ORTECH OD-ERV 150AC Energy Recovery Ventilators Instruction Manual
- May 15, 2024
- Ortech
Table of Contents
- ORTECH OD-ERV 150AC Energy Recovery Ventilators
- Product Information
- Product Usage Instructions
- Warning Instruction
- CLEANING & MAINTENANCE
- OPERATION
- LOCATION OF THE UNIT
- INSTALLATION GUIDE
- DUCTWORK
- EXHAUST & OUTSIDE AIR DUCTS
- LED INDICATOR LIGHT FAULT DESCRIPTION
- SERVICE PARTS
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
ORTECH OD-ERV 150AC Energy Recovery Ventilators
Product Information
Specifications
- Model: OD-ERV 150AC | OD-ERV 150-23
- Application: General ventilating use
- Filter Size: 9-1/2 x 7-1/4 x 3/8 (2 filters required per unit)
Product Usage Instructions
Installation
The installation of this Energy Recovery Ventilator must be carried out by a
qualified electrician to ensure safety and proper functioning.
Usage Guidelines
- Use the ventilator for general ventilating purposes only; do not exhaust hazardous materials.
- Avoid introducing drywall spray, construction dust, etc., into the unit to prevent motor damage.
- Before maintenance, always unplug the unit line cord.
Cleaning & Maintenance
Maintenance Requirements:
- Service filters every three months or as needed.
- Ensure the filters are clean to prevent blockage of the energy exchange core.
Cleaning Steps:
- Release the door spring clips and open the access door.
- Remove filter clips and filters for cleaning.
- Vacuum core and filters with a hose.
- Re-install filters and filter clips, then secure the door.
Cleaning the Energy Exchange Core:
- Annually, remove filters and the energy exchange core.
- Vacuum the exposed faces of the energy exchange core with a soft brush attachment.
- Clean out dust from the rest of the unit case.
CAUTION:
Do not wash the energy exchange core. Ensure the core latch is secured to
prevent damage or injury when maintaining the unit.
FAQ
-
Q: How often should I clean the filters?
A: Filters should be cleaned every three months or as needed to maintain efficiency. -
Q: Can I use finer filters in the unit?
A: Finer filters can be used but require more frequent cleaning to prevent blockage of the energy exchange core.
Warning Instruction
WARNING
THE INSTALLATION MUST BE CARRIED OUT BY A QUALIFIED ELECTRICIAN.
- For general ventilating use only. DO NOT use to exhaust hazardous or explosive materials and vapors
- To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. out of the unit
- Before maintenance, please unplug the unit line cord
Application Notice
- Blower wheels are sharp and can cause injury. Make sure it is not running before opening the door
- Before servicing or cleaning the unit, unplug the unit line cord or shut off power at the service switch or circuit breaker. Make sure the unit is not working before opening its door until the service or cleaning is completed
- This instruction manual shows the suggested installation method. Additional measures may be required by local codes and standards
- Connect this unit only to a 120V AC grounded circuit protected by a 15 amps circuit breaker
- DO NOT install units or controls where they can be reached from a tub or shower
- The Energy Recovery Ventilators MUST be properly ducted to the outdoors
- The outside air inlet for this unit MUST be located away from sources of hazardous air such as auto exhausts
- Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel-burning equipment, take steps to ensure that the combustion air supply is not affected. Follow the heating equipment manufacturer’s requirements and the combustion air supply requirements of applicable codes and standards
- When cutting or drilling into a wall or ceiling, DO NOT damage electrical wiring and other hidden utilities
- DO NOT connect power to the unit’s external control terminals — this will damage the unit. The external terminals are for use only with un-powered controls designed for low-voltage operation
- When door springs are disengaged, the ERV door can be hinged open to access internal components for routine maintenance and cleaning. Take precautions when disengaging the door springs to ensure the door does not cause any damage or injury. When the Energy Recovery Ventilator is installed so that the door swings down (upside down), lower the door down slowly
CAUTION
PLEASE READ THE INSTRUCTIONS BEFORE COMMENCING INSTALLATION AND RETAIN FOR
FUTURE REFERENCE. Electrical products can cause death injury, or property
damage. If in any doubt about the installation or use of this product, consult
a competent electrician.
