REHAU 13280001001 Nea Smart 2.0 Room Unit Instruction Manual

June 1, 2024
REHAU

NEA SMART 2.0 Room Unit
Quickinstall
(A) 13280001001, 13280001003, 13280001004, 13280041001, 13280041003, 13280041004, 13280051001, 13280051003
(B) 13280101001, 13280101002, 13280101003, 13280101004, 13280121001, 13280121002, 13280121003, 13280121004, 13280131001, 13280131002, 13280131003, 13280131004

 Safety Instructions and Product Conformity

Risk of life through electrical shock! The electrical installation must follow the applicable national standards and guidelines as well as any specific requirements of your local energy supplier. These instructions are intended for use by a qualified person who is holding an official certificate in one of the following professions:
electrician or electronics engineer. Always read the instructions prior to commencing the installation. Connection to the final power supply must only be carried out after the installation is complete. Hereby, REHAU Industries SE & Co. KG declares that the radio equipment type Room Unit (mat. no. see B) is in compliance with EU directive 2014/53/EU and UK regulation UK: 2017 No. 1206. The full text of the EU and UK declaration of conformity is available at the following internet address: www.rehau.com/neasmart2

System Overview

REHAU 13280001001 Nea Smart 2.0 Room Unit -

Scope of Delivery

Only wireless version

Installation

REHAU 13280001001 Nea Smart 2.0 Room Unit -
nstallation

A)  Bus (ZOBUS)
B) Wireless

REHAU 13280001001 Nea Smart 2.0 Room Unit - Set up external
sensor2

Remote Sensor
Set up external sensor at installer menu (HTML WIZARD)

REHAU 13280001001 Nea Smart 2.0 Room Unit -
nstallation1

REHAU 13280001001 Nea Smart 2.0 Room Unit -
nstallation2

Assignment of a room controller to a room zone

REHAU 13280001001 Nea Smart 2.0 Room Unit -
nstallation3

Assignment of a room controller to several room zones

REHAU 13280001001 Nea Smart 2.0 Room Unit -
nstallation4

Address
REHAU Industries SE & Co. KG
Rheniumhaus
Helmut-Wagner-Straße 1
95111 Rehau
Deutschland / Germany
Only for UK – Importer address:
REHAU Ltd.
Hill Court
Walford
Ross-on-Wye
Herefordshire
HR9 5QN
United Kingdom

Delete Pairing Sequence

REHAU 13280001001 Nea Smart 2.0 Room Unit - Delete Pairing
Sequence

Set up external sensor

REHAU 13280001001 Nea Smart 2.0 Room Unit - Set up external
sensor

Parameters

  • P0: Not connected
  • P01: Floor temperature probe for minimum and maximum value monitoring (minimum value valid for cooling, maximum value for heating
  • P02: Floor temperature probe for minimum and maximum value monitoring (minimum value valid for cooling and heating, maximum value for heating)
  • P03 : External room temperature probe (room temperature control only by this value)
  • P04: External floor temperature probe (floor temperature control only)
  • P05: External room temperature probe (room temperature control by mean value of external and internal probe)
  • P06:   Dew point monitor (switching contact)
  • P07: Window contact
  • P08: Condensation protection for chilled ceilings (only with humidity room units)
  • P09: External probe for core temperature (TABS)
  • P10: External probe for return temperature (TABS)
  • P11:   External probe for outside temperature

Er 01 : Room temperature sensor out of sensor range
Er 02: Room temperature sensor broken
Er 03: Room temperature sensor shorted
Er 04:   Humidity sensor out of sensor range
Er 05: Humidity sensor broken
Er 06:   Humidity sensor shorted
Er 07 : Remote temperature sensor out of sensor range
Er 08:   Remote temperature sensor broken
Er 09 :  Remote temperature sensor shorted
Er 10: Connection error Base and R-/U-Module
Er 90: Communication error between base and R-Module
Er 99:   Error that is only shown in the NEA SMART 2.0 app.
RAUCLIMATE SILENT BREEZE fan coils
Er 50: Communication error between base and fan coil
Er 51 : Motor fault
Er 52: Fan Coil Stop – difference between air and T2 water temperature too large
Er 53:   Unterbrechung) / Sensor T2 water temperature defective (short- circuit / interruption)
Er 54:   T2 Water temperature too cold for heating or too warm for cooling
Er 56: Fan Coil in fault mode

Additional information

This document is protected by copyright. All rights based on this are reserved. No part of this publication may be translated, reproduced or transmitted in any form or by any similar means, electronic or mechanical, photocopying, recording or otherwise, or stored in a data retrieval system. Our verbal and written advice with regard to usage is based on years of experience and standardised assumptions and is provided to the best of our knowledge. The intended use of REHAU products is described comprehensively in the technical product information. The latest version can be viewed at www.rehau.com/TI. We have no control over the application, use or processing of the products. Responsibility for these activities therefore remains entirely with the respective user/processor. Where claims for liability nonetheless arise, they shall be governed exclusively according to our terms and conditions, available at www.rehau.com/conditions, insofar as nothing else has been agreed upon with REHAU in writing. This shall also apply for all warranty claims, with the warranty applying to the consistent quality of our products in accordance with our specifications. Subject to technical changes.

www.rehau.com/neasmart2
http://www.rehau.com/neasmart2?utm_source=qr-code
954636 02.2024 © REHAU Industries SE & Co. KG, Helmut-Wagner-Str. 1, Rheniumhaus, 95111 Rehau

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals