SIEMENS A-Series Industrial Electric Actuator Instructions

October 30, 2023
SIEMENS

SIEMENS A-Series Industrial Electric Actuator

Technical Instructions

Document No. A6V11937852 August 23, 2022

Description| The A-Series quarter-turn industrial electric actuator features a compact, reliable design that mounts directly to Siemens resilient seat butterfly valves without the need for brackets and linkages. Available in torque outputs from 600 to 18,000 lb-in (68 to 2,033 Nm), 24V and 120 Vac, Two-position (On/Off) and Modulating units all in NEMA 4x and IP65-rated housings.
---|---
Features| ·         Compact, lightweight design and direct mounting

·         High visibility Beacon position indicator

·         Manual, declutchable override handwheel

·         Terminal strip for cable terminations

·         Servo NXT option for modulating control

·         Travel limit cams adjustable by hand or screwdriver

·         UL-approved (120 Vac only)

·         On/off or modulating control

·         Available in 120, 24 Vac 50/60 Hz, single-phase, 24 Vdc voltages

·         Output torque 600 lb-in (68 Nm) to 18,000 lb-in (2,033 Nm)

·         ISO 5211 for direct mounting

·         All actuators include a heater to prevent condensation build-up

·         All modulating units include a feedback potentiometer

Servo NXT Features (for Modulating Actuators)| ·         Provides precise modulating control of valve position

·         Single Finger Technology (SFT) menu-driven, pushbutton, programming with LED confirmation of all settings:

o    Input Control – 4 to 20 mA, 0 to 10 Vdc, 0 to 5 Vdc or 2 to 10 Vdc

o    Position Feedback – 4 to 20 mA, 0 to 10 Vdc, or 0 to 5 Vdc

o    Auto Calibrating

o    Fail Position

§   Loss of supply power – fail-in-place

§   Loss of control signal – selectable

o    Adjustable speed control

·         Including:

o    Manual mode

o    Onboard signal generator to simplify field set-up

o    Fault display – Simplifies troubleshooting

o    Stall detection – Eliminates mechanical damage in case of obstruction or bad switch settings

·         Optical isolation of all inputs/outputs

o    Provides interoperability with all controllers

o    Earth ground tolerant

o    Allows for parallel operation

Ordering| Actuators can be ordered separately or together with a valve as an assembly.

Product Numbers

Table 1. A-Series Industrial Electric Actuators, 24V.

Product Number| Operating Mode| Voltage 50/60 Hz| Torque| **90° Stroke Time*| Current Draw (Amps)
---|---|---|---|---|---
(lb-in)| (Nm)| Full Load| Locked**

Rotor

A126.600| ****

On/Off

| ****

24 Vac/dc

| 600| 68| 60 sec. AC

40 sec. DC

| 1.80| —
A126.2K| 2,000| 226| 60 sec.| 2.00| —
A126.5K| 24 Vac| 5,000| 565| 60 sec.| 4.00| —
A166.600| Modulating| 24 Vac| 600| 68| 60 sec.| 1.80| —
A166.2K| 2,000| 226| 60 sec.| 2.00| —
A166.5K| 5,000| 565| 60 sec.| 4.00| —

  • Operating times shown are with 60 Hz power supply. Actuators with 50 Hz power supply will be 20% slower.

Table 2. A-Series Industrial Electric Actuators, 120V.

Product Number| Operating Mode| Voltage 50/60 Hz| Torque| **90° Stroke Time*| Current Draw (Amps)
---|---|---|---|---|---
(lb-in)| (Nm)| Full Load| Locked**

Rotor

A226.600| ****




On/Off

| ****




120 Vac

| 600| 68| 30 sec.| 0.80| 1.00
A226.1K| 1,200| 135| 30 sec.| 0.78| 2.10
A226.2K| 2,000| 226| 30 sec.| 1.00| 2.10
A226.3K| 3,000| 339| 30 sec.| 1.20| 3.00
A226.5K| 5,000| 565| 30 sec.| 1.60| 3.00
A226.6K| 6,500| 734| 30 sec.| 2.30| 3.10
A226.13K| 13,000| 1,470| 110 sec.| 2.30| 3.10
A226.18K| 18,000| 2,034| 110 sec.| 2.50| 3.10
A266.600| ****




