SIEMENS DXR1.E09PDZ Compact actuating room automation stations, BACnet/IP, AC 24 V User Manual
- June 4, 2024
- SIEMENS
Table of Contents
Desigo™ Room Automation
Compact actuating room automation stations, BACnet/IP,
AC 24 V (Actuating DXR)
DXR1.E09PDZ-112, DXR1.E09PLZ-112, DXR1.E09PDZ-113
Combination of room automation station and actuator for buildings with increasing demand on functionality and flexibility in Room Automation, VAV and FPB applications.
- Compact, configurable room automation station in combination with actuator for HVAC
- QMX1.M34H room unit and QMA1.N30H room sensor
- BACnet IP communications (BTL certified)
- 2-port Ethernet switch
- USB interface
- Operating voltage AC 24 V
- Built-in 5 or 10 Nm actuator
- Internal 0…500 Pa differential pressure sensor
- Plug-in terminal blocks
Features
Configurable
The DXR1.. automation stations provide the infrastructure for systems and
application-specific functions which can be configured.
Compact series
The compact build allows direct mounting on the damper shaft. It is designed
for VAV and FPB.
Plug-in terminal blocks
Plug-in terminal blocks for easy exchange of room automation stations.
Integrated actuator
The actuator gear base is integrated into the housing of the actuating XDR. It
supports dampers with up to 5 or 10 Nm torque.
Use
Desigo Room Automation offers the highest level of flexibility for energy-
optimized solutions while satisfying requirements for temperature control,
ventilation and comfort using standard tools and established workflows.
Pre-installed application types
- Variable (VAV), Fan-Powered Box (FPB), and constant air volume flow
– With staged and modulating electric heating
– With modulating hot water / chilled water with a room or supply air temperature control
Application options
- Separate temperature and air volume flow setpoints for all 4 operating modes
- Separate minimum and maximum cooling and heating flow setpoints
- Single-stage, multi-stage or variable fan control (FPB/DXR1.E09PDZ-113)
- Chilled water and hot water valve
- Extract air volume flow control
Functions
The selected application and its parameters as well as input and output
configuration determine the automation station’s functionality.
A detailed description of functionality is available in the ABT (Automation
Building Tool) online help.
Communication
-
2-port Ethernet switch for cost-effective cabling via line topology.
Note: DXR1 supports cabling based on daisy chain topology. The max. the number is 20 devices and in the event of a failed automation station, all other stations are no longer reachable. DXR1 can be cabled as ring topology if higher reliability is required. This requires support for layer 2 switches RSTP (Rapid Spanning Tree Protocol) as well as SNMP monitoring and that any loss of the superposed system is reported. In the event of a fault, switching the communication paths can take between 10 and 30 seconds. DXR1 routes the RSTP protocol for the switches. It does not actually process the RSTP protocol. Further information can be found in the Application Guide for BACnet Networks in Building Automation (A6V11159798). -
USB connection for service, commissioning, and firmware download.
LED indication
LED | Color | Activity | Function |
---|---|---|---|
Run | Green | Steady ON | Device is ready for operation |
Steady OFF | Device is not powered | ||
Regular flashing | Start-up or the program is stopped | ||
Red | Steady OFF | OK | |
Steady ON | Program error Hardware fault | ||
Rapid flashing | Wrong or corrupt software No application loaded | ||
Blinking per wink command | Physical device identification |
**![DXR1E09PDZ Compact actuating room automation stations BACnet IP, AC 24 V
- fig2](https://manuals.plus/wp-content/uploads/2022/08/DXR1E09PDZ-Compact- actuating-room-automation-stations-BACnet-IP-AC-24-V-fig2.png)**
Service button (SVC)
Physical identification on the network.
Technical / Mechanical design
1| Service button (SVC) for sending device identification| 2| 2 UIs (universal
input), 1 AO (analog output)
---|---|---|---
3| Power supply| 4| RJ45 interface for room unit
5| 4 DOs (digital Triac output)| 6| Status information LED (bi-color)
7| 2-port Ethernet switch| |
Housing
The housing consists essentially of flame retardant, non-brominated plastic.
