inELS RFSAI-62B-SL Dual Band Wireless Switching Component Input Button Instruction Manual

June 5, 2024
inELS

RFSAI-62B-SL Dual Band Wireless Switching Component Input Button
Instruction Manual

Characteristics

  • Switching components with 2 relay outputs are used to control appliances and lights. Internal terminals can connect two existing buttons in the wiring.
  • They can be combined with detectors, controllers, iNELS RF Control, or system components.
  • The BOX design lets you mount it right in an installation box, a ceiling, or a controlled appliance cover.
  • It allows the connection of switched loads with a total sum of 8 A (2,000 W).
  • Function: button, impulse relay, and time function of a delayed start or return with a time setting range of 2s-60min. It is possible to assign any function to each output relay.
  • The external button is programmed as a wireless button.
  • Each output can be controlled by up to 12/12 channels (1 channel represents 1 button on the controller).
  • The programming button on the unit is also used for manual control of the output.
  • Memory status can be pre-set in the event of a power failure.
  • For components labeled as iNELS RF Control2 (RFIO 2 ), it is possible to set the repeater function via the RFAF/USB service device.
  • Range up to 200 m (in open space), if the signal is insufficient between the controller and unit, use the signal repeater RFRP-20 or protocol component RFIO2 that supports this feature.
    Communication frequency with bidirectional protocol iNELS RF Control (RFIO2).

Assembly

mounting in an installation box / (even under the existing button/switch)| mounting into the light cover| ceiling mounted
---|---|---
| |

Connection

inELS RFSAI 62B SL Dual Band Wireless Switching Component Input Button -
Connection

Screwless terminals

inELS RFSAI 62B SL Dual Band Wireless Switching Component Input Button -
Screwless terminals

Radiofrequency signal penetration through various construction materials

| | | |
---|---|---|---|---
60 – 90 %| 80 – 95 %| 20 – 60 %| 0 – 10 %| 80- 90 %
brick walls| wooden structures
with plasterboards| reinforced concrete| metal partitions| common glass

Indication, manual contro

inELS RFSAI 62B SL Dual Band Wireless Switching Component Input Button -
Indication

  1. LED / PROG button
    • LED green V1 – device status indication for output 1
    • LED red V2 – device status indication for output 2.
    Indicators of memory function:
    On – LED blinks x 3.
    Off – The LED lights up once for a long time.
    • Manual control is performed by pressing the PROG button for<1s.
    • Programming is performed by pressing the PROG button for 3-5s.

  2. Terminal block – connection for external button

  3. Terminal block – connecting the neutral conductor

  4. Terminal block – load connected with the sum of the total current 8A (eg V1=6A, V2=2A)

  5. Terminal block for connecting the phase conductor

In the programming and operating mode, the LED on the component lights up at the same time each time the button is pressed – this indicates the incoming command.

  • RFSAI-61B-SL: one output contact, status indication by a red LED

Compatibility

The device can be combined with all system components, controls, and devices of iNELS RF Control and iNELS RF Control2.
The detector can be assigned an iNELS RF Control2(RFIO2) communication protocol.

Channel selection

Channel selection (RFSAI-62B-SL) is done by pressing the PROG buttons for 1-3s.
RFSAI-61B-SL: press for more than 1 second.
After button release, LED is fl ashing indicating the output channel: red (1) or green (2). All other signals are indicated by the corresponding color of the LED for each channel.

Functions and programming with RF transmitters

Description of button

The output contact will be closed by pressing the button and opened by releasing the button.
For the correct execution of individual commands (press = closing / releasing the button = opening), the time delay between these commands must be a min.
1s (press – delay 1s – release).

Programming

inELS RFSAI 62B SL Dual Band Wireless Switching Component Input Button -
Programming

Function switch on

Description of switch-on

The output contact will be closed by pressing the button.

Programming

Function switch off

Description of switch off

The output contact will be opened by pressing the button.

Programming

inELS RFSAI 62B SL Dual Band Wireless Switching Component Input Button
-Programming

Function impulse relay

The output contact will be switched to the opposite position by each press of the button. If the contact was closed, it will be opened and vice versa.

Programming

inELS RFSAI 62B SL Dual Band Wireless Switching Component Input Button
-Programming 2

Function delayed off

Description of delayed off

The output contact will be closed by pressing the button and opened after the set time interval has elapsed.

Programming

inELS RFSAI 62B SL Dual Band Wireless Switching Component Input Button
-Programming 3inELS RFSAI 62B SL Dual Band Wireless Switching Component
Input Button -Programming 4

Function delayed on

Description of delayed on

The output contact will be opened by pressing the button and closed after the set time interval has elapsed.