Modulating

| ****




120 Vac

| 600| 68| 30 sec.| 0.80| 1.00
A266.1K| 1,200| 135| 30 sec.| 0.78| 2.10
A266.2K| 2,000| 226| 30 sec.| 1.00| 2.10
A266.3K| 3,000| 339| 30 sec.| 1.20| 3.00
A266.5K| 5,000| 565| 30 sec.| 1.60| 3.00
A266.6K| 6,500| 734| 30 sec.| 2.30| 3.10
A266.13K| 13,000| 1,470| 110 sec.| 2.30| 3.10
A266.18K| 18,000| 2,034| 110 sec.| 2.50| 3.10

  • Operating times shown are with 60 Hz power supply. Actuators with 50 Hz power supply will be 20% slower.

NOTE: 13K and18K torque models are available starting July 2020.

Warning/Caution Notations

WARNING:|  | Personal injury or loss of life may occur if you do not perform a procedure as specified.
---|---|---
CAUTION:|  | Equipment damage may occur if you do not perform a procedure as specified.

CAUTION:
Do not install or use the A-Series Industrial Electric Actuator in or near environments where corrosive substances or vapors could be present. Exposure of the electric actuator to corrosive environments may damage the internal components of the device and will void the warranty.

Application
These actuators are ideal for use on valves for chillers, cooling towers, boilers, heat exchangers and other indoor or outdoor applications. The actuators’ advanced electronics assure reliable compatibility with virtually any analog control signal used in today’s building automation and temperature control systems. All Siemens A-Series Industrial actuators are NEMA 4X rated for protection against the elements and are suitable for outdoor applications. The NEMA 4x rated housing prevents any water ingress in outdoor applications. The heater prevents any condensation build-up inside the housing.

Warning/Caution Notations| WARNING:|  | Personal injury or loss of life may occur if you do not perform a procedure as specified.|
---|---|---|---|---
 | CAUTION:|  | Equipment damage may occur if you do not perform a procedure as specified.|

|

CAUTION:

Do not install or use the A-Series Industrial Electric Actuator in or near environments where corrosive substances or vapors could be present. Exposure of the electric actuator to corrosive environments may damage the internal components of the device and will void the warranty.

|
A-Series Industrial Electric Actuator|
Specifications

Operating Conditions

| Ambient Temperature                   -20 to 150°F (-29° to 65°C)

Fail Position                                Loss of supply power – fail-in- place Motor Insulation

120 Vac                        Class F, 311°F (155°C) thermal trip at

275°F (135°C)

24 Vac/dc                      Class B, Slow Blow Fuse 5A @ 250 Vac

|
Physical Description| Housing                                      ASTM B85 Pressure Die Cast Aluminum, Polyester Powder Coated

Motor

120 Vac                       Single-Phase, Reversible, Permanent Split Capacitor Induction Motor

24 Vac/Vdc                  Single-Phase, Permanent Magnet-Brush D.C. Motor

Auxiliary/Limit Switches SPDT

120 Vac                        10A- 1/3 HP

12 Vdc                          2A

Terminal Strip

Switch Plate                  12 to 22 AWG (2.0 to 0.65 mm)

Servo                           14 to 24 AWG (1.63 to 0.51 mm) Heater 5-Watt, PTC style

Dimensions and weight                 See Dimensions.

Enclosure                                    Designed to meet NEMA Type 4, 4x and IP65 specifications

Travel stops                                Externally adjustable at both 0 and 90 degrees. Conduit entries

600 lb-in                        Two 1/2” NPT (BSP)

1200 lb-in and higher      Two 3/4” NPT

Manual operation                         Pull to engage, push to disengage –

__30:1 drive ratio, 12 and18K lb.-in. models are 90:1

|
Certifications|  |  | UL508 certified (120 Vac only)|

Servo Specifications (for Use with Modulating Actuators)

Power Requirements| 120 Vac 50/60 Hz +/- 10%

24 Vac 50/60 Hz +/- 10%

24 Vdc -10%, +30%

5 VA average (no load)

Fuse: 5A Slow Blow 5 mm × 20 mm

---|---
Input Signal| Control Signal                              4 to 20 mA, 0 to 10 Vdc, 0 to 5 Vdc, 2 to

