AJAX FISMHTCJ1UL Smoke Heat and CO Alarm User Guide
- June 17, 2024
- ajax
Table of Contents
- FISMHTCJ1UL Smoke Heat and CO Alarm
- Functional elements
- Installation
- FCC Regulatory Compliance
- Operation principal
- Adding to the system
- Indication
- Detector testing
- Testing at the place of installation
- Selection of installation place
- Malfunctions
- Maintenance
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
FireProtect 2 RB
(Heat/Smoke/CO) Jeweller
FISMHTCJ1UL Smoke Heat and CO Alarm
Model name : FP2. RBHSC.J-000-NA UL
Product name: Smoke, heat, and CO alarm
xxx — digtts from 0 to 9 indicate the device modification
Quick start guide
Before using the device, we strongly recommend reviewnig the User Manual an
the website
Functional elements
- The front panel of the detector with a Test/Mute button.
- Smart6racket mounting panel
- Device QR code and ID (serial number).
- Tamper button.
- information on the certification of the detector.
- Service button.
- First thenmistor.
- Green LED indicator.
- Yellow LED indicator
- Red LED indicator.
- Siren.
- Second thermistor
- Information about the detectors end of life date.
- Smoke chamber lid.
Installation
- Remove the SmartBracket mounting panel from the detector. To remove the panel, turn it counter-clockwise.
- Fix the SmartBracket panel to a surface using double-sided adhesive tape or other temporary fasteners. The mounting panel has an UP sign, which indicates the correct position.
- Run the Jeweller signal strength test. The recommended value is two or three bars. If the signal strength is a single bar or lower, we cannot guarantee the stable operation of the detector. Consider to relocate the device as repositioning even by 20 cm can significantly improve the signal strength. If there is still low or unstable signal after the relocation, use a radio signal range extender.
- Remove the detector from the mounting panel.
- Mount the SmartBracket panel with the bundled screws using all fixation points. When using other fasteners, make sure they do not damage or deform the mounting panel.
- Place the detector on the SmartBracket mounting panel.
- Adjust the position of the detector if necessary.
FireProtect 2 RB (Heat/Smoke/CO) Jeweller is a wireless smoke, heat, and CO alarm.
Frequency range | 905-926 5 MHz FHSS tcomplies with Part 15 of the FCC rules) |
---|---|
Power density RF | $0.60 mWicr2 |
Radio signal range | up to 5.500 ft (in an open space} |
Power requirements | 2 battenes CR1234, 3 V |
Operation from battery | up to 5 years |
Operating temperature range | from 32 °F to 100 °F |
Operating hurnidity | from 10% lo 80% |
Dimensions | 4.87 » 4.87 x 1.76″ |
Weight | 9.68 oz |
Complete Set:
- FireProtect 2 RB (Heat/Smoke/CO) Jeweller,
- 2 batteries CR123A (pre-installed);
- Installation kit;
- Quick start guide.
CAUTION: RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE.
DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS.
Smoke detectors are not to be used with detector guards unless the combination
has been evaluated and found suitable for that purpose.
FCC Regulatory Compliance
This device complies with Part 15 of the FCC Rules. Operation is subject to
the following two conditions: (1) this device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
Changes or modifications not expressly approved by the party responsible for
compliance could void the user’s authority to operate the equipment.
To maintain comphance with FCC’s RF Exposure guidelines, This equipment should
be installed and operated with a minimum distance between 20 cm the radiator
and your body: Use only the supplied antenna.
This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses and
can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications However, there is no guarantee that interference will not occur
in a particular installation.
If this equipment does cause harmful interference to racho or television
reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one or more of the
following measures.
- Reorient or relocate the receiving antenna
- Increase the separation between the equipment and the receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
ISED Regulatory Compliance
This device contains a license-exernpt transrnitter(s)/receiver(s} that comply
with Innovation, Science and Economic Development Canada’s license-exempt
RSS(s).
Operation is subject to the following two conditions:
- This device may not cause interference.
- This device must accept any interference, including interference that may cause undesired operation of the device.
Warranty: The warranty for devices is valid for two years after the
purchase date and does not apply to the supplied accumulator/battery.
If the device does not work correctly, you should first contact the support
service — in half of the cases, technical issues can be solved remotely.
The full text of the warranty is available on the website:
ajax.systema/warranty.
User Agreement: ajax.systems/end-user-agreement.
Technical support: support@ajax.systems.
Operation principal
The detector is equipped with a siren (prezoelectric buzzer) for audible
notification of alarms and events with a volume of up to 85 dB at a distance
of 3 metres from the detector) The detector is always active, so it responds
to a fire 24/7, regardless of the system’s arming mode.
The fire alann’s signal is clearty recognizable over any other signal due to
specific sound and LED indication even when the non-fire detector’s signal is
initiated first. You can learn more about the types of alarm and event
indication in the section on indication description.
FireProtect 2 ts protected by two tampers. The first tamper controls the
removal of the detector from the SmartBracket mounting panel:
the detector reacts with LED indication and sends notifications to users in
Ajax apps and to the monitoring station of the secunty company. The second
tamper signals the removal of the smoke chamber cover, which is located under
the detector front panel.
Ajax automation devices can respond to FireProtect 2 alarms and perform user-
defined actions using automation scenarios.
Hub is necessary for Interconnect functionality
Operation without a hub
FireProtect 2 can be used without connecting to the Ajax hub. It is enough to
install the detector following the instructions in this manual and switch it
on.
In case of autonomous operation, the detector notifies of fire alarms only
with an acoustic signal and LED indication, but does not send notifications to
the user’s smartphone, Ajax Translator, or PRO Desktop. At the same time, the
interconnected fire detector alarm function is Not available.
Smoke detector
FireProtect 2 detects smoke and does not react to water vapour thanks to a
bispectral optical sensor with blue and infrared LEDs. Inside the smoke
chamber, the LEDs emit light with different wavelengths. This technology helps
the detector to determine the size of the volatile particles and only react to
smoke.
Temperature sensor
Two built-in Class A thermistors are responsible for detecting a sharp rise
and exceeding the temperature threshold in FireProtect 2. This class of
thermistors triggers an alarm when a sharp temperature rise or static
temperature from 135 °F is detected.
CO (carbon monoxide) sensor
Achemical sensor built into FireProtect 2 detects dangerous levels of carbon
monoxide. The principle of operation of the sensor is based on the detection
of carbon monoxide through a chemical reaction, The sensor contains an
electrolyte bath. When a certain concentration of carbon monoxide is reached,
a chemical reaction is triggered. which is read by the detector and
transformed into an alarm signal.
The detector triggers an alarm if the carbon monoxide concentration is.
- 70 ppm alarm response time — 60-240 minutes;
- 150 ppm alarm response time — 10-50 minutes;
- 400 ppm alarm response time — 4-15 minutes.
Test/Mute button
Test/Mute button has the following functions:
- Upon pressing the button measures its sensitivity,
- If the alarm operates correctly, the sound and LED indication ensues;
- If the smoke sensitivity malfunctions, the yellow LED will flash 2 times in a row after pressing the Test/Mute button.
Interconnected Fire Detectors Alarms
All fire detectors of the FireProtect 2 product line support the
Interconnected Alarm function. This function activates the built-in sirens of
all fire detectors in the system as soon as at least one of the fire detectors
detects an alarm. Sirens of FireProtect 2 detectors are activated within 20
seconds after an alarm is detected. The FireProtect 2 detectors have different
sound and LED indications of alarm types to make it easier for users to
distinguish between them. In case of interconnected alarm, all FireProtect 2
detectors indicate exactly the alarm type detected by the initiating detector.
