REHAU Rehau RE.GUARD Leakage detector 14573121001 Manual
- June 8, 2024
- REHAU
Table of Contents
- REHAU
- Rehau RE.GUARD Leakage detector
- SKU: 14573121001
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Inclusion/Exclusion
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 1: operation mode
- Parameter 10: micro leakage pressure drop abort
- Parameter 11: number of measurements
- Parameter 12: wait time until next measurement
- Parameter 13: reaction to micro leakage
- Parameter 14: macro leakage detected
- Parameter 15: max flow rate if operation mode is 2
- Parameter 16: max pressure drop if operation mode is 2
- Parameter 18: max continious liter if operation mode is 2
- Parameter 20: max continious time if operation mode is 2
- Parameter 21: max flow rate if operation mode is 1
- Parameter 22: max pressure drop if operation mode is 1
- Parameter 24: max continious liter if operation mode is 1
- Parameter 26: max continious time if operation mode is 1
- Parameter 28: reaction to macro leakage
- Parameter 30: reaction to flooding sensor
- Parameter 31: backup battery nominal voltage
- Parameter 37: time set correctly
- Parameter 38: total operating time
- Parameter 39: operating time since last power on
- Parameter 4: fixed schedule time hours
- Parameter 5: fixed schedule time minutes
- Parameter 50: water temperature high threshold
- Parameter 51: water temperature low threshold
- Parameter 54: error code
- Parameter 6: fixed schedule day
- Parameter 7: automatic schedule time interval
- Parameter 8: micro leakage mesuring time
- Parameter 9: micro leakage pressure drop
- Technical Data
- Supported Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
REHAU
Rehau RE.GUARD Leakage detector
SKU: 14573121001
Quickstart
This is a
secure
Valve
for
.
Please make sure the internal battery is fully charged.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
The Rehau RE.GUARD is a water manager which protects your home against water leakages and meassures your consumption of water.It has a highly sophisticated water meter and pressure meter built inside. Its algorithms are able to detect very small microleakages as well aslarger leakages like e.g. pipe bursts. The sensibility can be adapted to your needs. Furthermore statistics of your water consumption can be created to help you save water.This product is available at your professional plumber.Made and engineered in Europe
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1 | 1 | Connection to Gateway etc. |
---|---|---|
2 | 5 | Sends status of valve |
3 | 5 | Sends notiofication in case of leackage |
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 1: operation mode
__
Size: 1 Byte, Default Value: 2
SettingDescription
0 | 0-valve (always) off |
---|---|
1 | 1-user absent=not at home=holiday |
2 | 2 = user present=at home |
3 | 3 = valve (always) on |
Parameter 10: micro leakage pressure drop abort
__
Size: 2 Byte, Default Value: 100
SettingDescription
0 – 32000 | pressure drop in kPa |
---|
Parameter 11: number of measurements
for micro leackage
Size: 1 Byte, Default Value: 3
SettingDescription
1 – 99 | how many in one time period |
---|
Parameter 12: wait time until next measurement
__
Size: 1 Byte, Default Value: 1
SettingDescription
0 – 60 | waiting time in minutes between two meassurements |
---|
Parameter 13: reaction to micro leakage
__
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 2 | 0=disable detection, 1=blink LED, 2= blink LED andshut off valve |
---|
Parameter 14: macro leakage detected
__
Size: 1 Byte, Default Value: 0
SettingDescription
0 | no leackage |
---|---|
1 | leackage detected |
Parameter 15: max flow rate if operation mode is 2
__
Size: 2 Byte, Default Value: 3000
SettingDescription
0 – 32000 | flowrate in l/h |
---|
Parameter 16: max pressure drop if operation mode is 2
__
Size: 2 Byte, Default Value: 1000
SettingDescription
0 – 32000 | pressure drop in kPa |
---|
Parameter 18: max continious liter if operation mode is 2
__
Size: 2 Byte, Default Value: 300
SettingDescription
0 – 32000 | liter |
---|
Parameter 20: max continious time if operation mode is 2
__
Size: 2 Byte, Default Value: 60
SettingDescription
0 – 32000 | time in minutes for water flow in present mode |
---|
Parameter 21: max flow rate if operation mode is 1
__
Size: 2 Byte, Default Value: 300
SettingDescription
0 – 32000 | max flow rate in absent mode liters/hour |
---|
Parameter 22: max pressure drop if operation mode is 1
__
Size: 2 Byte, Default Value: 1000
SettingDescription
0 – 32000 | max pressure drop in absent mode |
---|
Parameter 24: max continious liter if operation mode is 1
__
Size: 2 Byte, Default Value: 100
SettingDescription
0 – 32000 | max. liter of water in absent mode |
---|
Parameter 26: max continious time if operation mode is 1
__
Size: 2 Byte, Default Value: 30
SettingDescription
0 – 32000 | max. time of water flow in absent mode in minutes |
---|
Parameter 28: reaction to macro leakage
0=disable detection, 1=blink LED, 2= blink LED and shut off valve
Size: 1 Byte, Default Value: 2
SettingDescription
0 – 2 | 0=disable detection, 1=blink LED, 2= blink LED and shut off valve |
---|
Parameter 30: reaction to flooding sensor
0=disable detection, 1=blink LED, 2= blink LED andshut off valve
Size: 1 Byte, Default Value: 1
SettingDescription
0 – 2 | 0=disable detection, 1=blink LED, 2= blink LED andshut off valve |
---|
Parameter 31: backup battery nominal voltage
__
Size: 2 Byte, Default Value: 0
SettingDescription
0 – 7 | shows backup battery voltage |
---|
Parameter 37: time set correctly
__
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1 | 0=time not set 1=time set correctly |
---|
Parameter 38: total operating time
__
Size: 4 Byte, Default Value: 0
SettingDescription
0 – 2147483647 | Read only: Counting total operation time internally |
---|
Parameter 39: operating time since last power on
__
Size: 4 Byte, Default Value: 0
SettingDescription
0 – 2147483647 | Read only counting operation time since last power off |
---|
Parameter 4: fixed schedule time hours
__
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 23 | hour of day |
---|
Parameter 5: fixed schedule time minutes
minutes in time stamp
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 59 | minute |
---|
Parameter 50: water temperature high threshold
__
Size: 2 Byte, Default Value: 250
SettingDescription
0 – 32000 | 1C = 10; Recommended 25C by international standards |
---|
Parameter 51: water temperature low threshold
__
Size: 2 Byte, Default Value: 20
SettingDescription
0 – 32000 | 1C = 10; Water icing prevention |
---|
Parameter 54: error code
error codes; see documentation for
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 37 | showing different error codes. See website for error description |
---|
Parameter 6: fixed schedule day
_127 = 1111111 in binary, 0 - > automatic schedule time interval is used, see
u0022data_definitoncommentu0022
Size: 1 Byte, Default Value: 127
SettingDescription
1 – 127 | 1111111 in binary, |
---|
Parameter 7: automatic schedule time interval
__
Size: 2 Byte, Default Value: 0
SettingDescription
0 – 168 | How many days |
---|
Parameter 8: micro leakage mesuring time
__
Size: 2 Byte, Default Value: 100
SettingDescription
0 – 32000 | seconds measuring time |
---|
Parameter 9: micro leakage pressure drop
__
Size: 2 Byte, Default Value: 0
SettingDescription
0 – 32000 | presssure drop in kPa |
---|
Technical Data
Hardware Platform | ZM5101 |
---|---|
Device Type | Valve |
Network Operation | Always On Slave |
Firmware Version | HW: 1 FW: 1.05:01.06 |
Z-Wave Version | 6.71.03 |
Certification ID | ZC10-19096760 |
Z-Wave Product Id | 0x0413.0x0001.0x0001 |
Security V2 | S2_UNAUTHENTICATED ,S2_AUTHENTICATED |
Frequency | XXfrequency |
Maximum transmission power | XXantenna |
Supported Command Classes
- Association Grp Info V2
- Association V2
- Basic
- Battery
- Clock
- Configuration
- Device Reset Locally
- Firmware Update Md V4
- Manufacturer Specific V2
- Meter V4
- Notification V8
- Powerlevel
- Security
- Security 2
- Sensor Multilevel V9
- Supervision
- Switch Binary
- Transport Service V2
- Version V2
- Zwaveplus Info V2
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.