Comfort Glow KWD216 VENT-FREE INFRARED GAS WALL HEATER Owner’s Manual
- June 5, 2024
- Comfort Glow
Table of Contents
- Comfort Glow KWD216 VENT-FREE INFRARED GAS WALL HEATER
- WHAT TO DO IF YOU SMELL GAS
- PRODUCT SPECIFICATIONS
- IMPORTANT SAFETY INFORMATION
- PRODUCT FEATURES
- PREPARING FOR INSTALLATION
- PREPARING FOR INSTALLATION
- INSTALLATION
- CONNECTING TO GAS SUPPLY
- CHECKING GAS CONNECTIONS
- FOR YOUR SAFETY READ BEFORE LIGHTING
- LIGHTING INSTRUCTIONS
- Keep control depressed for (30) seconds after pilot lights. Release
- THERMOSTAT GAS CONTROL
- CARE AND MAINTENANCE
- TROUBLESHOOTING
- REPLACEMENT PARTS LIST
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Comfort Glow KWD216 VENT-FREE INFRARED GAS WALL HEATER
WARNING: This appliance is equipped for Natural and Propane gas. Field conversion is not permitted.
WARNING: Do not attempt to access or change the setting of the fuel selection
means.
Access to and adjustment of the fuel selection means must only be performed by
a qualified service person when connecting this appliance to a specified fuel
supply at the time of installation.
Change of the selector setting to other than the fuel type specified at the
time of installation could damage this appliance and render it inoperable.
The installer shall replace the access cover before completing the
installation and operating this appliance.
WARNING: IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
- Do not store or use gasoline or other flammable vapors and Iiquids in vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance.
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air For Combustion and Ventilation section on page 8 of this manual.
INSTALLER:
- Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
- This appliance may be installed in an aftermarket, permanently located, manufactured (mobile) home, where not prohibited by local codes.
- This appliance is only for use with propane or natural gas.
- This appliance is equipped with a simple means to switch between propane and natural gas. Field conversion by any other means including the use of a kit is not permitted. Questions, problems, missing parts? Before returning to your retailer, call our Technical Service Department at 800-776-9425.
WARNING: Read the Installation & Operating Instructions before using this
appliance.
IMPORTANT : Read all instructions and warnings carefully before starting
installation. Failure to follow these instructions may result in possible
injury to persons or a fire hazard and will void the warranty.
PRODUCT SPECIFICATIONS
IMPORTANT SAFETY INFORMATION
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, operate, or service this heater. Improper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
Installation and repair should be done by a qualified service person. The
appliance should be inspected before use and at least annually by a
professional service person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding material, etc. It
is imperative that control compartments, burners and circulating air
passageways of the appliance be kept clean.
- WARNING: Any change to this heater or its controls can be dangerous.
- WARNING: Carefully supervise young children when they are in the room with the heater.
- WARNING: Heater becomes very hot when operating. Children and adults should be alerted to the hazard of high surface temperatures and should stay away to avoid burns or clothing
- ignition Heater will remain hot for a time after shutoff. Allow surfaces to cool before touching.
- WARNING: Make sure any panel, safety screen or guard removed for servicing an appliance is replaced prior to operating the heater
- WARNING: Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors and liquids.
- WARNING: Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
- WARNING: Due to high temperatures, locate this appliance out of traffic and away from furniture and draperies.
This appliance is intended for supplemental heating.
This appliance can be used with propane or natural gas. It is shipped from the
factory adjusted for use with propane.
CARBON MONOXIDE POISONING: Early signs of carbon monoxide poisoning resemble
the flu with headaches, dizziness, or nausea. If you have these signs, the
heater may not be working properly. Get fresh air immediately! Have heater
serviced. Some people are more affected by carbon monoxide than others. These
include pregnant women, people with heart or lung disease, people who are
anemic, those under the influence of alcohol, and those living in high
altitudes.
NATURAL AND PROPANE/LP GAS: Natural and Propane/LP gases are odorless. An
odor-making agent is added to the gas. The odor helps you detect a gas leak.
However, the odor added to the gas can fade. Gas may be present even though no
odor exists. Make certain you read and understand all warnings. Keep this
manual for reference. It is your guide to operating this heater safely.
WARNING:
If the heater is being installed in a residential garage, it must be secured
firmly to the wall, a minimum of 18 in. (457mm) above the floor. The heater
must be located so that it is protected against any possibility of damage by a
moving vehicle, etc.
Raising the heater will reduce BUT NOT eliminate the possibility of lighting
the vapor of any flammable liquids which may be improperly stored or
accidentally spilled. If the smell of gasoline is present, do not operate this
heater until the area has been properly ventilated.
SAFETY INFORMATION
WARNING: Do not use any accessories not approved for use with this heater.
WARNING
This product and the fuels used to operate this product (liquid propane or
natural gas), and the products of combustion of such fuels, can expose you to
chemicals including benzene, which is known to the State of California to
cause cancer and reproductive harm.
For more information go to www.p65Warnings.ca.gov
- Do not place Propane/LP supply tank(s) inside any structure. Place Propane/LP supply tank(s) outdoors.
- All models cannot be installed in a bathroom or bedroom.
- This heater needs fresh air ventilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if not enough fresh air is available. See Air for Combustion and Ventilation, pages 7 through 9. If heater keeps shutting off, see Troubleshooting, pages 23 through 26.
