inELS RFSG-1M Wireless Contact Converter Instruction Manual
- June 3, 2024
- inELS
Table of Contents
inELS RFSG-1M Wireless Contact Converter
Characteristics
- This wireless contact converter is especially appropriate for wireless transmission of information on switching HDO.
- Thanks to the network supply, it can also be used for partial transmission of information for control of an appliance or device.
- One-module design of the unit with mounting into switchboard.
- After leading in power /disconnecting the supply to the “S” terminals, the switch on/off command is transmitted and then this command is being periodically transmitted in an interval of 2 min.
- The button TEST on the controller is used to assign to a switching unit.
- Option of setting light scenes, where with a single press, you can control multiple units of iNELS RF Control.
- The package includes an internal antenna AN-I, in case of locating the converter in a metal switchboard, you can use the external antenna AN-E for better signal reception.
- Range up to 160 m (in open space), if the signal is insufficient between the controller and unit, use the signal repeater RFRP-20.
- Communication frequency with bidirectional protocol iNELS RF Control.
Compatibility
The RFSG-1M converter is compatible with all iNELS RF Control switching components.
Radiofrequency signal penetration through various construction materials
| | | |
---|---|---|---|---
80 – 95 %| 80 – 90 %| 60 – 90 %| 20- 60 %| 0 – 10 %
wooden structures with plaster boards| common glass| brick walls| reinforced
concrete| metal partitions
Indication, manual control
- LED Un – green – supply voltage indication.
- LED STATUS – red – transmission indication.
- Programming is performed using the TEST button.
Assembly
mounting into switchboard
Connection
Programming
-
Pressing of the programming button on the actuator (e.g. RFSAI-61B-SL) for 1 second will activate the actuator into programming mode. LED is fl ashing in 1s interval.
-
Press and hold the TEST button on RFSG-1M for more than 4s to automatically assign the RFSG-1M transmitter to the actuator.
-
Press of programming button on actuator RFSAI-61B-SL shorter then 1 second will fi nish programming mode, LED switches off .
Indicators, settings
After connecting the power supply, the red LED lights up continuously for 3 seconds and then the selected controller function is indicated by fl ashing LED for 5 seconds.
- double fl ash – standard RFIO2 operating mode
- rapid fl ashing – mode of compatibility with older actuators
If you do not want to change the function of the controller, you must not press the TEST button during this time.
To switch between RFIO2 mode and compatibility mode:
If you need to change the operating mode of the controller, after connecting
the power supply, when the LED is lit continuously, press the TEST button and
hold until the LED starts to signal the changed mode (double fl ash or rapid
fl ash). Then the button must be released. The selected function mode is
stored in memory and after connecting the power supply, the controller
continues to operate in the same mode.
Technical parameters
Supply voltage: | 110-230 V AC / 50-60 Hz |
---|---|
Apparent input: | 2 VA |
Dissipated power: | 0.2 W |
Supply voltage tolerance: | +10 % / -25 % |
Power supply indication: | green / zelená LED |
Input | |
Control voltage: | AC 12-230V / DC 12-230V |
Control input power: | AC 0.025VA / DC 0.1W |
Control terminals: | S – S |
The length of control impulse: | min. 25ms (max. unlimited / max. neomezená) |
Transmission indication / function: | red / červená LED |
Transmitter frequency: | 866 MHz, 868 MHz, 916 MHz |
Signal transmission method: | unidirectionally addressed message / |
jednosměrně adresovaná zpráva
Range in free space:| up to / až 160 m
Minimum control distance:| 20 mm
Output for RF antenna:| SMA connector / konektor *
Other data|
Operating temperature:| -15 … + 50 °C
Operating position:| any / libovolná
Mounting:| DIN rail support / DIN lišta EN 60715
Protection:| IP20 from the front panel / z čelního panelu
Overvoltage category:| III.
Contamination degree:| 2
Connecting conductor cross-
section (mm2):
| max. 1×2.5, max. 2×1.5 /
with a hollow / s dutinkou max.1×2.5
Dimensions:| 90 x 17.5 x 64 mm
Weight:| 62 g
Related standards:| EN 60669, EN 300220, EN 301489 R&TTE Directive, Order. No
426/2000
Coll. (Directive 1999/EC) / EN 60669, EN 300 220, EN 301 489 směrnice RTTE,
NVč.426/2000Sb (směrnice 1999/ES)
Max Tightening Torque for antenna connector is 0.56 Nm.
Attention:
When you instal iNELS RF Control system, you have to keep minimal distance 1
cm between each units.
Between the individual commands must be an interval of at least 1s.
Warning
The instruction manual is designated for mounting and also for user of the
device. It is always a part of its packing.
Installation and connection can be carried out only by a person with adequate
professional qualifications upon understanding this instruction manual and the
functions of the device, and while observing all valid regulations. The
trouble-free function of the device also depends on transportation, storing,
and handling. In case you notice any sign of damage, deformation, malfunction
or missing part, do not install this device and return it to its seller. It is
necessary to treat this product and its parts as electronic waste after its
lifetime is terminated. Before starting the installation, make sure that all
wires, connected parts or terminals are de-energized. While mounting and
servicing observe safety regulations, norms, directives and professional, and
export regulations for working with electrical devices. Do not touch parts of
the device that are energized – life threat. Due to the transmissivity of RF
signal, observe the correct location of RF components in the building where
the installation is taking place. RF Control is designated only for mounting
in interiors. Devices are not designated for installation into exteriors and
humid spaces. They must not be installed into metal switchboards and into
plastic switchboards with metal doors – transmissivity of RF signal is then
impossible. RF Control is not recommended for pulleys etc. – the
radiofrequency signal can be shielded by an obstruction, interfered with,
battery of the transceiver can get fl at etc., and thus disable the remote
control.
ELKO EP declares that the RFSG type of equipment complies with Directives
2014/53/EU, 2011/65/EU, 2015/863/EU and 2014/35/
EU. The full EU Declaration of Conformity is at: https://www.elkoep.com
/wireless-contact-converter-230v—rfsg-1m
ELKO EP, s.r.o., Palackého 493, 769 01 Holešov, Všetuly, Czech Republic
Tel.: +420 573 514 211, e-mail: elko@elkoep.com,
www.elkoep.com
Wireless contact converter
Documents / Resources
|
inELS RFSG-1M Wireless Contact
Converter
[pdf] Instruction Manual
RFSG-1M, Wireless Contact Converter, RFSG-1M Wireless Contact Converter,
Contact Converter, Converter
---|---
|
inELS RFSG-1M Wireless Contact
Converter
[pdf] User Manual
RFSG-1M Wireless Contact Converter, RFSG-1M, Wireless Contact Converter,
Contact Converter
|
inELS RFSG-1M Wireless Contact
Converter
[pdf] Instruction Manual
RFSG-1M Wireless Contact Converter, RFSG-1M, Wireless Contact Converter,
Contact Converter, Converter
References
- ElkoEP - Výrobce elektronických přístrojů • ELKO EP POLAND Sp. z o.o.
- Převodník kontaktu RFSG-1M • ELKO EP s.r.o
- Input contact converter RFSG-1M • ELKO EP