SIEMENS SITOP PSU200M Instructions
- October 27, 2023
- SIEMENS
Table of Contents
SIEMENS SITOP PSU200M
- View of unit
- Design
- Do not subject the end stop to any higher stress
- Input
- Output
- Signaling contact
- Selector switch
- Signaling
- Voltage range selector switch
Description
SITOP power supplies are built-in units, IP20 degree of protection, protection class I. Primary switched-mode power supplies for connection to 1-phase AC system or to 2 line conductors of three-phase line supplies (TN, TT or IT line system in accordance with IEC 60364-1) with rated voltages of 120 – 230/230 – 500 V, 50 – 60 Hz; 24 V DC output voltage, isolated, short-circuit and idling- proof.
Safety notes
NOTICE
Appropriate transport, proper storage, mounting, and installation, as well as
careful operation and service, are essential for the error-free, safe and
reliable operation of the device/system. Setup and operation of this
device/system are permitted only if the instructions and warnings of the
associated technical documentation are carefully observed. Only qualified
personnel are allowed to install the device/system and set it into operation.
Assembling
- Mounting on a standard mounting rail TH35-15/7.5 (EN 60715).
- The device should be mounted so that the terminals are at the bottom.
- A clearance of at least 50 mm must be maintained above and below the device (max. cable channel depth 50 mm).
Connecting
WARNING: Before installation or maintenance work can begin,the system’s main switchmustbe switch edoffand measures taken to prevent it being switched onagain. If these instructions on to be served, touching live parts can result in deathor seriousinjury. It is only permissible to use an insulated screwdriver when actuatingthe potentiometer. The voltage range switchover switch can only be actuated in the no-voltage state.When installing the devices, the relevant country-specific regulations must be ob-served.
- Important note: A fuse, a miniature circuit breaker or circuit breaker must be provided at the input.
- The supply voltage must be connected according to IEC 60364 and EN 50178.
- The cables used must be suitable for tempera-tures of at least 85 °C.
See Figure 4 Input (Page 1)
See Figure 5 Output (Page 1)
See Figure 3 Terminal data (Page 1)
Do not subject the end stop to any higher stress
Structure
① | AC input |
---|---|
② | DC output |
③ | Potentiometer 24 – 28 V |
④ | Signaling contact (13, 14) |
⑤ | Indicator lights (24 V O.K., OVERLOAD, |
SHUT DOWN)
⑥| Selector switch
⑦| Voltage range selector switch
⑧| Mounting rail slider
⑨| Convection (Natural convection)
⑩| Clearance above/below
Operating mode
Parallel operation and short-circuit behavior that canbeswitchedover
It is only permissible to connect two identical devices in parallel to in
crease the power rating when the output characteristic isswitchedovertoONusing
select or switchA.
| A| B
---|---|---
ON| Parallel operation: Gradient of the output characteristic|
Latching shutdown The device is shut- down if the overload lasts
longer than 100 ms. Turning the
power supply off for a minimum of 30 s causes a reset.
OF
F *
| Standalone operation | Constant current type 1.2 × rated current for over- load/short-circuit
-
State when delivered
SignalingLED green: Output voltage > 20 V
LED yellow: Overload in the “constant current”
mode
LED red: Latching shutdown in the “Shut-
down” mode
Signaling contact
Signaling contact (13, 14): Output voltage
20 V
Contact rating:
30 V DC/0.1 A
ATTENTION: The signaling contact must not be connected on the primary side!
Technical data
6EP1333-3BA10
6EP1333-3BA10-0AY0
| 6EP1334-3BA10
---|---
Input variables
Rated input voltage Uin rated:
AC 120 – 230/230 – 400 – 500 V, 50 – 60 Hz
Voltage range: AC 85 – 264/176 – 550 V
see Figure 9 Voltage range selector switch (Page 2) delivery condition: 230 V
Rated input current Iin rated at rated load:
2.2 – 1.2/1.2 – 0.7 –
0.6 A
| 4.4 – 2.4/2.4 – 1.3 –
1.1 A
Input fuse: Internal
Recommended miniature circuit breaker, characteristic C (or B) connected to a
1-phase AC line supply:
6 A| 10 A
For two-phase operation connected to 2 line conductors of a three-phase line
supply, a two-pole, coupled miniature circuit breaker or a motor circuit
breaker must be used as a protective device. The latter must be connect- ed so
that current flows through all 3 current paths.
e.g. 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL489-listed, DIVQ) at 230 V
e.g. 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL489-listed, DIVQ) at 400/500 V
Power consumption (active power) at full load:
140 W| 270 W
Output variables
Rated output voltage Uout rated : 24 V
Setting range: 24 – 28 V, set using a potenti- ometer at the front of the
device
Derating at Uout > 24 V: 4 % [Iout]/V [Uout]; at Uin < 100 V/< 200 V: Iout
max: 90 % Iout rated
Rated output current Iout rated:
5 A| 10 A
Power Boost in operation for 25 ms (per min):
15 A| 30 A
Ambient conditions
Temperature for operation: -25 … 70 °C
Derating at 60 °C: 3 % Iout rated/K
Humidity (no condensation): 5 – 95 %
Overvoltage category: II to 2000 m
Pollution degree 2
Protective function
Current limiting for permanent overload Response value: typ. 1.2 × Iout rated
Characteristic of current limitation constantly dropping
Dimensions
Width × height × depth in mm:
70 × 125 × 121| 70 × 125 × 121
| Functional expansion possible using the redundancy, buffer, selectivity add-
on modules or DC UPS.
Accessories
Functional expansion is possible using the redundancy, buffer, and selectivity add-on modules DCUPS.
Disposal guidelines
Packaging and packaging aids can and must always be recycled. The product
itself may not be disposed of by means of domestic refuse
Service and Support
Additional information is available through the homepage
(https://support.industry.siemens.com)
Operating instructions and safety instructions
Only qualified personnel may install this device, wire it or work in its
proximity.
Before installation or maintenance work is begun, the main switch of the
system must be switched off and be secured against being switched back on. In
the case of non-observance, touching of live parts can result in death or
serious injury. Do not take clearly damaged devices into operation. The
relevant country-specific regulations are to be observed.
The device is a built-in device and must be mounted in a distribution box or cabinet.
The following applies for devices with power connections: A protective device (fuse) and a disconnector for disconnecting the power supply must be provided.
The following applies to devices approved for explosive atmospheres: Siemens AG Austria herewith declares that the device fulfills the requirements of EU directive 2014/34/EU. If the device is installed in a hazardous area, it must be installed in a distribution box with a degree of protection IP54 or higher. Do not pull out (disconnect) live terminals. Carry out voltage setting or switch actuation solely in a non-explosive environment. The following also applies to devices with an accessible fuse: Carry out removal / insertion of the fuse solely in a non-explosive environment.
Packaging and packaging material are suitable for recycling and should always
be recycled. Do not dispose of the product itself in domestic waste.
For detailed information about the product please refer to the “Operating
instructions (compact)” included with the product.
For further information please refer to the home pages:
https://www.siemens.com/sitop-manuals and
https://support.industry.siemens.com
https://support.industry.siemens.com