- Keep all air openings in front, top and bottom of heater free of objects and debris to ensure adequate air for proper combustion.
- If heater shuts off, do not relight until you have provided fresh, outside air. If heater keeps shutting off, have it serviced.
- Do not run heater:
- Where flammable liquids or vapors are used or stored.
- Under dusty conditions.
- Before using furniture polish, wax, carpet cleaner, or similar products, turn heater and pilot off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
- Do not use heater if any part has been under water. Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.
- Turn off and unplug heater and let cool before servicing. Only a qualified service person should service and repair heater.
- To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity
- WARNING: Do not allow fans to blow directly into the heater. Avoid any drafts that alter burner flame patterns..
PRODUCT FEATURES
-
SAFETY PILOT
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system.
The ODS/pilot shuts off the heater if there is not enough fresh air and cuts off main burner gas in the event of flame out. -
DUAL FUEL CAPABILITY
Your heater is equipped to operate on either propane or natural gas. The heater is shipped from the factory ready for connecting to propane. The heater can easily be changed to natural gas by having your qualified installer follow the instructions on page 11 and the markings on the heater. -
LEG KIT (SELECT MODELS)
2 support legs and 4 support leg screws are included for floor mounting the heater. See page 13. NOTE: This is an optional accessory and is not required for operation of the heater. -
PIEZO IGNITION SYSTEM
This heater is equipped with a piezo system. -
THERMOSTAT HEAT CONTROL (SELECT MODELS)
The control automatically cycles the burner on and off to maintain a desired room temperature. See page 19. -
FAN KIT (SELECT MODELS)
The fan kit helps to distribute the warmed air into the space more rapidly.
NOTE: This is an optional accessory and is not required for operation of the heater.
State of Massachusetts: The installation must be made by a licensed plumber or
gas fitter in the Commonwealth of Massachusetts. Sellers of unvented propane
or natural gas-fired supplemental room heaters shall provide to each purchaser
a copy of 527 CMR 30 upon sale of the unit.
In the State of Massachusetts, unvented propane or natural gas-fired space
heaters shall be prohibited in bedrooms and bathrooms.
In the State of Massachusetts the gas cock must be a T-handle type. The State
of Massachusetts requires that a flexible appliance connector cannot exceed
three feet in length.
LOCAL CODES
Install and use heater with care. The installation must conform with local
codes or, in the absence of local codes, with the latest edition of The Nation
Fuel Gas Code, ANSI Z223.1/NFPA 54
PREPARING FOR INSTALLATION
Before beginning assembly or operation of the product, make sure all parts are
present. Compare parts with package contents list. If any part is missing or
damaged, do not attempt to assemble, install or operate the product. Contact
customer service for replacement parts.
UNPACKING
-
Remove heater from carton.
-
Remove all protective packaging applied to heater for shipping
-
Verify all contents are present.
NOTE: Support Leg Screw (M415) (Select Models), Wood Screw (ST4.845-16), Expansion Bracket Screw (ST4.8*15-16), and Expansion Bracket come with (2) extra each. -
Check heater for any shipping damage. If heater is damaged, promptly inform dealer where you bought the heater.
WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS
Water vapor is a by-product of gas combustion. An unvented room heater
produces approximately one (1) ounce (30 mL) of water for every 1,000 BTUs (.3
Kw) of gas input
per hour. An unvented room heater is intended as a supplemental heater rather
than a primary heat source. In most supplemental heat applications, the water
vapor does not create a problem.
In most applications, the water vapor enhances the low humidity atmosphere
experienced during cold weather.
The following steps will help ensure that water vapor does not become a
problem:
- Be sure the heater is the proper size for the application, including adequate combustion air and circulation air.
- If there is high humidity, a dehumidifier may be used to help lower the water vapor content of the air.
- Do not use an unvented room heater as the primary heat source.
AIR FOR COMBUSTION AND VENTILATION
CAUTION: This heater shall not be installed in a room or space unless the
required volume of indoor combustion air is provided by the method described
in the National Fuel Gas Code, ANSI Z223.1/NFPA54, the International Fuel Gas
Code, or applicable local codes.
PRODUCING ADEQUATE VENTILATION
All spaces in homes fall into one of the three following ventilation
classifications:
- Unusually Tight Construction
- Unconfined Space
- Confined Space
The information on pages 7 through 9 will help you classify your space and provide adequate ventilation.
Confined and Unconfined Space
A confined space as a space whose volume is less than 50 cu. ft. per 1,000
BTU/hr (4.8 m^3 per kw) of the aggregate input rating of all appliances
installed in that space and an unconfining space as a space whose volume is
not less than 50 cu. ft. per 1,000 BTU/hr (4.8 m^3 per kw) of the aggregate
input rating of all appliances installed in that space. Rooms connecting
directly with the space in which the appliances are installed*, through
openings not furnished with doors, are considered a part of the unconfined
space.
This heater shall not be installed in a confined space or unusually tight
construction unless provisions are provided for adequate combustion and
ventilation air.
- Adjoining rooms are connecting only if there are doorless passageways or ventilation grills between them.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for
combustion and venti-lation. However, in buildings of unusually tight
construction, you must provide additional
fresh air.
Unusually tight construction is defined as construction where:
- walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm (6×10-11kg per pa-sec-m2) or less with openings gasketed or sealed and
- weather stripping has been added on windows that can be opened and on doors and
- caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.
If your home meets all of the three criteria above, you must provide additional fresh air. See “Ventilation Air From Outdoors” (page 9). If your home does not meet all of the three criteria above, proceed to “Determining Fresh-Air Flow For Heater Location”.
PREPARING FOR INSTALLATION
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this worksheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining
rooms with doorless passageways or ventilation grills between the rooms.
-
Determine the volume of the space Length × Width × Height = cu. ft. (volume of space)Example: Space size 20 ft. (length) × 16 ft.(width) × 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space. -
Divide the space volume by 50 cu. ft. to determine the maximum BTU/hr the space can support. ___ (volume of space) ÷ 50 cu. ft.= (Maximum BTU/hr the space can support)
Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum BTU/hr the space can support) -
Add the BTU/hr of all fuel burning appliances in the space.
- Vent-free heater _____ BTU/hr
- Gas water heater* ____BTU/hr
- Gas furnace _____BTU/hr
- Vented gas heater ____BTU/hr Example:
- Gas heater logs __BTU/hr Gas water heater 30,000 BTU/hr
- Other gas appliances*+ ____BTU/hr Vent-free heater + 26,000 BTU/hr
- Total = ____BTU/hr Total = 56,000 BTU/hr
-
Compare the maximum BTU/hr the space can support with the actual amount of BTU/hr used. BTU/hr (maximum the space can support)
BTU/hr (actual amount of BTU/hr used).
Example : 51,200 BTU/hr (maximum the space can support) 56,000 BTU/hr (actual amount of BTU/hr used)
The space in the above example is a confined space because the actual BTU/hr
used is more than the maximum BTU/hr the space can support.
You must provide additional fresh air. Your options are as follows:
- Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See “Ventilation Air From Inside Building,” page 9.
- Vent room directly to the outdoors. See “Ventilation Air From Outdoors”, page 9.
- Install a lower BTU/hr heater if lower BTU/hr size makes room unconfined. If the actual BTU/hr used is less than the maximum BTU/hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
Ventilation Air From Inside Building
This fresh air would come from adjoining unconfined space. When ventilating to
an adjoining unconfined space, you must provide two permanent openings: one
within 12 in. of the wall connecting the two spaces (see options 1 and 2, Fig.
1). You can also remove door into adjoining room (see option 3, Fig. 1).
Follow the National Fuel Gas Code NFPA 54/ANS Z223.1. Air for Combustion and
Ventilation for required size of ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or duct. You must provide
two permanent openings: one within 12 in. of the ceiling and one within 12 in.
of the floor. Connect these items directly to the outdoors or spaces open to
the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code NFPA 54/ANS Z223.1. Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic
has a thermostat-controlled power vent. Heated air entering the attic will
activate the power vent. Rework worksheet, adding the space of the adjoining
unconfined space. The combined spaces must have enough fresh air to supply all
appliances in both spaces.
INSTALLATION
- NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source.
- WARNING: A qualified technician must install heater. Follow all local codes.
- WARNING: Maintain the minimum clearances. If possible, provide greater clearances from the floor, ceiling, and adjoining wall than required.
- CAUTION: This heater creates warm air currents. These currents move heat to wall surfaces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as tobacco smoke, candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may cause walls to discolor.
CLEARANCES TO COMBUSTIBLES
Carefully follow the instructions below. This heater can be mounted on the
wall or on the floor using the support legs (Select models).
WARNING: Maintain the minimum clearances shown in (See Fig. 2). If you can,
provide greater clearances from floor, ceiling, and joining wall.
GAS SELECTION
- CAUTION: The knob to the gas selection means shall not be accessed or adjusted while the appliance is in operation.
- WARNING: Gas selection should only be done by a qualified technician.
- WARNING: The unused regulator must be fitted with a metal plug with a pipe thread sealant.
- WARNING: Failure to plug the unused regulator may result in a fire, property damage, personal injury, or death.
Units to be used with LP
Remove the plug from the inlet of the LP regulator; do not make any further
adjustments. Proceed to installing the gas line as instructed in the Owner’s
Manual.
LP TO NG Conversion
- Before gas conversion, remove screws and access panel for selector valve.
- The gas selector valve should be in the LP position. Push and turn the selector knob be locked in the NG position. DO NOT operate the heater between the locked positions.
- Remove plug from the inlet of the NG regulator.
- If the LP plug was removed previously, apply thread sealant to ensure that there are no leaks and install the NG plug into the inlet of the LP regulator and tighten firmly. (See Fig. 5).
- Replace selector valve access panel.
NG TO LP CONVERSION
- Before gas conversion, remove screws and access panel for selector valve.
- The gas selector valve should be in the NG position. Push and turn the selector knob counter clockwise until the knob locks into the LP position (See Fig. 4). The selector valve must be locked in the LP position. DO NOT operate the heater between the locked positions.
- Remove plug from the inlet of the LP regulator.
- Using thread sealant to ensure there are no leaks, replace plug into the inlet of the NG regulator and tighten firmly (See Fig. 6).
- Replace selector valve access panel.
GAS SELECTION
IMPORTANT: Before proceeding with the installation, the qualified service
technician converting the heater between gas supplies must verify correct
manifold pressure. A reading can be taken using a pressure gauge and the
appropriate pressure tap (See Fig. 7).
INSTALLING FAN (SELECT MODELS)
WARNING: Electrical Grounding Instructions
This appliance is equipped with a three-prong (grounding) plug for your
protection against shock hazard and should be plugged directly into a properly
grounded three-prong receptacle (See Fig. 8).
- Wall mounted heater must be disconnected from gas supply and removed from wall before installing fan accessory. Contact a qualified service person to do this.
- Remove fan knock-out panel using a screwdriver (See Fig. 9). Attach Fan to the rear panel of the heater using the four screws provided.
NOTE: Be sure the rocker switch is positioned in the upper right corner. (See Fig. 10).
This fan is equipped with manual “MAN”
and automatic “AUTO” settings (See Fig. 11 on page 13). Set the rocker switch
to “MAN” for manual mode, allowing the fan to continuously run until the
rocker switch is returned to the OFF “O” position. Set the rocker switch to
“AUTO” for the automatic mode, which will turn the fan on and off based on
ambient room temperature. It may take 5 to 10 minutes for the fan to come on
when the unit is cold.
NOTE: If any of the original wire as supplied with the appliance must be
replaced, it must be replaced with a wire of at least an equal tem-perature
rating. Refer to Fig. 12 on page 13 for wiring diagram.
CAUTION: Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous opera- tion. Verify proper
operation after servicing.
NOTICE: Use of the available optional fan will improve heat circulation
throughout the area being heated.
LOCATING HEATER
This heater is designed to be mounted on a wall or on a floor, using the
Support Legs (Select Models) includ-ed with select models.
For convenience and efficiency, install heater:
- Where there is easy access for operation, inspection, and service.
- n the coldest part of room.
- A minimum of 3′ away from furniture and draperies.
FLOOR MOUNTING (SELECT MODELS)
(Cannot be done in bedroom or bathroom)
(Cannot be used for garage and ice-house heaters) NOTE: This is an optional
accessory and is not required for operation of the heater.
Before installing Support Legs to heater base, please make sure you have the
following items:
(2) Support Legs (4) Support Leg Screws (M4*15)
- Set down a blanket onto the table where the heater will be placed for leg installation to prevent scratch- ing of the table and/or the heater.
- Set back of heater on table with the bottom of heater extending outside the table edge.
- Fasten Support Legs to heater using Support Leg Screws (Fig.13)
Note: If the heater is to be installed directly on carpet-ing, tile or other combustible material, other than wood flooring, the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.
3. Once positioned, secure heater to the floor
using Support Leg Screws (M4*15) and mounting holes found on heater Support Legs (See Fig. 14)
WALL MOUNTING
WARNING: Failure to position the parts in accordance with these diagrams or
failure to use only parts specifically approved with this heater may result in
property damage or personal injury.
Mounting Bracket
The mounting bracket is located separately from the unit, but packed inside
the same box.
Methods For Attaching Mounting Bracket To Wall
Use only the last hole on each end of mounting bracket to attach bracket to wall. Attach mounting bracket to a wall only in one of two ways:
- Attaching to wall stud: This method provides the strongest hold. Insert wood screws (ST.8*45-16) through mounting bracket and into wall studs.
- Attaching to expansion bracket: This method allows you to attach mounting bracket to hollow walls (wall areas between studs) or to solid walls (concrete or masonry).
Decide which method better suits your needs. Either method will provide a secure hold for the mounting bracket.
Marking Screw Locations
- Tape mounting bracket to wall where heater will be located. Make sure mounting bracket is level.
- Mark screw locations on wall (See Fig. 16). Note: Mark only last hole on each end of mounting bracket. Insert (2) wood screws (ST.8*45-16) total through these holes only.
- Remove tape and mounting bracket from wall.
Attaching Mounting Bracket To Wall
Note: Expansion bracket, wood screws (ST.8*45-16), and wall hanging spacers
are in hardware package. The hardware package is provided with heater.
Attaching to Expansion Bracket Method
For attaching mounting bracket to hollow walls (wall areas between studs) or
solid walls (concrete or ma-sonry):
-
Drill holes at marked locations using 5/16-inch drill bit. For solid walls (concrete or masonry), drill at least
1 inch deep. -
Fold wall expansion bracket as shown in (See Fig. 17).
-
Insert wall expansion bracket (wings first) into hole. Tap expansion bracket flush to wall.
-
For thin walls (1/2 inch or less), insert expansion bracket tool into expansion bracket. Push expansion bracket tool to “pop” open expansion bracket wings (See Fig. 18).
IMPORTANT: Do not hammer expansion bracket tool!For thick walls (over 1/2 inch thick) or solid walls, do not pop open wings. -
Place mounting bracket onto wall. Line up last hole on each end of bracket with expansion bracket.
-
Insert expansion bracket screws (ST4.8*15-16) through wall mounting bracket and into expansion brackets.
-
Tighten expansion bracket screws (ST4.8*15-16) until mounting bracket is firmly fastened to wall.
-
Check that the bracket is secure before mounting heater!
Attaching Wall Hanging Spacers to Heater
WARNING: Failure to properly install the wall hanging spacers may result in property damage, personal injury or even death.
- Locate spacer mounting holes on the lower right/left sections of the heater back panel.
- Secure (2) wall hanging spacers to heater back panel using (2) wall hanging spacer screws (M4*25) (See Fig. 19a).
Placing Heater On Mounting Bracket
- Locate two horizontal slots on back panel of heater.
- Place heater onto mounting bracket. Slide horizontal slots onto stand-out tabs on mounting bracket. Be sure spacers rest evenly against wall (See Fig. 19b).
CONNECTING TO GAS SUPPLY
-
WARNING: A qualified service technician must connect heater to gas supply. Follow all local codes.
-
IMPORTANT: This appliance requires a 3/8-inch NPT (National Pipe Thread) inlet connection to the pressure regulator. Never connect the heater to private (non-utility) gas wells, commonly known as wellhead gas.
-
WARNING: Do not overtighten gas connections.
-
CAUTION: Use only new, black iron or steel pipe. Internally tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2-in. diameter or greater to allow proper gas volume to heater. If pipe is too
-
small, undue loss of pressure will occur.
CAUTION: Two gas line installations at the same time are prohibited. The access plate to the switching means shall not be opened while the heater is in operation. -
CAUTION: Check your gas line pressure before connecting heater to gas line. Gas line pressure must be a minimum 6” WC for NG & 11″ WC for LP with a max pressure of 14” WC for NG & 14″ WC for LP. If gas line
-
pressure is higher, regulator damage could occur.
-
CAUTION: Never connect heater directly to an LP supply. This heater requires an external regulator (not supplied). Install the external regulator between the heater and gas supply.
-
CAUTION: Avoid damage to regulator. Hold gas regulator with wrench when connecting into gas piping and/or fittings.
-
CAUTION: Use pipe joint sealant that is resistant to gas (Propane or Natural Gas).
Typical Inlet Pipe Diameters
Use 3/8-inch black iron pipe or greater. Installation must include an
equipment shutoff valve, union, and plugged 1/8-inch NPT tap.
Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream
from heater (see Fig. 20).
IMPORTANT: Install an equipment shutoff valve in an accessible location.
The equipment shutoff valve is for turning on or shutting off the gas to the
appliance.
Apply pipe joint sealant lightly to male threads. This will prevent excess
sealant from going into pipe. Excess sealant in pipe could result in clogged
heater valves.
Install sediment trap in supply line as shown
(See Fig. 20). Place sediment trap where it is within reach for cleaning.
Place sediment trap where trapped matter is not likely to freeze. A sediment
trap traps moisture and contaminants. This keeps them from going into heater
controls. If sediment trap is not installed or is installed wrong, heater may
not run properly.
CHECKING GAS CONNECTIONS
- WARNING: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks immediately.
- WARNING: Never use an open flame to check for a leak. Apply a 50/50 mixture of liquid soap and water to all joints. If bubbles form, there may be a leak. Correct all leaks immediately.
- Pressure Testing Gas Supply Piping System
- Test Pressures In Excess Of 1/2 PSIG ( 3.5kPa )
- The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psi (3.5 kPa).
- Pressure Testing Gas Supply Equal To or less than
- 1/2 PSIG ( 3.5kPa )
- The appliance must be isolated from the gas supply piping system by closing its equipment shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than
- ½ psi (3.5 kPa).
Leak Testing Heater Gas Internal Connections
-
Open equipment shutoff valve (See Fig. 21).
-
Make sure control knob of heater is in the OFF position.
-
Open gas supply tank valve (LP systems).
-
Check all joints from equipment shutoff valve to control valve. Apply 50/50 mixture of
liquid soap and water to gas joints. If bubbles form, there may be a leak. -
Light heater (see Operation, page 18). Check all other internal joints for leaks.
-
Turn off heater (see “To Turn Off Gas to Appliance,” page 19).
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
-
This appliance has a pilot which must be lighted using the Piezo Ignitor. When lighting the pilot, follow these instructions exactly.
-
BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS- Do not try to light any appliance.
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
-
Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician. Forced or attempted repair may result in a fire or explosion.
-
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
LIGHTING INSTRUCTIONS
MANUAL GAS CONTROL
- STOP! Read the safety information above on this page.
- Turn off all electric power to the appliance.
- Push in gas control knob slightly and turn clockwise OFF ” ” position. (See Fig. 22a) NOTE: Knob cannot be turned from PILOT ” ” to OFF ” ” unless knob is pushed in slightly. Do not force.
- Wait (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information above. If you don’t smell gas, go to the next step. Push in gas control knob slightly and turn counterclockwise ” position. (See Fig. 23a) Depress control knob.
- With control knob depressed, repeatedly push down the piezo ignitor ” ” until the pilot lights. The pilot is visible, centered below the main burner, behind the glass panel. (See Fig. 24 on page 19)
- Do not attempt to light the pilot by hand.
Keep control depressed for (30) seconds after pilot lights. Release
control knob.
Note: If pilot goes out repeat steps 3 through 7. Wait (1) minute before
attempting to light pilot again.
If after several tries the pilot still goes out, turn the gas control knob
clockwise to the OFF ” ” position and call your service technician or gas
supplier. OPERATION
LIGHTING INSTRUCTIONS
If the control knob does not pop up when released, stop and immediately and
call your service technician or gas supplier.
- Turn on all electric power to the appliance.
