CAL-ROYAL ES1934 Electric Rim Strikes Instruction Manual

June 5, 2024
CAL-ROYAL

CAL-ROYAL ES1934 Electric Rim Strikes

Specifications

CAL-ROYAL-ES1934-Electric-Rim-Strikes-
fig-12

UL Requirements

  • For indoor use only
  • The ES1934 / ES1912 Series are intended to be used with UL Listed Exit Hardware.
  • The ES1934 / ES1912 Series electric strikes are access control unit accessories, intended to be controlled by an access control system. The access control system’s purpose is to provide a means for controlling the locking and unlocking of external and internal doors of a premise.
  • The ES1934 Series shall not be installed in the fail secure mode unless permitted by the local authority having jurisdiction and shall not interfere with the operation of panic hardware.
  • The Fire Rated ES 1934 Series electric strike is to be used only with UL Listed Rim Type Fire Exit Hardware, Von Duprin LLC, Model 99-F.
  • Remove the Listed Fire Rated Hardware label if the ES1934 Series Electric Strike will be used in the fail-safe operation. Using the above-mentioned strike in fails safe operation negates the fire rating.
  • The ES1934 Series Electric Strike is Fire Rated in Fail Secure operation only.

Surface Installation

CAL-ROYAL-ES1934-Electric-Rim-Strikes-
fig-1

  • Measure 39 13/16″ (1011 mm) up from the finished floor and mark strike centerline on door. Transfer centerline to frame.
  • Align strike on the centerline and mark two slotted holes. Drill holes and install strike to frame.
  • Align template on centerline and against strike.

For Exit Device Already Installed

Model ES1912 is used as example below.

  • a. Measure the exit device latch position on the door.
  • a. Close the door and mark latch position on the frame.
  • b. The latch position line will correspond with the inside of strike keeper as shown.
  • a. Position the strike on the frame according to the marked latch position.
  • b. Use the strike as a template; mark and drill cable access hole and two mounting holes.
  • c. Loosely mount the strike with Phillips flat head screws.
  • a. Check latchbolt interaction and adjust the strike horizontally until the door latches properly.
  • b. Tighten the two mounting screws and mark remaining screw holes.
  • a. Remove the strike and drill holes.
  • b. Connect the wires.
  • c. Insert the blind nuts into the holes and re-install the strike.
  • d. Add spacers to adjust the gap between strike and exit device if necessary.
  • e. Permanently secure the strike with the hex socket cap screws into the blind nuts.

Dimensions

CAL-ROYAL-ES1934-Electric-Rim-Strikes-fig-7

Wiring Diagrams

CAL-ROYAL-ES1934-Electric-Rim-Strikes-fig-8

Latch Monitor (Option)

CAL-ROYAL-ES1934-Electric-Rim-Strikes-fig-9

Installing the Crimp Connectors

CAL-ROYAL-ES1934-Electric-Rim-Strikes-fig-10

Changing Fail-Safe / Fail-Secure

Remove locking screw #1, loosen, slide and tighten sliding screw #2. Reinsert and tighten locking screw #1 to the desired fail-safe or fail-secure setting .CAL-ROYAL-ES1934-Electric-Rim-Strikes-fig-11