BEGA 34 2781 Wall and Ceiling Light Instruction Manual

June 1, 2024
BEGA

BEGA 34 2781 Wall and Ceiling Light

Product Information

Specifications

  • Lamp Module connected wattage: 16 W
  • Luminaire connected wattage: 19.1 W
  • Rated temperature: 25-35°C
  • Ambient temperature: max 85°C
  • Colour temperature: 3000 K (LED-0569/930), 4000 K (LED-0569/940)
  • Colour rendering index (CRI): > 90
  • Module luminous flux: 2440 lm (3000 K), 2535 lm (4000 K)
  • Luminaire luminous flux: 1587 lm (3000 K), 1649 lm (4000 K)
  • Luminaire luminous efficiency: 83.1 lm/W (3000 K), 86.3 lm/W (4000 K)

Product Usage Instructions

  • The electronic components in the luminaire are protected against overvoltage as per DIN EN 61547.
  • For additional protection against transients, it is recommended to use separate overvoltage protection components available on the manufacturer’s website.
  • Installation and operation of the luminaire must comply with national safety regulations and should only be conducted by a qualified electrician.
  • The manufacturer does not accept liability for damages resulting from improper use or installation.
  • Any modifications to the luminaire must be done by authorized personnel.
  • LEDs are high-quality electronic components, that avoid direct contact with the light output opening during installation or relamping.

FAQ

  • Q: Can I replace the LED modules myself?
  • A: No, installation and replacement of LED modules should be done by a qualified electrician to ensure the safety and proper functioning of the luminaire.
  • Q: What should I do if the luminaire is exposed to overvoltage?
  • A: In case of overvoltage exposure, check the luminaire for any visible damage and consider installing additional overvoltage protection components for future protection.

Ceiling and wall luminaire for indoor use.

Dimensions

BEGA-34-2781-Wall-and-Ceiling-Light-fig-2

Instructions for use

Application

  • Ceiling and wall luminaire · indoor luminaire made of hand-blown opal glass, satin matt and metal housing, for all lighting tasks.
  • They are ideal for places where a soft and uniform lighting distribution is required.

Product Description

  • Metal housing, finish colour white
  • Hand-blown opal glass, satin matt, with sliding-bolt closure 2 mounting holes ø 5.5 mm
  • Distance apart 200 mm 2 cable entries for through-wiring for mains cable up to ø 10,5 mm max. 5 x 1.5
  • Connecting terminal 2.5 with plug connection
  • Earth conductor connection 2-pole connecting terminal for digital control
  • LED power supply unit 220-240 V x 0/50-60 Hz
  • DC 176-280 V
  • DALI-controllable
  • Number of DALI addresses: 1
  • Basic insulation is provided between the mains and control cables
  • BEGA Thermal Control®
  • Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
  • Safety class I
  • Protection class IP 44
  • Protected against granular foreign bodies ≥ 1 mm and splash water Impact strength IK05
  • Protection against mechanical impacts < 0.7 joule
  • – Safety mark
  • – Conformity mark
  • Weight: 2.9 kg
  • This product contains light sources of energy efficiency class(es) D

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage under DIN EN 61547.
  • To achieve additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at www.bega.com.

Safety

  • The installation and operation of this luminaire are subject to national safety regulations.
  • Installation and commissioning may only be carried out by a qualified electrician.
  • The manufacturer accepts no liability for damage caused by improper use or installation.
  • If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Lamp

  • Module connected wattage 16 W
  • Luminaire connected wattage 19.1 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 35 °C

34 278.1 K3

  • Module designation LED-0569/930
  • Colour temperature 3000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 2440 lm
  • Luminaire luminous flux 1587 lm
  • Luminaire luminous efficiency 83,1 lm / W

34 278.1 K4

  • Module designation LED-0569/940
  • Colour temperature 4000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 2535 lm
  • Luminaire luminous flux 1649 lm
  • Luminaire luminous efficiency 86,3 lm / W

Installation

  • LED are high-quality electronic components!
  • Please avoid touching the light output opening of the LED directly during installation or relamping.

Disassemble LED module

  • Loosen LED connection and earth connection (plug connection).
  • Dismantle the mains supply cable max. 80 mm.
  • Lead mains supply cable through the cable entry into the luminaire housing.
  • Fix the luminaire housing with enclosed or any other suitable fixing material onto the mounting surface.
  • It is imperative to use the enclosed gaskets.
  • Make earth and electrical connections to the terminal.
  • For digital control please use the connecting terminal DA, DA.
  • In case this terminal is not used the luminaire will be operated at full light output.
  • Make an earth connection between the LED module and luminaire housing (plug connection).
  • Push LED plugs into couplers as far as it will go.
  • Assemble LED module.
  • Tighten the screws evenly (max. 0,8 Nm).
  • Please observe that the LED module is not damaged mechanically.

Place glass into the luminaire housing with sliding bolt glass closure and observe that the holding spring bolts fit into the notches of the glass.
IMPORTANT!

  • The glass must be turned clockwise past the first instance of palpable spring resistance.
  • By continuing to turn the glass, the glass retaining spring enters the “resting zone” of the glass. The end position of the glass is reached via a palpably firm stop.
  • Thus, you reach a safe and vibration-resistant holding of the glass.
  • To release the glass from the luminaire housing, turn it counterclockwise.

Replacement of the LED module · Maintenance

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
  • The module can be replaced by qualified persons using standard tools.
  • Disconnect the system.
  • Unscrew the glass from the luminaire housing by turning it counterclockwise.
  • Clean glass and luminaire regularly with solvent-free cleansers from dirt.
  • Please follow the installation instructions for the LED module.
  • Screw in the glass by turning it clockwise as far as it will go.
  • A broken glass must be replaced.

Spares

  • Spare glass 11 002 770 .0R G
  • LED power supply unit DEV-0409/700
  • LED module 3000 K LED-0569/930
  • LED module 4000 K LED-0569/940

CONTACT

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals