INSTALLATION INSTRUCTIONS
SAFETY
This product complies in full with AS/NZS 61439.3.
This product should be installed by a suitably qualified person in accordance with Australian and New Zealand wiring rules.
INSTALLATION PROCEDURE
This product is designed to be installed inside a wall cavity with a minimum stud size of 90mm and a minimum plaster board/ wall covering of 10mm.
This product is designed to be installed inside a wall cavity on its own. For surface mounting use VMCC surface mount enclosure in conjunction with this board.
The metal wall enclosure must be earthed. Fold out tags (x6) on the side walls of the enclosure can be folded out to set the correct height onto the studs.
Door hinge pins are easily removable and the door can be reversed so that it swings either left or right. This product is designed to be used with New Zealand and Australia’s MEN system.
DO NOT install a link between the neutral bars and earth bar on circuits dedicated to RCDs.
Please ensure circuits and protective devices are WARRANTY adequately identified during installation.
SPECIFICATIONS
Rated Operational Voltage| 415V AC maximum, 50Hz
Maximum Current| 100A
Rated Insulation Voltage| 1000V
Short Circuit Withstand| 10kA
DIMENSIONS
Cover Assembly| 800 x 400 x 35mm
Base Box Dimensions| 754 x 355 x 98mm
**WARRANTY
**
This product is covered by a 1 Year Vynco Warranty -proof of purchase is required.Please contact Vynco for details of returns procedure.
NOTE: This product contains NO user serviceable parts.
EARTH AND NEUTRAL BUSBAR LAYOUT
| Material| Number of Bars| Double Screw Tunnels| Single
Screw Tunnels
Earth Bar| Brass steel| 1| 3| 40
Neutral Bar| Brass steel| 1| 4| 22
RCD Neutral Bar| Brass steel| 8| 1| 3
REMOVING DOOR
STEP 1
Rotate top pin 90°.
STEP 2
Slide pin down to release door. There is no need to remove pin completely.
STEP 3
Lift and remove door
FITTING DIAGRAM
To fit into wall cavity, fold out tabs to set height of enclosure onto studs.
VYNCO INDUSTRIES (NZ) LIMITED CHRISTCHURCH
388 Tuam Street, Phillipstown, Christchurch, 8011
PO Box 9022, Tower Junction, Christchurch 8149
New Zealand
P +64 3 379 9283 F +64 3 379 6838
E sales@vynco.co.nz
AUCKLAND
9 Levene Place, Mount Wellington
PO Box 12 249, Penrose, Auckland 1061
New Zealand
P +64 9 525 6051 F +64 9 525 5799
VYNCO.CO.NZ
Documents / Resources
|
VYNCO VMC51 51 Way Combined Meter
Board
[pdf] Instruction Manual
VMC51, 51 Way Combined Meter Board, VMC51 51 Way Combined Meter Board,
INSV0026, VMC51B, VMC51C
---|---