Type summary
Product No.| Stock No.| Inputs| Outputs| Description|
Quantity
---|---|---|---|---|---
DXR1.E09PDZ-112 (5 Nm)| S55499-D456| 2 universal inputs| 4 digital outputs,
1 analog output| VAV application| Single package / multiple package (10)
DXR1.E09PLZ-112 (10 Nm)| S55499-D742| 2 universal inputs| 4 digital outputs,
1 analog output| VAV application| Single package / multiple package (10)
DXR1.E09PDZ-113 (5 Nm)| S55499-D457| 2 universal inputs| 4 digital outputs,
1 analog output| FPB application| Single package/multiple package (10)
Ordering
When ordering, indicate product number, stock number and description.
Equipment combinations
Product No. | Stock No. | Designation | **Datasheet*** |
---|---|---|---|
QMA1.N30H | S55499-D464 | Room temperature sensor for DXR1.. (without LCD) |
A6V11393922
QMX1.M34H| S55499-D465| Room unit for DXR1.. (with LCD)| A6V11393927
- The documents can be downloaded from http://siemens.com/bt/download by specifying the
Datasheet number as shown in the above table.
Product documentation
Topic | Title | Document ID: |
---|---|---|
Installation, cable length, topology | Desigo Room Automation installation | |
guide | CM111043 | |
Engineering and commissioning | ABT online help | N/A |
Installation instruction | Mounting instructions | A6V11393918 |
Commissioning | Quick guide | A6V11526405 |
Product environmental declaration | A6V11805930 | |
EU declarations (CE) | A6V11791489 |
Documents such as environmental declarations, CE declarations, etc., can be downloaded at the following Internet address: http://siemens.com/bt/download
Notes
Security
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal
injury and property damage.
- Observe national provisions and comply with the appropriate safety regulations.
- Use only properly trained technicians for mounting, commissioning and servicing.
Engineering
Identification
Each device has a unique serial number to ensure efficient commissioning. It
is provided on the adhesive barcode reader. The serial number can be read
directly into the engineering tool using a barcode reader.
Wiring
Wiring must be sufficiently insulated to the available rated voltage. The
sizing and fusing of the wiring depend on the connected load.
Mounting
The automation station is mounted directly on a damper shaft.
See the mounting instructions (document ID: A6V11393918) for detailed
information.
Differential pressure sensor
-
Avoid bends and pressure when attaching the tube.
-
Connect the “+” connection on the side with the higher pressure and the “-” connection on the side with the lower pressure.
-
Connection tubes (interior diameter) of 4 mm.
Air tube connection kit DXA.T50 for connection of tubes with 6.5 mm (interior diameter). -
The maximum tube length is 2 m.
Installation
Applies to devices with supply output (AC 24 V or mains voltage) such as Triac
output or output to supply a field device.
WARNING
No internal line protection for supply lines to external consumers
Risk of fire and injury due to short-circuits
- Adapt the line diameters as per local regulations to the rated value of the installed fuse.
Maintenance
The controller is maintenance-free.
Disposal
The device is considered an electronic device for disposal in accordance with European Directive and may not be disposed of as domestic waste.
- Use only designated channels for disposing of the devices.
- Comply with all local and currently applicable laws and regulations.
Warranty
Technical data on specific applications are valid only together with Siemens products listed under “Equipment combinations”. Siemens rejects any and all warranties in the event that third-party products are used.
Technical data
Power data
Power supply
Operating voltage (SELV/PELV)| AC 24 V +/-20%
Frequency| 50 or 60 Hz
Power consumption| 7.5 VA max.: DXR1.E09PDZ-112, DXR1.E09PDZ-113
8 VA max.: DXR1.E09PLZ-112
Transformer requirements and recommended voltages
Type| Class 2, AC 24 V, 50 / 60 Hz, SELV, PELV
Functional data
Functional data
Nominal torque| 5 Nm / 10 Nm
Nominal rotary angle| 90 °
Maximum rotary angle| 95 ° ± 2 °
Runtime for 90 ° rotary angle| 150 s
Shaft size| 8…16 mm, round
8…10 mm, round (with centering insert) 6…12.8 mm square
Minimum shaft length| 20 mm
Universal inputs
Analog inputs: DC 0…10 V
Operating range| 0…10 V
Resolution| 10 mV
Analog inputs: sensor
Type| Measuring range| Accuracy| Resolution
LG / DIN-Ni 1000| 0…50 ℃| +/- 0.5 K at 25 ℃| 0.1 K at 25 ℃
Pt1K, 375 / 385
NTC10K / NTC100K
Digital inputs
0/1 digital signal (binary)| For potential free contacts
Sampling voltage/current| DC 15 V, 7 mA
Digital inputs
Contact resistance| Max. 200 Ω (closed) Min. 50 kΩ (open)
Delay| 10 ms
Pulse frequency| Max. 20 Hz
Outputs
Analog output
Control range| 0…10 V
Resolution| 50 mV
Output current| Max. 1 mA
Triac outputs
Number of channels| 4
Type| Requires AC 24 V source to allow switching: switching to phase (AC 24 V)
or neutral (⏊)
Current rating| 0.5 A max. per channel
Voltage rating| AC 24 V +/-20 %
Max. load| 12 VA per channel
Pressure sensor
Pressure sensor
Measurement range| 0…500 Pa
Sample rate| ≤ 500 ms
Overload range| 0…100 kPa
Measuring range accuracy Zero point accuracy Resolution| 3 %0.2 Pa 12 Bit
Connections
Interfaces
Ethernet| Plugs: dual RJ45, 10M/100M fast Ethernet Interface type: IEEE 802.3
compliance Cable type: 100M STP CAT 5
USB (2.0)| Type Micro B
Interface for room unit (QMA1.N30H and QMX1.M34H)| RJ45 (shield CAT 5-E) Max.
