LUTRON PowPak RMKS-CCO1-24-B Contact Closure Installation Guide

June 3, 2024
Lutron

LUTRON PowPak RMKS-CCO1-24-B Contact Closure

LUTRON PowPak RMKS-CCO1-24-B Contact Closure

Part of the Vive Family

RMKS-CCO1-24-B      24 V~ 45 mA
RMNS-CCO1-24-B    24 V- 35 mA

Note for Replacement:
RMxS – the “S” model can replace the non-“S” model

Important Notes: Please read before installing.

  • For installation by a qualified electrician in accordance with all local and national electrical codes.
  • Note: Use copper conductors only.
  • The 24 V~ or 24 V- supply and load shall be provided via an approved power source in accordance with IEC/EN61558-2-6.
  • Check to see that the device type and rating is suitable for the application.
  • DO NOT install if product has any visible damage.
  • If moisture or condensation is evident, allow the product to dry completely before installation.
  • Operate between 0 °C and 55 °C.
  • 0% to 90% humidity, non-condensing.
  • For indoor use only.

Shock Hazard. May result in serious injury or death.

WARNING Turn off power at circuit breaker before installing the unit.

All Wireless Transmitters must be installed within 9 m of the PowPak CCO Module.

Required Components

For each system ensure you have:

At least one PowPak CCO Module

At least one Wireless Transmitter

Start Here

Install PowPak CCO Module
Suggested Installation Location: Center of room to ensure proper RF coverage of area.

A Install the 1/2 in NPT to 20 mm conduit adapter (provided) onto the PowPak CCO Module (optional).
B The PowPak CCO Module can be installed in a junction box or marshalling box using the conduit nut (provided) or with mounting screws (not provided). Please consult local and national electric codes for proper installation.
C Once installed, energize the PowPak CCO Module.
D Use the CCO Toggle button to toggle between high-end and OFF to verify wiring.

Supply Voltage

24 V~ / 24 VVive
Note: CCO Module supply wires can be connected in any polarity

Wiring a Lever

Operated Connector
When wiring lever operated connectors (2 supplied) use 2.5 mm2 to 4.0 mm2 (14 AWG to 12 AWG) solid or stranded copper wire.

LUTRON PowPak RMKS-CCO1-24-B Contact Closure-7

Programming with a Vive Hub

A .Use an iOS or Android-compatible device.

B. Download the Lutron Vive app.

C. Open the app and follow the instructions.

Note: For further information on set up, programming, and troubleshooting with a Vive system, please refer to the installation instructions included with the Vive hub or visit www.lutron.com/viveeurope
Note: For programming the PowPak CCO Module without a Vive hub see Programming Without a Vive Hub below.

Programming Without a Vive Hub

Associate Wireless Transmitters to PowPak CCO Module
Before beginning this step, make sure that there are no other PowPak modules being set up within the same building.
It is possible that Wireless Transmitters from other systems can be incorrectly associated to this system.

A. Hold the CCO Toggle button on the PowPak CCO Module for 6 seconds to enter association mode.

Note: The CCO will open and close once after eachstep to confirm successful completion.

B Hold the indicated button on a Wireless Transmitter for 6 seconds to associate the device.
Repeat for any additional Wireless Transmitters.

If no button, hold “Lights Off” button.

C. Hold the CCO Toggle button on the PowPak CCO Module for 6 seconds to save association(s).
D. Permanently install wireless transmitters (consult individual component installation guides for information).

Calibrate the Radio Powr Savr Daylight Sensor

Daylight Sensor will control all wired fixtures equally.

A. Press and release the “Cal” button on the Daylight Sensor.
B. Turn lights in room on using the CCO Toggle button on the PowPak CCO Module or an associated Pico wireless control.
C. Press and hold the “Cal.” button for 6 seconds.
D. Exit room for 5 minutes to allow calibration to be completed.
Note: When calibration has completed, all lights will flash and begin to respond to daylight.

CCO Information

• This product features a single contact closure output with both normally open (NO) and normally closed (NC) dry contacts.

• The CCO incorporates maintained output behavior only.


• The CCO is rated to switch resistive loads at  Switching

voltages up to 24 V only. To properly control        Voltage

inductive load types such as relays, solenoids, 0-24 V-

or motors, refer to Application Note #434.           0-24 V~

| Resistive Load R

1.0 A

0.5 A

Transmitting Device| Transmitted Command| CCO Default Action
Pico

Wireless Control

| On| NO = Close, NC = Open
Off| NO = Open, NC = Close
Raise| NO = Close, NC = Open
Lower| No Action
Preset| NO = Close, NC = Open
Radio Powr Savr Occupancy Sensor| Occupied| NO = Close, NC = Open
Unoccupied| NO = Open, NC = Close
Radio Powr Savr Vacancy Sensor| Occupied| No Action
Unoccupied| NO = Open, NC = Close
Radio Powr Savr Daylight Sensor| Ambient light below target level| NO = Close, NC = Open
Ambient light above target level| NO = Open, NC = Close

Reset Factory Defaults

Note: In some instances it may be necessary to reset the PowPak CCO Module back to factory default settings.

A .Rapidly tap the Advanced Operations (“ADV”) button on the CCO module three times and hold on the fourth time until the LED begins to flash at a rate of approx. 2 blinks every 1 second, then release the ADV button.
B. Within 3 seconds of the start of flashing of the LED on the CCO module, rapidly tap the ADV button on the CCO module three times again. Make sure to release the ADV button after the third press.
C. The LED will flash at a rate of 2 blink/3 seconds to indicate the unit has been reset to factory defaults.
Note: Any associations or programming previously set up with the unit will be lost and will need to be re-programmed.

Troubleshooting

CCO controlled device does not respond to Wireless Transmitter(s)

  • Ensure breaker to the PowPak CCO Module is on.
  • Ensure the CCO-controlled device has been properly wired to the PowPak CCO Module.
  • Ensure Wireless Transmitter is properly associated to PowPak CCO Module.
  • Ensure Wireless Transmitter’s battery is installed correctly.

Wireless Transmitter(s) cannot be associated to PowPak CCO Module

  • The maximum number of Wireless Transmitters have been associated to the PowPak CCO Module. To remove a previously set up Wireless Transmitter, tap the button used for association on the Wireless Transmitter three times, on the third tap hold for three seconds and then tap three more times.

Hereby, Lutron Electronics Co., Inc. declares that the radio equipment type RMKS-CCO1-24-B is in compliance with Directive 2014/53/EU.
The full text of the EU declaration of conformity is available at the following internet address: www.lutron.com/cedoc

Limited Warranty:
RMKS:
www.lutron.com/europe/ResourceLibrary/warranty/Limited%20Comm.pdf
RMNS:
www.lutron.com/asia/ResourceLibrary/warranty/Limited%20Comm.pdf

Customer Assistance:
Europe: +44.(0)20.7680.4481
India: +91.124.439.0130
Others: +1.610.282.3800
www.lutron.com/support

Lutron EA Ltd | 125 Finsbury Pavement, 4th floor London EC2A 1NQ, UK

Lutron, Pico, and PowPak are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. Radio Powr Savr and Vive are trademarks of Lutron Electronics Co., Inc. App Store is a trademark of Apple Inc., registered in the U.S. and other countries.
iOS is a registered trademark of Cisco in the U.S. and other countries and is used under license. Android, Google Play and the Google Play logo are trademarks of Google Inc. ©2013 – 2021 Lutron Electronics Co., Inc.

www.lutron.com/vive

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals