ES1433 Series
Electric Strike Installation Instructions
The ES1433 Series electric strikes are designed to accommodate cylindrical locksets with up to3/4″ (19mm) latch throw. The strikes can be configured to fail-safe or fail-secure on site.
Specifications
Operating Voltage | 12 / 24VDC |
---|---|
Current Draw | 300mA / 12VDC, 150mA / 24VDC |
Operating Temperature | 32°F to 120°F (0°C to 49°C) |
Humidity | 0% to 85% Non-condensing |
Latch Throw | 3/4″(19mm) [ 5/8″(16mm) strike depth, 1/8″(3mm) door gap ] |
Keeper Width | 1 7/16″ (36mm) |
Static Strength | 1500 lbs (680Kg) |
(UL Witness test: 2000lbs)
Dynamic Strength| 70 ft-lbs
Endurance| 250,000 cycles (UL tested) 1,000,000 cycles (Factory tested)
Performance Level| Destructive Attack: Level I Line Security: Level I
Standby Power: Level I Endurance: Level IV
Fail-Safe/ Fail-Secure Reversible
Change screw position at fail-safe/fail-secure hole to the desired setting.
Frame Application
Model | Latch Monitor | Body Construction |
---|---|---|
ES1433 | – | Zinc Alloy |
UL Requirements
- For indoor use only.
- Wiring methods shall be in accordance with NFPA70.
- The ES1433 series is intended to be used with UL Listed Exit Hardware.
- The ES1433 series shall not impair the intended operation of an emergency exit.
- The ES1433 series shall not impair the operation of panic hardware mounted on the door.
ES1433 Series
**Compatible Locksets
Installation Instructions
**
Measure latch position.| Mark latch position line.| Attach sticker template to
the marked centerline.
Cut hole using template.| Install the mounting tabs.| Connect the wires using
the crimp connectors, then test the strike,
ensure to give it the correct voltage.
Caution:
The proper gap must be reserved between the strike keeper and latch bolt to
prevent failure of the solenoid valve.
Using the Trim Plate
In case of over-cutting, use the enclosed trim plate to cover up any
errors.
Installing the Crimp Connectors:
Crimp connectors are provided to make wiring connections easier and more reliable. To install the connectors:
- Insert the wires into the connector.
- Use a crimping tool or pliers to evenly press down on the head of the connector.
12 / 24 VDC Plug-In Wiring
For 12VDC Operation:
For 24VDC Operation:
DWG # ELG8009, P/2, 20220407