Sending events to the monitoring station
The Ajax system can transmit events and alarms to the PRO Desktop monitoring
app as well as the Central Monitoring Station (CMS) via SurGard (Contact ID),
SIA DC-09 (ADM-CID), ADEMCO 685, and other protocols. Addressability of Ajax
devices allows you to send not only events but also the type of the device,
the name, virtual room, and security group assigned to it to the PRO Desktop
and to the CMS.
The following versions of the application shall be used in order to achieve
proper operation of the alarm: Android 2.36/ PRO 1.28;iOS 2.34/ PRO 1.28; Ayax
PRO Desktop 3.17, Malevich 2.19.0).
Adding to the system
Before adding a device
- Install the Ajax app.
- Create an account if you don’t have one.
- Add a hub compatible with the detector to your app. Set the required settings and create at least one virtual room
- Make sure that the hub is on and has Intemet access via Ethemet, Wi-Fi, and/or mobile network. You can do this in the Ajax app or by looking at the LED indicator of the hub. it should light up white or green.
- Make sure that the hub does not start updates and that it is disarmed by checking the status in the Ajax app.
A PRO or a user with system setup nghts can connect the device to the hub.
To connect to the hub, the detector should be within the coverage area of the
hub radio network To operate via a radio signal range extender, first connect
the detector to the hub and then to the range extender. You can do this in the
range extender settings in Ajax apps.
How to connect FireProtect 2 to a hub
- Open the Ajax app.
- Select the hub if you have several of them or if you are using the Ajax PRO app.
- Go to the Devices tab. Press Add Device.
- Enter the name of the device.
- Scan the QR cade or enter the ID manually. GR code is located on the rear part of the enclosure (under the mounting panel) and on the device packaging. The device ID can be found below the QR code.
- Select the virtual room and security group (if the group mode is enabled).
- Click Add; the countdown will begin
- Turn on the detector by holding the service button for 3 seconds. The hub connection request is sent only if the detector is enabled.
If the detector fails to connect to the hub, try again in 5 seconds.
The detector cannot connect to the hub if they operate on different radio
frequencies. The radio frequency range of the device may vary by region.
Please contact technical support for information on the operating frequency
range of your devices.
Once connected, FirePratect 2 will appear in the hub device list in the Ajax
app. Device status update depends on the ping interval set in the Jeweller or
Jeweller/Fibra settings The defautt value is 36 seconds FireProtect 2 only
works with one hub. When connected to a new hub, the detector stops
transmitting data ta the old hub. Once added to a new hub, FireProtect 2 is
not removed from the list of devices of the old hub. This must be done
manually in Ajax apps.
Autonomous operation mode
FireProtect 2 detectors can be used autonomously without connecting to an Ayax
hub. In this case, the detector notifies of fire, smoke, or dangerous CO level
with only a built-in siren and LED indication
To use the detector autonomously, follow these steps:
- Select the optimal location of the detector using the recommendations in the Selection of installation place section.
- Mount the detector on the SmartBracket panel as described in the Installation section.
- Press the service button to switch on the detector.
- Start a self-test with the Test/Mute button. Press the centre of the front panel and hold it for 1.5 seconds.
During a self-test FireProtect 2 notifies about each step with a built-in
siren and LED indication. Once a self-test is completed, the LED indication
turns off, and the detector works autonomously.
In case of an alarm, press the Test/Mute button or eliminate the cause of the
alarm to mute the siren.
Indication
**LED indication** |
**Sound indication** |
**Event** |
**Notes** |
---|---|---|---|
The red LED flashes 3 times every 1.5 seconds, | The siren sounds in time with | ||
the LED indication. | Alarm by: smoke; temperature threshold exceeded. | The |
detector stops alarming as soon as its sources are eliminated. Also, you can
mute the alarm by pressing the Test/Mute button.The LED and sound indications
resume if the source of the alarm is stil present after the muting timer (10
minutes) has expired.
