 seconds. Indicator LED will flash and load will fade to OFF. B Raise button
” “press sets the current phase to forward-phase, Lower button ” ” press sets
the current phatsoereverse-phase. Indicator LED Feedback:
(Reverse-phase): Flash 1 time with 1 second period and then turn OFF for 2
seconds (Forward-phase): Flash 2 times with 1 second period and then turn OFF
for 1 second
C Press and hold Toggle button for 6 seconds. Indicator LED will flash for 5
seconds. Load will fade to full ON.
6 Set Minimum Light Level (Optional)
Certain applications (e.g., hallways), may require that the lights never turn
off. For these areas, activate Minimum Light Level mode. A Enter minimum light
level adjustment mode: Press and hold Toggle button “u” and Lower button ” ”
for 12 seconds. Lights will flash high-low-high and LED will begin flashing.
If lights stop flashing and go to high-end, the minimum light level is set to
OFF (default). If lights stop flashing and go to low-end, the minimum light
level is ON and set to low-end. B Change the minimum light level: Press Raise
button “” to set minimum light level to low-end. Press Lower button ” ” to set
minimum light level to OFF. C Save the minimum light level: Press and hold
Toggle button “u” for 6 seconds. LED will quickly flash to indicate that new
level has been saved.
7 Set Occupancy Light Levels (Optional)
Note: Unoccupied light level is always the minimum light level and cannot be
adjusted. A Set desired occupancy light levels:
Use Raise / Lower buttons “/ ” on the Dimming Module or Raise / Lower buttons
” / ” on all associated Pico Remote Controls. B Save occupancy light levels:
Press and hold Test button for 6 seconds on any associated Radio Powr Savr
Occupancy Sensor without a Lights On button. Release when Sensor lens starts
to flash. Or, press and hold Lights On button for 6 seconds on any associated
Radio Powr Savr Occupancy Sensor. Release when Sensor lens starts to flash.
5 Set Low-End Trim and High-End Trim (Optional)
For best results, minimize the amount of sunlight entering the room before performing the following procedures.
Notes:
Depending on the fixture manufacturer or load, low-end trim and high-end trim
may need to be adjusted.
· Trim low-end to ensure a stable light level because some loads will flicker
or drop out if trimmed too low.
· Be sure that you can turn on the lights to the low-end trim level without
any abnormal operation.
· The factory default high-end trim is suitable for most applications but can
be adjusted as desired.
RMJS-PNE-DV 120 / 277 V~ 50 / 60 Hz
50019498a
lutron.com
Low-End Trim
A Enter low-end trim adjustment mode: Press and hold the Lower button ” ” on
the fixture control for 12 seconds. The lights will flash and the indicator
LED will begin flashing.
B Adjust the low-end trim: Use the Raise button “” and Lower button ” ” on the
fixture control to adjust and set the lights to the desired low-end (1 to
45%).
C Save the low-end trim: Press and hold the Toggle button “u” for 6 seconds to
save setting. The indicator LED will begin flashing and then turn solid to
indicate new level has been saved.
High-End Trim
A Enter high-end trim adjustment mode: Press and hold the Raise button “” on
the fixture control for 12 seconds. The lights will flash and the indicator
LED will flash.
B Adjust the high-end trim: Use the Raise button “” and Lower button ” ” on
the fixture control to adjust and set the lights to the desired high-end (55
to 100%).
C Save the high-end trim: Press and hold the Toggle button “u” for 6 seconds
to save setting. The indicator LED will begin flashing and then turn solid to
indicate new level has been saved.
FCC/ IC Information: This device complies with part 15 of the FCC Rules and
Industry Canada license-exempt RSS standard(s). Operation is subject to the
following two conditions: (1) This device may not cause interference, and (2)
this device must accept any interference, including interference that may
cause undesired operation. Modifications not expressly approved by Lutron
Electronics Co., Inc. could void the user’s authority to operate this
equipment.
Note: This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more
of the following measures:
·Reorient or relocate the receiving antenna ·Increase the separation between
the equipment and receiver ·Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected ·Consult the dealer or
an experienced radio/TV technician for help
Customer Assistance: U.S.A. / Canada: 1.844.LUTRON1 www.lutron.com/support
Limited Warranty:
www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf
Lutron, Pico, Radio Power Savr, and Vive are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the US and/or other countries. Safari is a trademark of Apple Inc., registered in the U.S. and other countries. All other product names, logos, and brands are property of their respective owners. ©2013 2020 Lutron Electronics Co., Inc.
References
- Vive Reconnect | Lutron
- Lutron Support Center | Lutron
- Vive - Commercial Wireless Lighting Control System | Lutron
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>