10 Vdc

Input Impedance                           >100 Meg Ohms (0 to 10V, 2 to 10V, 0 to 5V)

Output Signal| Operating Modes                         4 to 20 mA, 0 to 10 Vdc, 0 to 5 Vdc

Output Impedance                        <10 Ohms (0 to 5 Vdc, output, 0 to 10V output)

200 Ohms (4 to 20 mA output mode)

Loop Voltage                               12 Vdc (4 to 20 mA output mode)

Resolution| Absolute Position Accuracy          <1%

Dead Band Adjustment                 1% (+/- 0.5%) to 6% (+/-3%) (3%

default)

1% minimum increment

Potentiometer Feedback Signal| Supply Voltage                            3.3 Vdc

External Feedback Potentiometer 1K to 10K Ohms

Speed Control| Open/Close Speed                       0% to 100% (default). Step size: 20%.

Actuator                                       open/close speed as a percentage of full speed.(See motor speed specification for maximum 90° run times.)

Operating Mode| Normal Mode                               Modulating – follow setpoint

Loss of Control Signal                  Selectable to Open, Close, or Last Loss of Supply Power                   Fail-in-place

Reverse Acting Mode                   Configurable for inverted input signal Autocalibration                             Automatic endpoint detection

Manual Operation                         Keypad electrical manual operation of actuator (Open, Stop, Close)

Torque Protection| Stall Detection                              Motor detected stationary >2 seconds (600 to 6500 lb-in units only)

Torque Limit                                 ( Optional ) externally connected

Open/Close torque                       limit switch

Electronic Torque Limit                 ( Optional ) factory-programmable current/torque                               limit switch

Environmental| Ambient Temperature                    -20°F (-29°C) to 150°F (65°C)

Compliance                                  120V units comply with UL, cUL, and CSA. All models are CE certified.

Table 3. Product Numbers.
Use the product numbers in the following table to order a valve or a valve and actuator assembly. The valve product number consists of the type, action, valve size, disc type, and valve configuration. To order an assembly, add a (-) after the valve product number and then choose the application, actuator, voltage, control signal, end switches followed by a separator (.) and the actuator torque.

Sample:| B| 2| 02| F| C| | S| A| 1| 2| 6| .| 600
---|---|---|---|---|---|---|---|---|---|---|---|---|---
Valve Type: Butterfly|  |  |  |  |  |  |  |  |  |  |  |
Action:

2 = 2-Way

3 = 3-Way

Valve Size:

02=2″, 25=2.5″, 03=3″, 04=4″,

05=5″, 06=6″, 08=8″ 10=10″,

12=12″, 14=14″, 16=16″,

18=18″, 20=20″, 24=24″

Disc Type:

F = Full Cut

U = Under Cut

Valve Configuration:

3-Way – A, B, C, D

2-Way

O = Normally Open C = Normally Closed

M = Valve assembly with manual operator

Denotes Assembly
Application:

S = Standard Temp – Intermittent 250°F Operation

H = High Temperature – Continuous 250°F Operation Blank = Siemens Commercial Actuator

Actuator:

A = Industrial Actuator

GCA = Siemens SR Commercial Actuator GIB = Siemens NSR Commercial Actuator

Voltage: 1 = 24V

2 = 120V

Control Signal:

2 = 2-Position

3 = Floating (Commercial Actuators only) 6 = Modulating (0-10V)

End Switches:

1 = No switches 6 = Switches

Separator
Actuator Torque (lb-in):

600=600, 1K=1200, 2K=2000, 3K=3000, 5K=5000, 6K=6500,

13K=13000, 18K=18000, 21K=21300, 41K=40680, 3U = Shaft adapter with 3-foot cable (Commercial Actuators only)

NOTE: 13K and 18K torque models are available starting July 2020.

Accessories/Kits| 599-10097LT      120V Servo NXT Kit A-Series 600 to 6.5K lb-in actuators

599-10097HT     120V Servo NXT Kit for A-Series 13K & 18K lb-in actuators 599-10098         24V Servo NXT Kit A-Series 600 to 5K lb-in actuators

---|---
Mounting and Installation| All A-Series industrial electric actuators are suitable for direct mounting on Siemens resilient seat butterfly valves.

