CAL-ROYAL ES1433 Grade 1 Universal Electric Strike Instruction Manual

June 5, 2024
CAL-ROYAL

ES1433 Series
Electric Strike Installation Instructions

The ES1433 Series electric strikes are designed to accommodate cylindrical locksets with up to3/4″ (19mm) latch throw. The strikes can be configured to fail-safe or fail-secure on site.

Specifications

Operating Voltage 12 / 24VDC
Current Draw 300mA / 12VDC, 150mA / 24VDC
Operating Temperature 32°F to 120°F (0°C to 49°C)
Humidity 0% to 85% Non-condensing
Latch Throw 3/4″(19mm) [ 5/8″(16mm) strike depth, 1/8″(3mm) door gap ]
Keeper Width 1 7/16″ (36mm)
Static Strength 1500 lbs (680Kg)

(UL Witness test: 2000lbs)
Dynamic Strength| 70 ft-lbs
Endurance| 250,000 cycles (UL tested) 1,000,000 cycles (Factory tested)
Performance Level| Destructive Attack: Level I Line Security: Level I
Standby Power: Level I Endurance: Level IV

Fail-Safe/ Fail-Secure Reversible
Change screw position at fail-safe/fail-secure hole to the desired setting.

Frame Application

Model Latch Monitor Body Construction
ES1433 Zinc Alloy

UL Requirements

  • For indoor use only.
  • Wiring methods shall be in accordance with NFPA70.
  • The ES1433 series is intended to be used with UL Listed Exit Hardware.
  • The ES1433 series shall not impair the intended operation of an emergency exit.
  • The ES1433 series shall not impair the operation of panic hardware mounted on the door.

ES1433 Series

**Compatible Locksets

Installation Instructions
**


Measure latch position.| Mark latch position line.| Attach sticker template to the marked centerline.
Cut hole using template.| Install the mounting tabs.| Connect the wires using the crimp connectors, then test the strike,
ensure to give it the correct voltage.

Caution:
The proper gap must be reserved between the strike keeper and latch bolt to prevent failure of the solenoid valve.
Using the Trim Plate
In case of over-cutting, use the enclosed trim plate to cover up any errors.

Installing the Crimp Connectors:

Crimp connectors are provided to make wiring connections easier and more reliable. To install the connectors:

  1. Insert the wires into the connector.
  2. Use a crimping tool or pliers to evenly press down on the head of the connector.

12 / 24 VDC Plug-In Wiring

For 12VDC Operation:
For 24VDC Operation:

DWG # ELG8009, P/2, 20220407

Documents / Resources

| CAL- ROYAL ES1433 Grade 1 Universal Electric Strike [pdf] Instruction Manual
ES1433, Grade 1 Universal Electric Strike, Universal Electric Strike, Electric Strike, ES1433, Strike
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

CAL-ROYAL User Manuals

Related Manuals