The red LED flashes 4 umes every 5 seconds.| The siren beeps in time with the
LED indication| Alam by dangerous CO (carbon monoxide) level.| The detector
will stop alarming as soon as the CO level drops below 70 ppm. You can also
mute the alarm by pressing the Test/Mute button. The alarm cannot be muted if
the CO level exceeds 400 ppm. The LED and sound indications resume if the
source of the alarm is still present after the muting timer (10 minutes) has
expired. The signal is repeated until the alarm resets after dissipation of CO
or the alarm signal is manually silenced.
No.| Short, low tone beep.| Prohibition on alarm muting.| The sound is played
after pressing the Test/Mute button, The alarm cannot be muted if the CO level
exceeds 400 pprn.
The red LED flashes every 4 seconds.| No.| Muted alarm.| The detector stops
alarming as soon as its source is eliminated.
The red LED flashes 2 times in a row| No.| Restore after alarm.| if the source
of the alarm is removed, the detector is restored automatically.
The yellow LED lights up for 1 second.| No.| Tamper alarm. The cletector is
removed from the SinartBracket mounting panel.| To turn on the detector, hold
the service button for 1 second.
Green, yellow, and red LEDs light up in turn, then go off.| No.| Turning the
detector on,| To turn off the detector, hold the service button for 2 seconds.
Green, yellove, and red LEDs light up at the same time then go off in reverse
order.| No.| Tuming the detector off.| The indication tums off after the
detector is connected to the hub.
The green LED is permanently on.| No.| Connection to the hub in progress,| The
indication turns on when the detector receives information that it has been
removed from the hub.
The green LED flashes 6 times in a row.| No.| The detector has been removed
from the hub.| All malfunctions are displayed in the detector states in Ajax
apps. Fields with malfunctions are highlighted in red. If the detector needs
to be tepaired, contact our Technical Support.
The yellow LED flashes 2 times in a row every minute.| The siren beeps in
time with the LED indication every minute.| Malfunction detected.| You can
replace batteries in a detector with teplaceable batteries only (has RB in its
name).
The yellow LED flashes. once per minute.| The siren beeps in time with the LED
indication once per minute.| Low battery level,| A detector with sealed
batteries (with SB in the name) should be reptsced with a new one after the
battenes are discharged.
The yellow LED constantly flashes| No.| The battery is completely discharged.|
You can replace batteries in a detector with teplaceable batteries only (has
RB in its name). Adetector with sealed batteries (with SB in the name) should
be replaced with a new one after the batteries are discharged.
The red LED flashes 5 times during the smoke chamber test. Then flashes 3 more
times but slower during the CO sensor test.| The siren beeps 5 times during
the smoke chamber test. Then it makes 3 longer beeps during the CO sensor
test.| Performing a self-test.| The test can be started by pressing the
Test/Mute button or in the detector settings in the Ajax app In CO-free
versions, only the smoke chamber is tested.
The yellow LED flashes 3 times in a row every minute.| The siren beeps 3 times
every minute.| The device service life has expired.| The device has operated
for more than 10 years. The sensitivity of its sensors may have decreased. We
recommend replacing this detector with a new one.
LEDs and the built-in siren of the detector can report alarms as well as
certain states of the detector.
If an alarm by smoke/termperature occurs at the same time as a dangerous CO
level alarm, the detector starts the indication of a smoke alarm.
Detector testing
Functionality testing
Testing with Test/Mute button
Test/Mute button testing is available when there are no alarms in the device
including both its own and interconnected alarms, When there are alarms
present, pressing the button for the first time will silence all alarms on the
device. Subsequent presses will have no effect since the device initiated the
alarm. Testing on the detecting device will not start.
Test/Mute button principle of operation:
-
Press and hold the button for 1.5 second.
-
When the test command is accepted, all LEDs will turn on simultaneously. Once the LEDs are lit, the test will be executed regardless of whether the button is released or held down.