wiring length: 30 m
Wiring connections
Wiring lengths for signals| Signal lines: max. 80 m For analog inputs: max. 30 m
Conformity
Ambient conditions and protection classification
Classification per IEC/EN 60730
Function of automatic control devices Pollution degree
Overvoltage category| Type 1
2
III
Design type| Device suited for use with equipment of safety classes I and II
Degree of protection of housing to IEC EN 60529 Room automation station|
IP20
Climatic ambient conditions
Transport (packaged for transport) as per IEC EN 60721-3-2
Operation as per IEC/EN 60721-3-3| Class 2K3
Temperature -25…70 °C
Air humidity 5…95 % (non-condensing)
Class 3K5 Temperature -5…50 °C
Air humidity 5…95 % (non-condensing)
Mechanical ambient conditions Transport as per IEC/EN 60721-3-2 Operation as
per IEC/EN 60721-3-3| Class 2M2 Class 3M2
Standards, directives and approvals
Product standard| IEC/EN 60730-1
Automatic electronic controls for household and similar use
EU conformity (CE)| A6V11791489
RCM conformity| A6V11791498
EAC conformity| Eurasian conformity
UL Approbation
Federal Communications Commission| UL as per UL916, http://ul.com/database
cUL as per CSA – C22.2 No. 205
FCC CFR 47 Part 15 Class B
ICES003| CAN ICES-3 (B)/NMB-3(B)
Environmental compatibility| The product environmental declaration
(A6V11805930*) contains data on environmentally compatible product design and
assessments (RoHS compliance, materials composition, packaging, environmental
benefit, disposal).
- The documents can be downloaded from http://siemens.com/bt/download.
FCC regulations
Modification of this device to receive cellular radiotelephone service signals
is prohibited under FCC rules and federal law.
This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more
of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Statement
This device complies with part 15 of the FCC Rules. Operation is subject to
the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
General
General information
Color| Light gray
Dimensions| L × W × H = 137 × 143 × 82 mm
Weight| Net weight: 631.9 g Gross weight: 852.9 g
Diagrams
Connection terminals
DXR1.E09PDZ-112, DXR1.E09PLZ-112 and DXR1.E09PDZ-113
Pin | Description | Terminal |
---|---|---|
1, 2 | IP connection | **** |
USB | USB interface | **** |
81…82 power 24 V~ | Power supply AC 24 V | V~ |
System neutral (must always be grounded at the transformer) | ⏊ | |
64…66 inputs | Universal inputs | X1, X2 |
62, 63 outputs | DC 0…10 V output | Y10 |
54…56 Triac outputs | Digital output, switching to phase (AC 24 V ) or neutral | |
(⏊) | Y3, Y4 | |
57…59 Triac outputs | Digital output, switching to phase (AC 24 V ) or neutral | |
(⏊) | Y5, Y6 | |
Room unit connection | RJ45 interface | |
ΔP differential pressure detector | Connected to the higher pressure | P1+ |
Connected to the lower pressure | P1- | |
Service | Service button | SVC |
Display | Operation LED | RUN |
Dimensions
Dimensions in mm
|
---|---
Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd, 2019
Technical specifications and availability subject to change without notice.
Document ID A6V11393931_en–_f
Edition
2021-11-01
References
- Smart Information Delivery
- Product Sourcing and Certifications Database | UL Solutions
- Building technology - Siemens Global
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>