SIEMENS VNT Virtual Network Tunnel Instruction Manual

October 30, 2023
SIEMENS

SIEMENS LOGO Installation Instructions
Model VNT
Virtual Network Tunnel

INTRODUCTION

The Model VNT Virtual Network Tunnel (as shown in Figure 1) from Siemens Industry, Inc. is a UL approved fanless single board computer that is powered from its local 24V power supply with battery back up. The VNT Gateway is responsible for supporting the
intercommunication of system components.
It transports HNET and XNET supervision and monitoring between VNTs via TCP/IP. It also routes audio over TCP/IP when required between VNTs. If the VNT Gateway is at a control point, it is responsible for generating audio from the local source.

SIEMENS VNT Virtual Network Tunnel - Network Tunnel

The VNT Gateway utilizes some or all of the following interfaces depending upon its location within the system:

  • 100BaseT TCP/IP connection to a local Fiber Ring Switch. This connection transports the network signals (HNET and XNET), audio, supervision and monitoring data streams.
  • One or more independent HNET RS485 interfaces to the module network of an XLS/Desigo Fire Safety Modular/Cerberus PRO Modular or its components.
  • An XNET RS485 interface to the XLS/Desigo Fire Safety Modular/Cerberus PRO Modular node(s) within a given system.
  • An XNET over TCP/IP feed to an NCC at a command center.
  • An HNET RS485 interface to an XLS/Desigo Fire Safety Modular/Cerberus PRO Modular node within a given system.
  • An audio input to accept a microphone paging source.
  • An audio output to distribute paging audio to a given system.

INSTALLATION

The VNT mounts on a VNT-MP in a CAB1, CAB2 or CAB3 enclosure. Refer to the VNT-MP Installation Instructions, P/N 315-050489, for information on mounting the VNT-MP.
Remove all system power before installation, first battery then AC. (To power up, connect the AC first, then the battery.)
The following items are supplied with the VNT (P/N 500-650490):

Quantity 1 Item
1 VNT fanless computer
1 Cable P/N 555-150464
4 Cable P/N 555-150494 (to fiber switch)
#8-32 hex nuts

VNT Mounting
Refer to Figure 2.
The VNT mounts at the top of the VNT mounting plate with the four hex nuts provided.

  1. Place the VNT over the four studs on the VNT-MP.
  2. Place the four hex nuts supplied over the studs and tighten them to secure the VNT to the VNT-MP.

SIEMENS VNT Virtual Network Tunnel - VNT MP

WIRING
Wiring for the VNT-Building Configuration is shown in Figure 3. Wiring for the VNT-Fire Command Center is shown in Figure 4.
All connections are supervised and power limited unless otherwise stated.

ELECTRICAL RATINGS

For power, the VNT may only be connected to the VNT-PS (P/N 500-450491).
Input Voltage: Regulated 24VDC
Input Current: 1.7A @ 24VDC max.

SIEMENS VNT Virtual Network Tunnel - DiagramSIEMENS VNT Virtual Network Tunnel - Diagram
2

Cyber security disclaimer
Siemens products and solutions provide security functions to ensure the secure operation of building comfort, fire safety, security management and physical security systems. The security functions on these products and solutions are important components of a comprehensive security concept.
It is, however, necessary to implement and maintain a comprehensive, state-of- the-art security concept that is customized to individual security needs. Such a security concept may result in additional site-specific preventive action to ensure that the building comfort, fire safety, security management or physical security system for your site are operated in a secure manner. These measures may include, but are not limited to, separating networks, physically protecting system components, user awareness programs, defense in depth, etc.
For additional information on building technology security and our offerings, contact your Siemens sales or project department. We strongly recommend customers to follow our security advisories, which provide information on the latest security threats, patches and other mitigation measures.
http://www.siemens.com/cert/en/cert-security- advisories.htm

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Canada, Ltd.
1577 North Service Road East
Oakville, Ontario
L6H 0H6 Canada
Document ID A6V10316286
P/N 315-050490-3
firealarmresources.com

Documents / Resources

| SIEMENS VNT Virtual Network Tunnel [pdf] Instruction Manual
VNT Virtual Network Tunnel, VNT, Virtual Network Tunnel, Network Tunnel
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals