HYTRONIK HBIR29SV-RH PIR Standalone Motion Sensor with Mesh Instruction Manual
- May 15, 2024
- HYTRONIK
Table of Contents
- HYTRONIK HBIR29SV-RH PIR Standalone Motion Sensor with Mesh
- Product Usage Instructions
- Technical Specifications
- Download the App
- Installation
- To Reprovision
- Placement Guide and Typical Range
- Detection Pattern & Optional Accessories
- Additional Information / Documents
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
HYTRONIK HBIR29SV-RH PIR Standalone Motion Sensor with Mesh
Technical Specifications
- Operation frequency: 2.4 GHz – 2.483 GHz
- Transmission power: 4 dBm
- Range (Typical indoor): 10~30m
- Protocol: Mesh
- Operating voltage: 220~240VAC 50/60Hz
- Stand-by power: Knowledge
- Switched power: PIR Sensors – Precautions for ProductInstallation and Operation
- Warming-up Sensor principle
- Detection range (Max.): HBIR29/SV/RH
- Detection angle
- Operation temperature
- IP rating
- Standard compliance
- Certification: HBIR29/SV/RH-20230831-A0
Product Usage Instructions
Installation
- Ensure the power source meets the specified operating voltage of 220~240VAC 50/60Hz.
- Mount the PIR Standalone Motion Sensor in a suitable location within the detection range of 10~30m.
- Follow the provided guidelines for installation to ensure proper functioning.
Operation
- The sensor operates on a Mesh protocol within the specified frequency range.
- Familiarize yourself with the detection angle and adjust the sensor placement accordingly.
- Ensure the sensor is not obstructed and has a clear line of sight within its detection range.
Maintenance
- Regularly check for any physical obstructions that may interfere with the sensor’s operation.
- Clean the sensor periodically to prevent dust or debris build-up that could affect performance.
Frequently Asked Questions (FAQ)
Can I install the sensor outdoors?
It is recommended to install the PIR Standalone Motion Sensor indoors for
optimal performance.
How can I adjust the detection range of the sensor?
The detection range is fixed and cannot be adjusted manually.
Ensure proper placement within the specified range for best results.
Technical Specifications
Operation frequency | 2.4 GHz – 2.483 GHz |
---|---|
Transmission power | 4 dBm |
Range (Typical indoor) | 10~30m |
Protocol | Mesh |
Operating voltage | 220~240VAC 50/60Hz |
Stand-by power | <0.65W (Empty load) |
Switched power | I guaranteed: 44mA |
I max: 80mA
Warming-up| 5s
Sensor principle| PIR detection
Detection range (Max.)* HBIR29/SV/RH| Installation height:20m (forklift)
12m (person)
Detection range (Ø):40m
Detection angle| 360O
Operation temperature| Ta:-20OC~+50OC
IP rating| IP20
Standard compliance
| EN300328, EN301489-1, EN301489-17, EN62479, EN55015, EN61547, EN60669-1, EN60669-2-1,
EN62493
Certification| CE
Download the App
The access to Silvair apps mobile app: Silvair on the App Store web app: platform.silvair.com
Installation
Mechanical Structure & Dimensions
- Ceiling (drill hole φ66~68mm)
- Carefully prise off the cable clamps.
- Make connections to the pluggable terminal blocks.
- Insert plug connectors and secure using the provided cable clamps, then clip terminal covers to the base.
- Fit detection blind (if required) and desired lens.
- Clip fascia to body.
- Bend back springs and insert into ceiling.
Wire Preparation
Pluggable screw terminal. It is recommended to make connections to the terminal before fitting to the sensor.
- 200 metres (total) max. for 1mm² CSA (Ta = 50℃)
- 300 metres (total) max. for 1.5mm² CSA (Ta = 50℃)
Wiring Diagram
Mesh Factory Reset
The device HBIR29/SV/RH can be reset by placing a strong magnet (e.g. N38 neodymium magnet, d=10mm*h=4mm) near the sensor lens for 5 seconds. Once the factory reset is done successfully, the luminaire flashes and then permanent on, then the device is being able to be re-commissioned by SILVAIR app.
To Reprovision
Place a strong magnet on the site of the Reset/Hall effect sensor (see diagram 4 below). To trigger the reset the magnet must be held in position for 5 seconds.
Diagram
Note: When change the lens part of HBIR29/SV/RH, please kindly make sure that the lens fits the right location,where the “Reset dot” and “BLE dot”matches with the physical location on the PCB.
Status LED blinking Sequence
HBIR29/SV/RH Unprovisioned | 30ms ON | 300ms OFF |
---|---|---|
HBIR29/SV/RH Provisioned | 15ms ON | 2,000ms OFF |
Factory reset | 500ms ON | 1,000ms OFF |
Factory reset (initial burst) | 100ms ON | 1,000ms OFF |
MESH package received | 30ms ON | 50ms OFF |
Attention (from network) | 500ms ON | 500ms OFF |
Big and small silicon gasket used to make IP54 degree protection when HBIR29/SV/RH series device mounted into HA03 housing for ceiling mount
Placement Guide and Typical Range
The smart device with the App installed will have a typical range of 10m, but varies from device to device. During commissioning, the installer will need to be in range of the devices when searching for devices to add to the network.
Once the devices have been added to the network via the App, the devices will
start communicating within the wireless mesh.
This means that once the network is complete, all devices are accessible from
the smart device when in a 20m range of a single point.
Detection Pattern & Optional Accessories
HBIR29/SV/RH (Reinforced High-bay with 3-Pyro)
HBIR29/SV/RH: Reinforced high-bay lens detection pattern for forklift @ Ta =
20ºC
(Recommended ceiling mount installation height 10m-15m)
HBIR29/SV/RH: Reinforced high-bay lens detection pattern for single person @
Ta = 20OC
(Recommended ceiling mount installation height 2.5m-12m)
Optional Accessory – Ceiling/Surface Mount Box: HA03
Additional Information / Documents
- Regarding precautions for PIR Sensors installation and operation, please kindly refer to www.hytronik.com/download->knowledge->PIR Sensors -Precautions for Product Installation and Operation
- Data sheet is subject to change without notice. Please always refer to the most recent release on www.hytronik.com/products/bluetooth technology ->Partnership
- Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download ->knowledge ->Hytronik Standard Guarantee Policy
Subject to change without notice.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>