NOTE:

The standard mounting position for the actuator is to orient the base of the actuator parallel to the pipeline.

To mount an actuator on a vertical pipe, position the unit with the conduit entries on the bottom to prevent condensation from entering the actuator through its conduits.

Service| The resilient seat butterfly valve and actuator are maintenance-free.
Wiring|  | CAUTION:

·         When wiring an A-Series Industrial Electric Actuator for two- position (on/off) control and the power to the actuator is commanded to be off, you must ensure that there is no extraneous or leakage voltage between hot and common. Leakage voltage greater than 3 Vac can cause actuator failure.

·         When wiring an A-Series Industrial Electric Actuator for two- position control, the controller should use at minimum a one-second time delay for command signal reversal. Instantaneous command reversals may cause actuator failure.

Figure 1. 24 Vac/dc On/Off Wiring 600 and 2000 lb-in Models.

NOTE:

Use this A-Series Industrial Electric Actuator only to control equipment under normal operating conditions. Where failure or malfunction of the electric actuator could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of, or protect against, failure or malfunction of the electric actuator.

Wiring, Continued

NOTES:

  1. Command signal and feedback wires MUST be shielded and grounded for proper servo operation.
  2. The command signal input (-) terminal is internally connected to the Servo neutral terminal. DO NOT connect the live to the neutral terminal on the Servo.
  3. Command signal and feedback signal must be isolated from each other and any other circuits. When using 0 to 10 Vdc, 0 to 5 Vdc and 2 to 10 Vdc the common of the command signal should NOT be ground/earth referenced.
  4. The feedback loop is powered by the Servo, do not supply external power.
  5. Command signal and feedback signal wires should be properly shielded and grounded, on one end only, preferably the controller end.
  6. The 24V Servo Pros can be wired with 3- or 4-wire configuration.

Dimensions

Actuator Model Number| A| B| C| D| E| F| G| H| J| K| L| M| N| P| Q| R| S| Wt lbs (kgs)
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Axx6.600| 7.5| 5.8| 5.6| 1| 1.94| .19| 1/2| 2.2| 5/16-18| | L75| .51| 1.75| 3.5| | | | 13
 | (191)| (147)| (141)| (48)| (49.2)| (4.7)|  | (55)| ×Ø 2.76|  | (19)| (31)| (44.5)| (89)|  |  |  | (6)
Axx6.1K| 10.1| 7.8| 6.6| 2.4| 2.69| .56| 3/4| 2.6| (F07)| 1/2-13| 1.18| .87| 2.22| 8.0| 8.0| 8.0| 8.0| 28
Axx6.2K| (256)| (198)| (168)| (62)| (68.3)| (14.3)|  | (66)|  | x ø4.92 (F12)| (30)| (22)| (56.3)| (203)|  |  |  | (13)
Axx6.3K| 12.1| 9.5| 7.2| 2.9| 3.19| .56| 3/4| 3.1| 1/2-13| 3/4-10| See Detail A1| 12| | | _| 48
Axx6.5K| (308)| (242)| (183)| (73)| (80.9)| (14.3)|  | (78)| x ø4.92| x ø 6.50|  | (304.8)|  |  |  | (22)
Axx6.6K|  |  |  |  |  |  |  |  | (F12)| (F16)|  |  |  |  |  |
Axx6.13K| 12.1| 9.5| 12.5| 8.1| 9.2| .56| 3/4| 8.3|  |  | See Detail A1| 12| 6.1| 12.7| 8| 118
Axx6.18K| (308)| (242)| (317)| (206)| (234)| (14.2)|  | (211)|  |  |  | (305)| (155)| (323)| (203)| (54)

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Products or company names mentioned herein may be the trademarks of their respective owners. © 2020 2022 Siemens Industry, Inc.

Siemens Industry, Inc. Smart Infrastructure
1000 Deerfield Parkway Buffalo Grove, IL 60089 USA + 1 847-215-1000 Your feedback is important to us. If you have comments about this document, please send them to sbt_technical.editor.us.sbt@siemens.com Document No. A6V11937852 Printed in the USA

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals