Bega 22203 Recessed Wall Luminaire Instruction Manual
- June 1, 2024
- BEGA
Table of Contents
Bega 22203 Recessed Wall Luminaire
Technical amendments reserved
Application
Recessed luminaire for glare-free lighting of floor spaces from a low mounting
height.
Dark Sky
The light of this luminaire is directed evenly and highly efficiently onto the
surface to be illuminated. No light is emitted into the upper half-space of
the luminaire.
Product Description
- LED recessed luminaire without power supply unit
- Luminaire made of cast aluminium, aluminium and stainless steel
- BEGA Unidure® coating technology
- Matt safety glass
- Silicone gasket
- Required recessed opening 70 x 70mm
- Recessed depth 90mm
- Fixing is achieved by using two adjustable
- wedge-shaped claws
- 1 cable entry
- for connecting cable max. ø 10,5mm
- Connecting terminals 2.5
- Safety Class III
- Protection class IP 65
- Dust-tight and protection against water jets
- Safety mark
- Impact strength IK07
- Protection against mechanical
- impacts < 2 joule
- Conformity mark
- Weight: 0.25 kg
- This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations. Installation and commissioning may only be carried out by
a qualified electrician. The manufacturer accepts no liability for damage
caused by improper use or installation. If subsequent modifications are made
to the luminaire, the person responsible for these modifications shall be
considered the manufacturer.
Lamp
- Module connected wattage 1.9 W
- Luminaire connected wattage 2.3 W
- Rated temperature ta=25 °C
- Ambient temperature ta max=60 °C
- When installed in heat-insulating
- material ta max=50 °C
- Voltage 24 V = DC 22 203K3
- Module designation LED-0312/930
- Colour temperature 3000 K
- Colour rendering index CRI >90
- Module luminous flux 285 lm
- Luminaire luminous flux 9 lm
- Luminaire luminous efficiency 3,9 lm/W 22 203K4
- Module designation LED-0312/940
- Colour temperature 4000 K
- Colour rendering index CRI >90
- Module luminous flux 295 lm
- Luminaire luminous flux 10 lm
- Luminaire luminous efficiency 4,3 lm/W
Please note
The luminaire must not have permanent contact with aggressive media.
Aggressive media can be washed out of building materials and destroy the
housing of the luminaire. In case of an unknown composition of the building
materials, a material analysis is to be carried out before installation of the
luminaire. Aggressive media that is outgoing from the surface might also
affect the luminaire. Thus an overuse of cleaning agents in the surroundings
of the luminaire must be avoided.
Please note
The luminaire can only be operated with an operating device that fulfils the
requirements according to EN 61347-2-13. The maximum idle voltage of 60 V DC
must conform to SELV or SELV equivalent.
Installation
The electrical connection must only be made to safety transformers according to EN 61558 – see accessories. The recessed opening will be covered by the frame of the luminaire housing. Fixing of the luminaire is achieved by using two adjustable wedge-shaped claws.
Installation into solid walls
For this purpose installation housing 10 406 is available. If the installation
housing cannot be used a recessed opening of 70 x 70 mm is necessary to accept
the luminaire housing. Recessed depth min. 90 mm.
Installation into wall panels
A recessed opening of 70 x 70 mm is necessary to accept the luminaire housing.
Recessed depth min. 90 mm. The lateral distance between the recessed luminaire
and other building parts must be at least 50 mm. The claws catch the wall
panel from the backside. The minimum thickness of the wall panel is 10 mm. If
the wall panel has a thickness of less than 5 mm, the panel thickness must be
increased from the back side.
Undo screws
Remove the front plate with glass and gasket. Disassemble the tray for
electrical equipment. Do not remove the desiccant pouch from the luminaire
housing. It is needed to remove residual moisture. Lead the secondary
connecting cable supplied by others from the power supply unit through the
cable entry into the luminaire housing.
Make an electrical connection
- Connect the black conductor with the negative pole and the red conductor with the positive pole of the power supply unit.
- A 24 V safety direct voltage source with a smoothed residual ripple of max. 10 % is required for the electrical connection of the luminaire – see accessories.
- If other safety direct voltage sources are used, an upstream fuse (max. 6 A) must be provided by the customer.
- Assemble tray for electrical equipment.
- Push luminaire housing into the recessed opening.
- Tighten the screws of the claw fastener.
- Place glass with gasket onto the luminaire housing so that the matt surface is inside the housing.
- Assemble the front plate.
Cleaning Maintenance
- Clean the luminaire regularly with solvent-free cleansers from dirt and deposits.
- Do not use high-pressure cleaners.
Replacing the LED module
The designation of the LED module is noted on a separate label in the
luminaire or on the underside of the specific LED module. The light colour and
light output of BEGA replacement modules correspond to those of the modules
originally fitted. The module can be replaced by qualified persons using
standard tools. Disconnect the system and open the luminaire. Please follow
the installation instructions for the LED module. Inspect and, if necessary,
replace the luminaire gaskets. The defective glass must be replaced. Close the
luminaire.
Accessories
Power supply unit for LED luminaires 24 V DC
Safety transformer according to EN 61558/VDE 0570 part 2-6
- 70 564 Power supply unit for 5-15 W
- 70 465 Power supply unit for 10-25 W
- 70 565 Power supply unit for 20-35 W
- 70 566 Power supply unit for 30-50 W
- 70 567 Power supply unit for 40-75 W
- 70 169 Power supply unit for 70-150 W
- 230 V y 50-60 Hz
- 71 134 Power supply unit for 0-70 W
- AC range: AC: 198-264 V y 50-60 Hz
- DC range: DC: 176-275 V
The power supply units are also suitable for the operation of several LED luminaires. In this case, the maximum wattage of the power supply unit must not be exceeded.
10 406 Installation housing
For the accessories, separate instructions for use can be provided upon
request.
Spares
- Spare glass 14 000 425
- LED module 3000 K LED-0312/930
- LED module 4000 K LED-0312/940
- Gasket 83 000 839 .1