CLEANING & MAINTENANCE
Maintenance Requirements
Service filters every three months or as needed when the unit is in regular
use to keep them reasonably clean
- Release the door spring clips and carefully swing the access door open. Remove the door if necessary
- Remove filter clips and pull out the filters
- Vacuum core and filters with a hose (not included)
- Re-install filters and filter clips
- Re-install door and secure door spring clips
- The filters should be replaced after they have been cleaned several times. The primary contact for replacement filters for your unit is the installing contractors. You may also wish to produce your own filters. Spun polyester filter media or material should be used similarly to the existing filter in the residential unit. The size of each filter (2 required per unit) is as follows: 9-1/2″ x 7-1/4″ x 3/8″
- Filters MUST be used, otherwise the face of the energy exchange core will become blocked by dust. The filters existing in the unit are usually able to keep the energy exchange core clear for many months. Finer filters can be used but MUST be cleaned more often
Clean the face of the energy exchange core annually:
- Remove the filters
- Remove the core latch and pull out the core
- Vacuum the exposed faces of the energy exchange core with a soft brush attachment
- After maintenance, re-install the core and filters
- Vacuum out dust from the rest of the unit case. Dust collects only on the entering faces of the energy exchange core. The interior of the energy exchange core stays clean even if the core faces are covered with dust
CAUTION!
- DO NOT WASH THE ENERGY EXCHANGE CORE:
- The energy exchange core can be replaced but is expensive.
- The core is secured to the unit by the core latch, when the unit is installed as installation B.
- If the core latch is disengaged, the core can fall out, causing damage or injury if not prepared after the door swings down. Ensure the core latch is secured until you are ready to remove the core for maintenance.
- Re-engage the core latch after maintenance to secure the core in place.
OPERATION
- RA = Return Air
- OA = Outside Air
- EA = Exhaust air
- FA = Fresh Air
- SA = Supply Air (furnace)
Features
- OA knob — Low airflow knob for OA, from 20%~100% of full speed or OFF, factory set at 100%
- RA knob — Low airflow knob for RA, from 20%~100% of full speed or OFF, factory set at 100%
- T knob — Timer knob for run-time per hour (minutes/hour), stepless adjustable from 0 to 60 minutes, factory set at 60 minutes
- RH knob — Relative humidity limit knob from 50%~100% or OFF. Factory set at 90% approximately
- Filter reset button
- L1 — Red indicator light
- L2 — Orange indicator light
Operating Instructions
-
Inspect your installation to be sure that all ductwork is correctly installed and sealed and filters are in place
-
Shut and latch the door to the unit. Plug the unit into a 120V AC power outlet. It will start immediately and run a one-minute system check. The Red indicator light (L1) and Orange indicator light (L2) will illuminate continuously. After one minute, the Red indicator light and Orange indicator light turn off, and the unit runs per the user’s setting
-
The unit runs at low speed (20-100% of full speed) set by the Outside Air (OA)/Return Air (RA) low airflow knobs for some time (0-60 minutes/hour) set by the timer knob. The manual override switch (MOS) boosts the unit to high speed. The unit returns to low-speed operation after the MOS is turned off
-
Humidity Sensor Operation
When the outdoor relative humidity exceeds the user-set limit (50-100% RH), the unit will stop running and enter a check cycle. The orange L2 LED indicator light will illuminate continuously. The check cycle will run the unit for 5 minutes at full speed every 15 minutes (25% of every hour) to sample the outside air conditions and meet code requirements.- The HVAC/AHU blower (if connected) will NOT run during this check cycle to prevent cycling. The MOS will still boost the unit to high speed during the check cycle and WILL activate the ** HVAC/AHU blower if connected
-
Temperature Sensor Operation
When the outdoor temperature falls below 14 degrees F, the unit will stop running and enter a check cycle. The orange L2 LED indicator light will illuminate continuously. The check cycle will run the RA fan for 5 minutes at full speed every 15 minutes (25% of every hour) to minimize frost on the core and meet code requirements. The OA fan will not run during this check cycle- The HVAC/AHU blower (if connected) will NOT run during this check cycle to prevent cycling. The MOS will still boost the ** RA fan to high speed during the check cycle and WILL NOT activate the HVAC/AHU blower if connected. Install an
- auxiliary duct heater upstream of the OA duct connection (minimum of 12″ clearance) if necessary.