- Turn control knob counter clockwise
THERMOSTAT GAS CONTROL
-
STOP! Read the safety information on the previous page.
-
Turn off all electric power to the appliance.
-
Turn control knob clockwise to “OFF” position. (See Fig. 22b)
-
Wait (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information above. If you don’t smell gas, go to the next step. Turn knob counterclockwise to the “PILOT” position. (See Fig. 23b) Depress control knob.
-
With control knob depressed, repeatedly push down the piezo ignitor until the pilot lights. The pilot is visible, centered below the main burner, behind the glass panel. (See Fig. 24 on page 19)
• Do not attempt to light the pilot by hand. -
Keep control depressed for (30) seconds after pilot lights. Release control knob.
Note: If pilot goes out repeat steps 3 through 7. Wait (1) min-ute before attempting to light pilot again. If after several tries the pilot still goes out, turn the gas control knob clockwise to the “OFF” position and call your service technician or gas supplier. If the control knob does not pop up when released, stop and immediately and call your service technician or gas supplier. -
Turn on all electric power to the appliance.
-
Turn control knob counter clockwise to desired setting.
Burner Patterns (Thermostatic Control)
TO TURN OFF GAS TO APPLIANCE
- Turn off all electric power to the appliance if service is to be performed.
- Push in gas control knob slightly and turn clockwise DO NOT FORCE.
THERMOSTATIC CONTROL OPERATION (SELECT MODELS)
The thermostat used on this heater senses the room tempera-ture. At times the
room may exceed the set temperature. If so, the burner will shut off. The
burner will cycle back on when room temperature drops below the set
temperature. The control knob can be set to any comfort level between “HIGH”
(5) and
“LOW”(1) (See Fig. 25).
MANUAL CONTROL OPERATION
Manual valves remain burning in the HIGH ” ” setting until manually turned to
OFF ” “(See Fig. 25).
INSPECTING BURNERS
Check pilot flame pattern daily when in use and at least yearly by a qualified
service agency.
PILOT FLAME PATTERN
Fig. 26 shows a correct pilot flame pattern. Fig. 27 shows an incorrect pilot
flame pattern. The incor-rect pilot flame is not touching the thermocouple.
This will cause the thermocouple to cool, which shuts the heater off. If pilot
flame pattern is incorrect:
- turn heater off (see “To Turn Off Gas to Appliance” on page 20)
- see Troubleshooting pages 23 through 26.
WARNING: If yellow tipping occurs, your heater could produce increased levels of carbon monoxide. If burner flame pattern shows yellow tipping, follow instructions under BURNER FLAME PATTERN, page 21.
Notice: Do not mistake orange flames with yellow tipping. Dirt or other fine particles enter the heater and burn causing brief patches of orange flame.
BURNER FLAME PATTERN
Fig. 28 shows a correct burner flame pattern. Fig. 29 shows an incorrect
burner flame pattern with lifting, and excessive flame height.
If burner flame is incorrect:
- turn heater off (see “To Turn Off Gas to Appliance”, page 20).
- see Troubleshooting, pages 23 through 26.
CARE AND MAINTENANCE
NOTE: Before servicing you will need to remove the front panel of the heater. There are 4 Philips head screws, 2 on the left side and 2 on the right, securing the front panel to the heater (See Fig. 30). Always allow the unit to cool for at least thirty minutes before attempting to remove the front panel.
- WARNING: Turn off heater, unplug electrical cord and let cool before servicing.
- CAUTION: You must keep control areas, burner, and circulating air passageways of heater clean. Inspect these areas of heater before each use. Have heater inspected yearly by a qualified service person. Heater may need more frequent cleaning due to excessive lint from carpeting, bedding material, pet hair, etc.
- WARNING: Failure to keep the primary air opening(s) of the burner(s) clean may result in sooting and property damage.
CLEANING ODS/PILOT AND BURNER
Use a vacuum cleaner, pressurized air, or a small, soft bristled brush to
clean tile face, orifice and primary burner. Look into burner opening and
ensure that it is clean.
CLEANING BURNER PILOT AIR INLET HOLE
We recommend that you clean the unit every three months or after 2,500 hours
of operation. We also recommend that you keep the burner tube and pilot
assembly clean and free of dust and dirt. To clean these parts we recommend
using compressed air no greater than 30 PSI. You can use a vacuum cleaner in
the blow position. If using compressed air in a can, please follow the
directions on the can. If you don’t follow directions on the can, you could
damage the pilot assembly.
CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This
can damage ODS/ pilot unit.
- Shut off the unit, including the pilot. Allow the unit to cool for at least thirty minutes.
- Remove 4 screws – 2 screws on each side of the front panel.
- Pull front panel forward.
- Blow air through the ports/slots and holes in the burner. Also clean the pilot assembly. A yellow tip on the pilot flame indicates dust and dirt in the pilot assembly. There is a small pilot air inlet hole about two inches from where the pilot flame comes out of the pilot assembly (see Fig. 26 & 27 on page 20). With the unit off, lightly blow air through the air inlet hole. You may blow through a drinking straw if air is not available.
- Replace front panel when completed, using the screws removed.
CLEANING CABINET AIR PASSAGEWAYS
Use a vacuum cleaner or pressurized air to clean.
CLEANING FAN (Select models)
Carefully use a vacuum cleaner or compressed air to keep fan compartment and
blades free of dust and debris.
NOTE: The fan motor is pre-lubricated for extended bearing life and requires
no further lubrication.
CLEANING EXTERIOR
Use a soft cloth dampened with a mild soap and water mixture. Wipe the cabinet
to remove dust.
TROUBLESHOOTING
WARNING: If you smell gas:
- Shut off gas supply.
- Do not try to light any appliance.
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
IMPORTANT: Operating heater where impurities in air exist may create odors. Cleaning supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These fumes may mix with combustion air and create odors.
- WARNING: Make sure that power is turned off before proceeding.
- WARNING: Turn off and let cool before servicing. Only a qualified service person should service and repair heater.
PROBLEM | POSSIBLE CAUSE | CORRECTIVE ACTION |
---|---|---|
When Ignitor Module is pressed in, there is no spark at ODS/pilot. | 1. |
Ignitor electrode is
positioned wrong.
2. Ignitor electrode is broken.
3. Ignitor electrode is not
connected to ignitor cable.
4. Ignitor cable is pinched or wet.
5. Damaged ignitor cable.
6. Bad ignitor module or ignition module.
| 1. Replace ODS.
2. Replace ODS.
3. Replace ignitor cable
4. Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry.
5. Replace ignitor cable.
6. Replace ignitor module or ignition module.
Unit shuts off after running a few minutes.| 1. Gas supply is turned off or equipment shutoff valve is closed.
2. Control knob not fully pressed in while pressing Ignitor Module.
3. Air in gas lines when
installed.
4. ODS / pilot is clogged.
5. Gas regulator setting is not correct.
6. Control knob not in PILOT
position.
7. Depleted gas supply (propane).
8. Incorrect gas setting regulator
or selector valve.
| 1. Turn on gas supply or open equipment
shutoff valve.
2. Fully press in control knob while
pressing Ignitor Module.
3. Continue holding down control knob. Repeat igniting operation until air is removed.
4. Clean ODS/pilot (see Care and Maintenance, page 22) or replace ODS/pilot assembly.
5. Replace gas regulator.
6. Turn control knob to PILOT position.
7. Contact local propane/LP gas company.
8. Call qualified service technician.
PROBLEM | POSSIBLE CAUSE | CORRECTIVE ACTION |
---|
ODS/pilot lights
but flame goes out when control knob is released.
| 1. Control knob is not fully
pressed in.
2. Control knob is not pressed
in long enough.
3. Equipment shutoff valve is
not fully open.
4. Thermocouple connection is loose.
5. Thermocouple damaged.
6. Control valve damaged.
7. Wrong Gas Setting
| 1. Press in control knob fully.
2. After ODS/pilot lights, keep control knob pressed in 30-60 seconds.
3. Fully open equipment shutoff valve.
4. Hand tighten until snug, and then tighten ¼ turn more.
5. Replace thermocouple.
6. Contact customer service.
7. Correct Gas Selection
Burner(s) does not light after ODS/pilot is lit.| 1. Thermostat setting too low.
2. Burner orifice is clogged.
3. Burner orifice diameter is
too small.
4. Inlet gas pressure is too low.
| 1. Turn thermostat knob to a higher setting.
2. Clean burner orifice (see Care and Maintenance, page 22) or contact customer service.
3. Contact customer service.
4. Contact your gas supplier.
Delayed ignition of burner(s).| 1. Manifold pressure is too low.
2. Burner orifice is clogged.
| 1. Contact your gas supplier.
2. Clean burner (see Care and Maintenance, page 22) or contact customer service.
Burner backfiring during combustion.| 1. Burner orifice is clogged or
damaged.
2. Burner is damaged.
3. Gas regulator is damaged.
| 1. Clean burner orifice (see Care and Maintenance, page 22 or contact customer service.
2. Contact dealer or customer service.
3. Replace gas regulator.
High yellow flame during burner combustion| 1. Not enough air.
2. Gas regulator is defective.
3. Wrong gas type selected.
| 1. Check burner for dirt and debris. If found, clean burner (see Care and Maintenance, page 22).
2. Replace gas regulator.
3. See Gas Selection, page 11.
Gas odor during
combustion.
| 1. Foreign matter between control valve and burner.
2. Gas leak. (See Warning Statement at top of page 23).
| 1. Take apart gas tubing and remove foreign
matter.
2. Locate and correct all leaks (see “Check- ing Gas Connections,” page 17).
Heater produces a clicking/ticking noise just after burner is lit or shut off.| 1. Metal is expanding while heating or contracting while cooling.| 1. This is common with most heaters. If noise is excessive, contact qualified service technician.
PROBLEM| POSSIBLE CAUSE| CORRECTIVE ACTION
White powder resi- due forming within burner box or on adjacent walls or
furniture.| 1. When heated, the vapors from furniture polish, wax, carpet
cleaners, etc., turn into white powder residue.| 1. Turn heater off when
using furniture polish, wax, carpet cleaner or similar products.
Heater produces
unwanted odors.
| 1. Heater is burning vapors from paint, hair spray, glues, etc. See IMPORTANT state- ment, page 22.
2. Gas leak. See Warning
Statement, page 23.
3. Low fuel supply.
| 1. Ventilate room. Stop using odor causing products while heater is running.
2. Locate and correct all leaks (see “Checking Gas Connections,” page 17).
3. Refill supply tank (Propane /LP models).
Heater shuts off in use (ODS oper- ates).| 1. Not enough fresh air is
available.
2. Low line pressure.
3. ODS/pilot is partially clogged.
| 1. Open window and/or door for
ventilation.
2. Contact local gas supplier.
3. Clean ODS/pilot (see Care and Maintenance, page 22).
Gas odor exists even when control knob is in OFF posi- tion.| 1. Gas leak. See Warning
Statement at top of page 22.
2. Control valve is defective.
| 1. Locate and correct all leaks (see “Checking Gas Connections”, page 17).
2. Contact customer service.
Moisture/conden- sation noticed on windows.| 1. Not enough combustion/
ventilation air.
| 1. Refer to “Air for Combustion and Ventilation” requirements, page 7.
Slight smoke or odor during initial operation| 1. Residues from manufacturing
process.| 1. Problem will stop after a few hours of
operation.
Heater produces a whistling noise when burner is lit.| 1. Turning control knob to high (5) position when burner is cold.
2. Air in gas line.
3. Air passageways on heater are blocked.
4. Dirty or partially clogged burner orifice.
| 1. Turn control knob to low (1) position and let warm up for a minute.
2. Operate burner until air is removed from line. Have gas line checked by local propane/LP gas company.
3. Observe minimum installation clearances (Fig. 3, page 10)
4. Clean burner (see Care and Maintenance, page 22) or contact customer service.
PROBLEM | POSSIBLE CAUSE | CORRECTIVE ACTION |
---|
Fan is not spinning.
(Select models)
| 1. There is no power to the fan.
2. Fan is set to “AUTO”.
3. Fan motor is bad.
| 1. Verify fan is plugged in and set to “MAN” or “AUTO”.
2. Allow 5-10 minutes for fan to engage.
3. Replace fan.
Fan is making a loud noise. (Select models)| 1. Fan housing or blades are dirty.
2. Fan rotation is blocked.
3. Defective fan.
| 1. See “Cleaning Fan”, page 22.
2. Verify wiring is not in fan path.
3. Replace fan.
QUALIFIED INSTALLING AGENCY
Only a qualified agency should perform installation and replacement of gas
piping, gas utilization equipment or accessories, and repair and servicing of
equipment. The term “qualified agency” means any individual, firm,
corporation, or company that either in person or through a representative is
engaged in and is responsible for:
- Installing, testing, or replacing gas piping or
- Connecting, installing, testing, repairing, or servicing equipment; that is experienced in such work; that is familiar with all precautions required; and that has complied with all the requirements of the authority having jurisdiction.
REPLACEMENT PARTS LIST
For replacement parts, call our customer service department at 1-814-643-1775, 8:30 a.m. – 4:30 p.m., CST, Monday – Friday.
WARNING : Only use genuine replacement parts from the World Marketing of America, Inc. Using any parts other than the original replacement parts may result in property damage, personal injury or even death.
Item No.| | | | Part Number|
---|---|---|---|---|---
Description| Qty| KWD216| KWD326
KWDB322
| KWD526 KWDB542
1| Front Panel Assembly| 1| AQ000258| AQ000257| AQ000256
2| Burner Assembly| 1| AQ000137| AQ000065| AQ000022
3| ODS Assembly (Complete)|
3-1| ODS -(NG) Natural Gas Pilot| 1| IR30K-22(NG)| IR30K-22(NG)| IR30K-22(NG)
3-2| ODS – (LP) Propane Gas Pilot| 1| IR30K-22(LP)| IR30K-22(LP)| IR30K-22(LP)
4| ODS Connector Harness| 1| IR30K-22-01(L=700)| IR30K-22-01(L=700)|
IR30K-22-01(L=700)
5| Thermostatic Gas Valve, SIT 630| 1| 0630560| 0630560| 0630560
6| Manual Gas Valve| 1| N/A| N/A| N/A
7| Gas Selector Valve| 1| GH01| GH01| GH01
8| Regulator Bracket| 1| AQ000015| AQ000015| AQ000015
9| Regulator, (LP) Propane 10″ WC| 1| GR-130A(12K)| GR-130A(18K)| GR-130A(30K)
10| Regulator, (NG) Natural Gas 5″ WC| 1| GR-130(12K)| GR-130(18K)|
GR-130(30K)
11| Front Grille| 1| AQ000264| AQ000263| AQ000250
12| Wall Mounting Bracket| 1| AQ000108| AQ000006| AQ000006
13| Piezo| 1| AQ000247| AQ000247| AQ000247
14| Knob, Selector Valve| 1| AQ000251| AQ000251| AQ000251
15| Support Legs (Select Models)| 2| AQ000351| AQ000351| AQ000351
16| Fan Assembly (Select Models)| 1| AQ000232| AQ000232| AQ000232
17| Hardware Pack| 1| AQ000367| AQ000367| AQ000367*
18| Nozzle – LP| 1| IR12K-LP| IR18K-LP| IR30K-LP
19| Nozzle – NG| 1| IR12K-NG| IR18K-NG| IR30K-NG
World Marketing of America, Inc. PO Box 192, Route 22 West
Mill Creek PA 17060-0192
(Tel) 1-800-776-9425
Register Online At:
www.worldmkting.com