Programming

inELS RFSAI 62B SL Dual Band Wireless Switching Component Input Button
-Programming 5inELS RFSAI 62B SL Dual Band Wireless Switching Component
Input Button -Programming 6

Programming with RF control units

inELS RFSAI 62B SL Dual Band Wireless Switching Component Input Button -RF
control units

Addresses listed on the front side of the actuator are used for programming and controlling the actuator and individual RF channels by control units.

Delete actuator

Deleting one position of the transmitter

By pressing the programming button on the actuator for 8 seconds (RFSAI-61B- SL: press for 5 seconds), the deletion of one transmitter activates. LED flashs 4x in each 1s interval.
Pressing the required button on the transmitter deletes it from the actuator’s memory.
To confi rm deletion, the LED will confi rm with a flash long and the component returns to the operating mode. The memory status is not indicated. Deletion does not affect the preset memory function.

Deleting the entire memory

By pressing the programming button on the actuator for 11 seconds (RFSAI-61B- SL: press for more than 8 seconds), deletion occurs of the actuator’s entire memory. LED
flashes 4x in each 1s interval. The actuator goes into the programming mode, the LED fl ashes in 0.5s intervals (max. 4 min.).
You can return to the operating mode by pressing the Prog button for less than 1s. The LED lights up according to the pre-set memory function and the component returns to the operating mode. Deletion does not affect the pre-set memory function.

Selecting the memory function

inELS RFSAI 62B SL Dual Band Wireless Switching Component Input Button
-memory function

  • Memory function on:
    – For functions 1-4, these are used to store the last state of the relay output before the supply voltage drops, the change of state of the output to the memory is recorded 15  seconds after the change.
    – For functions 5-6, the target state of the relay is immediately entered into the memory after the delay, after re-connecting the power, the relay is set to the target state.

  • Memory function off:
    When the power supply is reconnected, the relay remains off.

The external button RFSAI-62B-SL is programmed in the same way as for wireless.
RFSAI-11B-SL it is not programmed, it has a fixed function.

Technical parameters

Supply voltage: 230 V AC
Supply voltage frequency: 50-60 Hz
Apparent power: 7 VA / cos φ = 0.1
Dissipated power: 0.7 W
Supply voltage tolerance: +10 %; -15 %
Output
Contact: 2x switching
Rated current: 8 A / AC1
Switching power: 2000 VA / AC1
Peak current: 10 A / <3 s
Switching voltage: 250 V AC1
Mechanical service life: 1×107
Electrical service life (AC1): 1×105
Control
Wirelessly: each of the output up to 12 chanels (buttons)
Communication protocol: RFIO 2
Frequency: 866–922 MHz
Function repeater: yes
Manual control: button PROG (ON/OFF)
External button:  max. 100 m
Range: up to / 200 m
Other data
Operating temperature: -15 …+ 50 °C
Operating position: any
Mounting: free at lead-in wires
Protection: IP40
Overvoltage category: III.
Contamination degree: 2
Cross-section of connecting wires: 3x 0.2, 1x 1.5 mm2
Dimension: 43 x 44 x 22 mm
Weight: 45 g
Related standards: EN 50491, EN 63044, EN 300 220, EN 301 489
  • Control button input is at the supply voltage potential.
    Attention:
    When you install iNELS RF Control system, you have to keep a minimum distance of 1 cm between each unit.
    Between the individual commands must be an interval of at least 1s.

Warning

The instruction manual is designated for mounting and also for the user of the device. It is always a part of its packing. Installation and connection can be carried out only by a person with adequate professional qualification upon understanding this instruction manual and functions of the device, and while observing all valid regulations. The trouble-free function of the device also depends on transportation, storing, and handling. In case you notice any sign of damage, deformation, malfunction, or missing part, do not install this device and return it to its seller. It is necessary to treat this product and its parts as electronic waste after its lifetime is terminated. Before starting the installation, make sure that all wires, connected parts, or terminals are de-energized. While mounting and servicing observe safety regulations, norms, directives, and professional, and export regulations for working with electrical devices. Do not touch parts of the device that are energized – a life threat. Due to the transmissivity of RF signal, observe the correct location of RF components in a building where the installation is taking place. RF Control is designated only for mounting in interiors. Devices are not designated for installation in exteriors and humid spaces. They must not be installed into metal switchboards and into plastic switchboards with metal doors – transmissivity of RF signal is then impossible. RF Control is not recommended for pulleys etc. – the radiofrequency signal can be shielded by an obstruction, interfered with, a battery of the transceiver can getflat, etc., and thus disable the remote control.

ELKO EP, s.r.o. e-mail: elko@elkoep.cz
Support: +420 778 427 366 |
www.elkoep.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals