BEGA 85141 Performance Floodlight Instruction Manual
- June 1, 2024
- BEGA
Table of Contents
08.23 · Technical amendments reserved
85 141
Performance floodlight
IP 65
85141 Performance Floodlight
Instructions for use
Application
Performance floodlight with mounting box.
For a variety of interior and exterior lighting applications.
Product description
Luminaire made of aluminium alloy, aluminium and stainless steel
BEGA Unidure® coating technology
Colour graphite or silver
Clear safety glass
Silicone gasket
Reflector surface made of pure aluminium
BEGA Hybrid Optics®
Rotation range of floodlight 350°
Swivel range -30°/+90°
Mounting box with 2 fixing holes
ø 6 mm · 85 mm spacing
2 cable entries for through-wiring of mains supply cable ø 7-10.5 mm, max. 5 G
1.5@
Connecting terminal 2.5@ with plug connection
Earth conductor connection
BEGA Ultimate Driver®
Complies with flicker requirements in accordance with IEEE 1789,
DIN IEC/TR 63158, DIN IEC/TR 61547-1
LED power supply unit
220-240 V x 0/50-60 Hz
DC 176-264 V
DALI-controllable
Number of DALI addresses: 1
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components
without switching off the luminaire
Safety class I
Protection class IP 65
Dust-tight and protection against water jets
Impact strength IK08
Protection against mechanical impacts < 5 joule
**– Conformity mark
Wind catching area: 0.057 m²
Weight: 6.2 kg
This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation. If subsequent modifications are made to the luminaire, the
person responsible for these modifications shall be considered the
manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
The ideal protection of all electronic components installed in the luminaires
is achieved by using bounce-free switching contacts such as an electronic
relay (solid-state relay), e.g. BEGA 71 320.
Installation
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
Undo hexagon socket head screw (wrench size 3 mm) up to the stop and
disassemble the mounting plate.
Pass the power connecting cable through the cable entry in the mounting plate.
Note position of application of the mounting plate “arrow down”.
Fix the mounting plate with enclosed or any other suitable fixing material
onto the mounting surface.
Be sure to use the gasket rings supplied.
Make earth conductor connection.
Push silicone sleeves over the lines and make electrical connection to
terminal (plug connection).
For digital control please use the 2-pole plug connector DA, DA.
In case this connector is not used the luminaire will be operated at full
light output.
Push plug into coupler as far as it will go.
Make sure that gasket is positioned correctly.Place
floodlight unit onto the mounting plate as displayed in the sketch, align and
screw together firmly.
Adjustment of beam direction:
Undo joint screw (hexagon socket head wrench size 6 mm) and set the desired
beam direction.
Tighten the joint screw.
Torque = 12 Nm.
Lamp
**
Module connected wattage | 71.1 W |
---|---|
Luminaire connected wattage | 76 W |
Rated temperature | ta= 25 °C |
Ambient temperature | ta max = 40 °C |
85 141 K3
Module designation | LED-0442/930 |
---|---|
Colour temperature | 3000 K |
Colour rendering index | CRI > 90 |
Module luminous flux | 10550 lm |
Luminaire luminous flux | 7886 lm |
Luminaire luminous efficiency | 103,8 lm / W |
85 141 K4
Module designation | LED-0442/940 |
---|---|
Colour temperature | 4000 K |
Colour rendering index | CRI > 90 |
Module luminous flux | 10710 lm |
Luminaire luminous flux | 8005 lm |
Luminaire luminous efficiency | 105,3 lm / W |
Lighting technology
Symmetrical wide beam light distribution Half beam angle 61°
For special lighting applications, an optical filter can be used to change the
symmetrical light cone into a flat beam light distribution.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt and deposits.
Do not use high pressure cleaners.
Maintenance
The connecting cable between mounting box and floodlight has to be inspected
regarding obvious damages and has to be replaced by a qualified electrician
only.
Please note:
Do not remove the desiccant bag from the luminaire housing.
It is needed to remove residual moisture.
Replacing the LED module
The designation of the LED module is noted on a separate label in the
luminaire or on the underside of the specific LED module.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted. The module can be replaced by
qualified persons using standard tools.
Disconnect the system.
Open the floodlight:
Undo locking pin (hexagon socket head wrench size 2.5 mm) on the back side of
the floodlight housing.
Remove the trim ring along with the safety glass and reflector by twisting it
counterclockwise.
Replace LED module.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Place trim ring with glass and reflector on the floodlight housing in such a
way that the notches in the trim ring and floodlight housing align on top to
each other.
Twist on the trim ring clockwise as far as the stop. Tighten locking pin.
Accessories
71 292 | Optical filter flat beam |
---|---|
71 334 | Shield |
71 339 | Cylindrical shield |
For the accessories a separate instructions for use can be provided upon request.
Spares
Trim ring graphite with glass | 25 000 285 |
---|---|
Trim ring silver with glass | 25 000 286 |
LED power supply unit | DEV-0356/1400i |
LED module 3000 K | LED-0442/930 |
LED module 4000 K | LED-0442/940 |
Reflector | 75 005 021 |
Gasket housing | 83 001 780 |
Gasket mounting box | 83 001 838 |
Gasket trim ring | 83 002 225 |
BEGA Gantenbrink-Leuchten KG · Postfach 31 60
· 58689 Menden · info@bega.com ·
www.bega.com
References