Technical Specifications
Installation
- Installation must be carried out by a qualified engineer in accordance with local regulations.
- Disconnect supply before installing.
- Install to a solid surface – vibrations may cause mis-triggering.
- Ensure environmental conditions are suitable for electronic equipment
Note: the blinds are optional, they may be inserted behind the lens for focussing the detection range.
Note: We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false triggering.
Direct junction “J” box mounting
- Separate control board (A) from facia (B) & junction box (C).
- Make electrical connections to the control board (A). See detailed wiring diagram on next page.
- Secure control board (A) to the junction box.
- Set up sensor modes as per sections 3 & 4 of this manual.
- Clip facial plate (B) to control board (A).
Surface mount assembly
- Separate control board (A) from facia (B) & Surface box (C).
- Securely mount surface box (C) to a flat and solid surface.
- Make electrical connections to control board (A). See detailed wiring diagram on next page.
- Set-up sensor modes as per sections 3 & 4 of this manual.
- Secure control board (A) to surface box (C).
- Clip facial plate (B) to control board (A).
Rotary Switch Settings
A rotary switch is built inside the sensor for scene selection / fast programming. Total 16 channels available:
Note: settings can also be changed by remote control HRC-11. The last action controls.
Sensor Mode Selection
Sensor mode can be easily selected by choosing the correct combination of the DIP switches (see table below):
- HF+PIR: Light is on when both HF and PIR sensors are activated.
- HF/PIR: Light is on when HF or PIR sensors are activated.
Wiring Diagram
Functions
Lux Off Function
The light dims to a minimum level and even switches off completely if ambient
daylight is sufficient (natural light level exceeds target lux level), no
matter it is during hold-time or stand-by time, with or without motion.
Note:
if the stand-by time is preset at “+∞”, the light never turns off even when
natural light is sufficient.
Daylight Harvest (Daylight Regulating)
The built-in daylight sensor can measure ambient natural light, and calculate
how much electrical light is needed to reach the target lux level. The demand
is given to the LED driver by 1-10V signal, so as to deliver the needed amount
of electric light. The target lux level can be adjusted by remote control or
long press on the push switch.
Manual Override (Push Function)
With the help of push-switch, this sensor may be overridden by the end-users
to switch on/off the lights manually or adjust the target lux level. This
makes the product more user-friendly and offers more options to fit for
extraordinary demands.
- Short push (<1s): on/off function;
- ON → OFF: the light turns off immediately and cannot be lightened for a certain time (equals to hold time preset) even if movement is detected. After this period, the sensor goes back to auto sensor mode.
- OFF → ON: the light turns on and goes to auto sensor mode.
-
- Long push (>1s): adjust the target lux level by turning the light up or down. Both the adjustment by remote control and push switch can overwrite each other, the last adjustment remains in memory.
Semi-auto Function ( Absence Detection)
The motion sensor is employed, but only activated on the manual press of the
push switch. With presence, the light remains on and can interact with ambient
natural light, then dims down in absence, eventually switching off
automatically after the stand-by time has expired.
Note:
end-user can choose either function 5.3 or 5.4 for application. Default
function is 5.3.
Detection Pattern
Description of the Button Functions
Permanent ON/OFF [ Button 1]
- Press button 1 to select permanent ON or permanent OFF mode.
- Press button 2/4 to resume automatic operation.
- The mode will change to AUTO Mode after power failure.
RESET [ button 2]
- Press button 2, all settings go back to the rotary switch settings.
- Sensor mode return to DIP switch settings.
Shift [ button 3]
- Press button 3, the LED on the top left corner flashes for indication.
- All values/settings in RED are invalid for 20 seconds.
Auto Mode [ button 4]
Press button 4 to initiate automatic mode. The sensor starts working and all
settings remain as before the light was switched ON/OFF.
Semi-auto Mode [ button 3 & 4]
- Press button 3 Shift (the red LED flashes for indication),
- Press button 4 to initiate semi-auto mode. The fixture is manually on by push-switch and automatically off in semi-auto mode.
Power output [ button 5]
Press button 5, the light output shifts between 80% and 100%.
Brightness +/- [ button 6]
Press button 6 to adjust light brightness to reset the target lux level.
Scene prog. [ zone 7] (One-key-commissioning)
-
Press button “Start” to program.
-
Select the buttons in 8 “Detection range”, 9/10 “Daylight threshold”,
11 “Hold time”, 12 “Stand-by time”, 13 “Stand-by dimming level” to set all parameters. -
Press button “Memory” to save all the settings programmed in the remote control.
-
Press button “Apply” to set the settings to each sensor unit(s).
For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +, stand-by dimming level 30%, steps should be:
Press button 7 Start, button 8 100%, Disable, 3 Shift, 11 5min, 3 Shift, 11 +, 13 30%, 7 Memory. By pointing to the sensor unit(s) and pressing 7 Apply, all settings are passed on to the sensor(s).
Detection range [ zone 8 ]
Press buttons 8 in zone to set HF detection range at 100% / 75% / 50% / 10%.
Daylight threshold [ zone 9 ]
Press buttons 9 in zone to set the daylight sensor at 50Lux / 100Lux / 300Lux
/ 500Lux or Disable as threshold/target Lux level.
Note: 2Lux / 10Lux are disabled.
To set the daylight sensor at 100Lux / 300 Lux / 500Lux, press button 3 Shift
at first.
Ambient daylight threshold [ button 10 ]
- Press button 3 Shift, the red LED flashes for indication.
- Press button 10, the ambient lux level is sampled and set as daylight threshold/target Lux level.
Hold time [ zone 11 ]
Press buttons in zone 11 to set the hold time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min.
Note:
- To set hold-time at 30s / 5min / 15min / 30min, press button 3 Shift at first.
- 2s is for test purposes only, stand-by time and daylight sensor settings are disabled in this mode.
To exit from Test mode, press button 2 or any button in zone 11.
Stand-by time [ zone 12 ]
Press buttons in zone 12 to set the stand-by time at 0s / 10s / 1min / 5min / 10min / 30min / 1h / +.
Note:
“0s” means on/off control; “+” means bi-level control, 100% on when motion
detected, and remains at the stand-by dimming level when no presence after
hold-time.
Stand-by dimming level [ zone 13 ]
Press buttons in zone 13 to set the stand-by dimming level at 10% / 20% / 30%
/ 50%.
Daylight harvest auto-configuration function
- Press button “Shift”, the red LED is on for indication.
- Select a time period and the sensor will do light level measurement and determine/save the lowest light level (commission line) with 100% light on, so as to set the target lux level automatically.
Note:
- Make sure the light level measurement covers the nighttime.
- The fixture will go into sensor mode after the measurement, all sensor settings remain unchanged.
Dual tech & RF mode [ zone 14 ]
-
Press buttons in zone 14 to select sensor technology.
HF+PIR: Light is on when both HF and PIR sensors are activated.
HF/PIR: Light is on when HF or PIR sensors are activated. -
Learn / Erase, Transmit, RX100% and RX STBY% are disabled.
Hytronik Industrial Ltd. | www.hytronik.com
3rd Floor, block C, complex building, 155#, Bai’gang road south, Bai’gang
village, Xiao Jin Kou town, Huicheng district, Huizhou 516023 Tel:
86-752-2772020 Fax: 86-752-2777877