-
The test’s duration is 5 seconds. At the Sth second of the test, the green and yellow LEDs tun off and the red LED will start indicating an alarm, If the sensor detects a fault, the light and sound notification will be the same as described in point 5 (below).
-
Smoke and Heat chamber test is performed first, followed by the CO sensor test. There are approximately 1-second pauses between light and sound notifications.
-
Incase of test failure (Fault), the green and red LEDs will tum off on the 3rd second, and the sensor emits a chirp (Fault) instead of the typical test notification that is 2 beeps and 2 blinks of yellow LED.
-
If a fault is detected, the test is initiated as described in point 1. If the fault persists, the results should be displayed as in point 5.
-
The light indication should correspond to the sound patterns for Heat/Smoke and CO (for sensors equipped with CO detection).
-
The application receives an event about the result:
a, For FP2 (Heat/Smoke) — 1 event: smoke chamber status
b. For FP2 (Heat/Smoke/CO) — 2 events: smoke chamber status and CO sensor status. -
The “Test” button can abort the test instantly at any moment, including immediately after the test initiation. In this case the test results are not displayed on the hub.
-
Bracket tamper status is ignored during the self-test.
CAUTION: If there is dust, stearn or smoke in the smoke charnber, the
test must not be performed.
Mute
- In the event of an alarm, pressing the ‘Test” button or muting from the application will silence the audio notification for 5 minutes.
- In muted mode, the red LED on the alarm initiator flashes in Muted alarm mode once every 4 seconds until the alarm expires or the muting timer expires.
- When attempting to mute when interconnect is active, each press of the “Test” button produces an audible alert (Prohibition/Ervor).
- When a new alarm occurs on a device with an already muted alarm, the muted alarms are canceled, and the notification starts according to priority.
Heat/Smoke always has priority in light and sound notification. That means if
there are two alarms, Heat/Smoke and CO, the light and sound indication is the
same as described for Heat/Smoke, regardless of which alarm occurred first.
Testing via app
To run the test in the Ajax app:
- Open the Ajax app.
- Select the hub if you have several of them or if you are using the Ajax PRO app.
- Go to the Devices menu.
- Select FireProtect 2 (Heat/Smoke/CO)
- Go to the settings by clicking on the gear icon.
- Click on the Self-test field.
After starting the test, the red LED of the detector blinks 5 times in a row
and then blinks 3 more times but slower. The detectar’s siren sound in time
with an LED indication, When the test is over, users receive a notification
about the detector state in Ajax apps.
The detector also notifies about the test result with sound and LEO
indications. If the test is failed and a malfunction is detected, the detector
starts to Indicate a malfunction 3 seconds after the test is begun: the yellow
LED blinks twice, and the siren beeps in time with the LED indication.
If no sound and LED indications occurred during the self-test, the detector
may not be used. Contact our Technical Support.
Testing at the place of installation
Ajax system provides several tests to select the correct installation place of
devices. Jeweller Signal Strength Test is available for FireProtect 2. The
test determines the strength and stability of the signal at the intended
location of the device.
To run the test in the Ajax app:
- Select the hub if you have several of them or if you are using the Ajax PRO app.
- Go to the Devices menu.
- Select FireProtect 2 (Heat/Smoke/CO).
- Go to the settings by clicking on the gear icon.
- Select Jeweller Signal Strength Test.
- Perform the test following the tips in the app.
States
The states include information about the device and its operating
parameters, You can see FireProtect 2 (Heat/Smoke/CO) states in Ajax apps. To
access them:
- Open the Ajax app.
- Select a hub if you have several of them or if you are using the Ajax PRO app.
- Go to the Devices tab.
- Select the device from the list.
Parameter | Meaning |
---|---|
Temperature | Air temperature in the room where FireProtect 2 is installed. |
Measured in Celsius or Fahrenheit degrees depending on the app settings. In
the normal state, the temperature value is displayed in black. When the
temperature rises, the field is highlighted with red.
Jeweller Signal Strength| Jeweller signal strength between FireProtect 2 and
the hub or radio signal range extender. The recommended value is two or three
bars.
Connection via Jeweller| Connection status between FireProtect 2 and the hub
or range extender via Jeweller.
Online — the detector is connected to the hub or range extender. Normal state.
Offline — no connection between the detector and the hub or range extender,
Check the detertor connection.
Battery Charge| The battery charge level of the device:
OK — detector batteries have sufficient charge. Normal state.
Battery low — detector batteries are discharged.
When the batteries are discharged, users and the security company monitoring
station receive a nabficatian. After the low battery notification, the
detector is able to aperate far another month under narmal conditions. In case
of an alarm, the battery charge is enough to ensure 4 minutes of the sound and
LED indication aperatian.
Lid| The status of the detector’s tamper that responds to detachment af the
device from the surface or opening of the enclosure:
Open — the detector is removed from the Smart Bracket mounting panel, or
the enclosure integrity is violated in another way. Check the mounting of the
detector.
Closed — the detector is installed on the SmartBracket mounting panel.
The integrity of the device enclosure and the mounting panel is nat victated.
Normal state.
Smoke| Smoke sensor status:
Clear — normal state, the detector does not detect smoke.
Alarm — the detector detects smake.
If smoke is detected, the text field highlights red.
Temperature Threshold Exceeded| Alarm state if temperature threshold is
exceeded.
No— normal state, the detector does not detect temperature threshold
exceeding.
Alarm — the detector has detected temperature threshold exceeding.
If temperature threshold exceeding is detected, the text field highlights red.
Temperature Rise| Alarm by the rapid temperature rise:
No—normeal state, the detector does not detect a temperature rise.
Alarm — the detector has detected a ternperature rise.
If a temperature rise is detected, the text field highlights red.
High CO Level| CO (carbon monoxide) level in the room where FireProtect 2
is installed:
No — the CO level is normal.
Alarm — the detector has detected a dangerous CO level,
If a dangerous CO level is detected by the detector. the text field will turn
red.
Permanent Deactivation| Shows the status of the device’s permanent
deactivation functon:
No — the device operates in normal mode.
Lid only — detector’s tamper triggering natificatians are disabled.
Entirely — the detector does nat execute system cammnands, does not
participate in automation scenarios, and does not send notifications of
alanns, malfunctions, and other events to the CMS and system users. In this
case, the detector will continue to operate autonomously and indicate alanns
using the built-in siren.
Firmware| FireProtect 2 firmware version.
Device ID| ID (serial nurnber) of FireProtect 2. Also avaitable on the
detectcr’s enclosure (under the mounting panel) below the QR code and on the
packaging box,
Device No.| The number of FireProtect 2 loop (zone). Events are sent to the
CMS with this number.
Selection of installation place
The detector is designed for indoor installation only.
- The coverage area of one FireProtect 2 (Heat/Smoke/CO) is 50 to 60 m?, depending on the type of premises.
- The detector should be installed in every room. The detector is placed in the center of the ceiling at a distance of 30 cm from light fixtures, chandeliers, or any other decorative objects that may interfere with alarm detection.
- If there are beams on the ceiling protruding 30 cm or more, the detector must be installed between every two beams. If the beams protrude by less than 30 cm, installation on a beam in the central part of the ceiling is allowed.
- Inhalls or narrow corridors, detectors should be installed at a distance of no more than 7.5 m from each other.
- If the ceiling is sloping, the detector is installed at a distance of 60 cm from the top point of the ceiling. To select an installation place, draw a straight line down from the top of the ceiling. Then, draw a perpendicular from this line to the stoping part of the ceiling.
- The detector is installed at this point.
- The detector shall be installed by a competent person only.
When choosing the location of the detector, consider the parameters that affect its operation:
- Jeweller signal strength.
- Distance between the detector and the hub.
- Presence of barriers for radio signal passage between devices: walls, interfloor ceilings, large objects located in the room.
Signal strength
The Jeweller signal strength is determined by the ratio of the number of
undelivered/corrupted data packets that are exchanged between the hub and the
detector to expected ones within a certain period of time. Signal strength is
indicated by the icon on the Devices tab:
- Three bars — excellent signal strength.
- Two bars — good signal strength.
- One bar — low signal strength; stable operation is not guaranteed.
- Crossed out ican — no signal; stable operation is not quaranteed.
If the signal strength is as low as one or zero bars, we cannot guarantee
stable operation of the device. In this case, move the device.
Repositioning even by 20 cm can significantly improve the signal reception.
If, after relocation, the detector still has a tow or unstable signal
strength, use a radio signal range extender.
Do not install the detector
- Outdoors. This can lead to the detector failure.
- In places with low or unstable Jeweller signal strength. This can result the connection loss.
- Inside premises with temperature and humidity outside the permissible limits. This could damage the detector.
- In places with fast air circulation. For example, near fans, vents, open windows, or doors, This may interfere with Smoke/Heat and CO detection.
- Opposite any objects with rapidly changing temperature. For exarnple, electric and gas heaters, This can lead to false alarms.
- In the comers of the room. This may interfere with fire detection.
- In bathrooms, showers, or other areas where the temperature changes rapidly. This can lead to false alarms.
- In rooms where the generation of gases/vapors/smoke is part of the operating process. For example, in a garage, where the possibility of a detector’s alarm due to vehicle exhaust gases exists. For such premises we recommend using a detector without a smoke sensor. FireProtect 2 (Heat/CO).
- In very dusty places or areas with a lot of insects. Insects, dust, and other contaminants can settle on the smoke chamber lid and prevent fire detection.
- Near lighting fixtures, decorations, and other interior items that may interfere with the circulation of air in the room. This may interfere with fire detection,
- On surfaces that are usually warmer or colder than the rest of the room. For example, roof traps. Temperature fluctuations can interfere with fire detection.
- In high or inconvenient places. Access to the Test/Mute button is required to mute the alarm and test the detector if it’s used without connection to a hub.
Malfunctions
If FireProtect 2 malfunction is detected (for example, there is no connection
with the hub), the malfunction counter is displayed in the device feld in the
Ajax apps. All malfunctions are displayed in the detector States. Fields with
malfunctions are highlighted in red.
The device can report malfunctions to the CMS, as well as to users through
push notifications and SMS.
FireProtect 2 (Heat/Smoke/CO) malfunctions
- No connection with the hub or radio signal range extender.
- The detectors enclosure is open.
- Low battery charge level.
- The device service life has expired.
- Hardware malfunction (failure of one or more sensors of the detector).
- The user tampered with the detector during detector’s installation or operation.
Maintenance
The detector has a self-test systern and does not require the user or
installer intervention. The smoke chamber is protected from dust and insects,
so there is no need to clean it. We recommend to periodically run a self-test
to familiarize people with the alarm sound and LED indication.
The service life of the detector is 10 years. After this period, the
sensitivity of the sensors decreases. We recormmend replacing the detector
with a new one to ensure uninterrupted fire protection at the premises.
The version of the detector with replaceable batteries (has RB in the name)
operates from pre-installed batteries for up to 5 years.
When the batteries are discharged, replace thern with new ones.
Ensure the batteries are installed with the correct polarity. The polarity is
marked inside the enclosure. Please run a self-test with Ajax apps or by
pressing the Test/Mute button after the batteries are replaced to check the
correct operation of the detector.
The manufacturing date is indicated on a sticker at the bottom of the box. The
importer’s name, location, and contact details are indicated on the package.
Designed by Ajax
Address: 5 Sktyarenka Str, Kyiv, 04073
Ukraine www.ajax.systems
ajax.systems/support/devices/fireprotect-2-heat-smoke-
co/
QG.86117 Rev.1
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>