-
Filter Service Indicator
The filters should be cleaned/replaced at a minimum of every 3 months, depending on outdoor air conditions.
The red L1 LED indicator light will illuminate continuously and will buzz once a second in 15 seconds every 2 hours after 3 months of motor operation. This indicates that it is time to clean/replace the filters. After servicing the filters, press and hold the filter reset button for 5 seconds. Four quick beeps will indicate that the buzzer has successfully been deactivated. Re- activate it by pressing the button once more.
Balancing Instructions
Balancing the airflow is done by setting the OA fan speed and the RA fan speed
to exhaust the same or similar airflow from and to the outdoors. Inspect your
installation to be sure all ductwork is correctly installed, sealed, and clean
filters are in place. The entire air delivery duct system needs to be in place
and all vents should be in their normal operating position.
- KEEP THE MOS SWITCH OFF, and plug the unit into a 120V AC power outlet.
- After one minute, L1 and L2 turn off, and the unit runs per the user setting.
Equipment required for testing airflows: A Magnehelic gauge (or manometer) or
other device capable of measuring 0 to 0.6 inches water gauge of differential
pressure. 2 pieces of tubing, 1/8” I.D., 1/16” wall thickness works best.
Individual differential static pressures (DP) are measured ACROSS the core,
using the installed pressure ports located on the removable door.
Keep the MOS off so the unit will run at a low speed. Open the pressure port
caps for the OA air stream and insert the tubing into the ports about 1”. Take
a DP reading and record it in section d.1. Adjust the OA fan speed control to
obtain the desired CFM per the table in section d.2. Enter the CFM information
in the box in Section d.2. Remove the tubing, close the pressure port caps,
and then repeat the process for the RA air stream.
Important Reminder
- After 30 days of unit operation, check/tighten all mounting and support hardware. Inspect filters for cleanliness. If filters appear dirty, replace or clean them.
- Whenever there is a reconfiguration of the HVAC system in a residence, the speed controls should be re-calibrated for optimum performance. If the residence undergoes significant structural changes, such as an addition to the home, the unit should also be re-calibrated. If optional MERV 13 filters are installed, recalibration is also required
- The unit provides the ability to deliver completely balanced airflows or to modify them as desired. In a perfect environment, airflows would be balanced so that there is no difference between OA (Outside Air) airflow and RA (Return Air) airflow. Many owners will prefer to have a slight imbalance, providing a slight excess of OA to reduce air infiltration into a house.
Some homes may require imbalance because a furnace or water heater is not direct-vented. If needed, an HVAC professional will be able to advise balance settings that will best address the circumstances in each house.
Manometer Readings at Commissioning
Pressure Drop to Airflow Conversion Table
Outside Air Flow:
LOCATION OF THE UNIT
Select a location so that:
- The fresh air inlet from the outside is placed a minimum of 10 feet from any other exhaust vent
- The two ducts to the outside are as short and straight as possible for the best system performance
- The door can be opened to clean the core and filters conveniently. Provide clearance at the front of the unit for service access to the blowers, filters, and energy exchange core (minimum 20-1/8″ for full door swing, 14-1/4″ for door removal from hinges)
- The exhaust outlet to the outside and fresh air inlet from the outside of the building should be at least ten feet apart to avoid cross-contamination. The exhaust duct should be about the same length as the fresh air duct
- The exhaust outlet should NOT dump air into an enclosed space or any other structure
The preferred mounting location for the unit is on a concrete foundation wall because the foundation wall isolates any blower vibration. If a basement area is not available or practical, use other mechanical room space such as a closet, garage, storage, or accessible attic or crawl space.
- If you locate the unit in an attic or other unconditioned space, all of the unit’s ductwork that is located in the attic MUST be ** insulated. Use at least R-6 insulation
INSTALLATION GUIDE
CAUTION!
RISK OF INJURY WHEN LIFTING AND INSTALLING UNIT OVERHEAD: Get a helper and
wear eye protection and gloves.
- Locate the unit for the simplest duct layout and connections.
- Note that the door is equipped with hinges. For the homeowner’s convenience, it is helpful to locate the unit so that the door does not drop off when it is unlatched.
Unit Installation
Installation A
- Mount the 4 brackets to the unit as illustrated at right, using two screws provided for each bracket through 2 appropriate holes. The unit may be installed in any orientation. Be careful as condensation could be present when the outdoor temperature is low
- Secure the unit to the truss by screws provided through the smaller hole of the brackets
Installation B
- Trace a level line on both trusses, at 1-1/16″ from the bottom b1) (based on the ceiling sizes is 1/2″, if not this size, needs to be adjusted properly), for the unit bracket location. On one truss, screw halfway on level line two provided screws, leaving 24-7/8″ between each other
- Mount the 4 brackets to the unit as illustrated on the right, using 2 screws provided for each bracket through 2 appropriate holes. b2) Screw halfway the screws to allow adjustment between trusses within b2) 23″ and 21-1/4″ (left shows the minimum distance and right the maximum distance)
- Hang the one side of the unit on the screws mounted on the a1) truss. Lift the other side of the unit and secure it to the other a1) truss. Mount the unit to the truss using 2 screws per bracket.
- After installation, the bottom of the unit is in contact with the a2) bottom of the ceiling.
DUCTWORK
-
For Houses WITHOUT Ducted Heating or Cooling Systems (see Fig.2)
In most houses, one or two fresh air grilles in a central part of the house provide effective distribution of the fresh air into the home, particularly when the stale exhaust air is picked up at several points. Because the fresh air is usually somewhat cooler than the indoor air, the fresh air supply grilles should be located in a traffic area like a hallway or stairway rather than in a sitting area. If you want to get fresh air into specific room with high occupancy, you can split up the fresh air supply. -
For Houses WITH Forced-air Heating and Cooling Systems (see Fig.1, Fig.3, and Fig4)
- Most units are installed with the fresh air duct connected directly to a return duct for the main heating and cooling system.
- Make sure to connect the fresh air duct at least 3 feet from the return plenum to minimize suction from the furnace blower. A connection closer to the furnace may result in unbalanced flow or other associated problems.
-
For Installations that Collect Stale Air from Specific Rooms in the Home (see Fig.1 and Fig.2)
Locate stale air return grilles (RA) in rooms where moisture and odors are generated: bathrooms, kitchens, and perhaps areas where contaminants may be generated such as the home workshop. Return grilles in these areas such as the home workshop may be dampened so that they can be shut off when not in use. A central location such as a hallway is also acceptable, but it would not clear humidity and odors from baths and kitchens quickly. Locate stale air return grilles (RA) near the ceiling on the inside walls. Stale air returns are usually easiest to install in interior partitions.
EXHAUST & OUTSIDE AIR DUCTS
The exhaust air (EA) duct and the outside air (OA) duct connect the unit to the outside. Flexible insulated duct is usually used.
WARNING!
DO NOT PLACE ANY STALE AIR RETURNS IN GARAGES.
Installing Outside Air (OA) & Exhaust Air (EA) Ducts
Ducts connecting the unit to the outside MUST be well-insulated. A vapor
barrier is required on both the inside and outside of the insulation. The
inlets and outlets should be screened against insects and vermin and shielded
from the weather to prevent the entry of rain or snow.
CAUTION!
-
The vapor barrier should be continuous and sealed against air and moisture leakage.
If not, condensation or ice may form in cold weather on the duct surface or in its insulation. -
INSTALL FRESH AIR INLET AWAY FROM SOURCES OF CONTAMINANTS
- DO NOT locate the fresh air inlet where vehicles may be serviced or left idle
- The fresh air inlet should be at least 10 feet away from any exhaust such as dryer vents, chimneys, furnaces, and water
- heater exhausts or other sources of contamination or carbon monoxide
- NEVER locate the fresh air inlet inside a structure
Installing Return Air (RA) Ducts
All the stale air returns are connected by ducts to the unit. Generally, empty
stud cavities are used for returns as is often done with cold air returns for
the furnace, using standard duct boots to connect to a six-inch pipe at the
bottom or top of the wall cavity. Always be sure to seal all joints with duct
sealant or tape. Some local codes may require metal ducting from the boots to
the stale air grilles. Rigid ducts will allow the air to move freely and
easily through the ducts.
DO NOT use more flex ducts than necessary:
Flex ducts are much more resistant to airflow than rigid ducts. Longer runs of
flex ducts will reduce the ventilation performance of your system. Stretch the
flex duct and avoid sharp bends.
CAUTION!
- DO NOT connect dryers directly to the unit
- DO NOT connect range hoods to the unit
- SEAL ALL DUCT COLLARS AT THE UNIT TO MINIMIZE AIR LEAKAGE
WARNING!
DANGER OF ELECTRIC SHOCK WHEN SERVICING THE UNIT: ALWAYS unplug the unit
before connecting or servicing controls.
ELECTRICAL CONNECTIONS
WARNING!
UNPLUG THE LINE CORD BEFORE WORKING ON THE UNIT.
- Run 120V AC house wiring to the location of the fan. The unit comes with a grounded 3-prong power cord for connection to an electrical outlet.
OPTIONAL CONNECTIONS
- The unit has an optional terminal block for 24VAC HVAC/AHU blower integration. The user can connect the HVAC/AHU 24VAC dry contact relay to the terminal block so that when the ERV is operating, the HVAC/AHU blower operates to help distribute the fresh air through the existing ductwork if needed.
- The unit has an optional terminal block for a MANUAL OVERRIDE SWITCH (MOS) connection. Connect an on/off switch to the terminal block to manually switch the unit to high speed. When the switch is off, the unit returns to the low-speed operation per the OA, RA, and T knobs.
- The unit has an optional terminal block for a WALL TIMER SWITCH(WTS) connection. In the case of the timer activation, the unit goes to the high-speed mode and runs for the set time.
- The optional terminal block is not required for the unit
WALL TIMER SWITCH (OPTIONAL) OPERATION
- Press the button, L1 Indicator lights up, the timer setting for 20 mins, and ERV runs at high speed, after the timer delay of 20 mins, ERV gets back to low-speed operation per the OA, RA, and T knobs and the indicator goes out.
- Press the button twice quickly, and the L2 indicator lights up, timer setting for 40 minutes, the ERV runs at high speed, and the L1 and L2 indicator light up after 20 minutes; ERV gets back to low-speed operation per the OA, RA, and T knobs after 40 mins and indicator go out.
- Press the button 3 times quickly, and the L3 indicator lights up, timer setting for 60 minutes, the ERV runs at high speed, and the L2 and L3 indicator light up after 20 minutes; the L1 and L3 indicator light up after 40 mins; ERV get back to low-speed operation per the OA, RA, and T knobs after 60 mins and indicator go out.
- Press the switch 4 times, the Cont indicator lights up and ERV goes into high-speed running, press the switch again, and the Cont dictator is put out, ERV runs at the speeds, and the timer delay per knobs is adjusted.
LED INDICATOR LIGHT FAULT DESCRIPTION
SERVICE PARTS
Contact Information
- info@ortechindustries.com
- www.ortechindustries.ca
- 13376 Comber Way Surrey BC V3W 5V9 205 Summerlea Rd Brampton, ON L6T 4E5
- 1-888-543-6473
- 1-888-541-6474
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>