ActronAir CRV290T Variable Capacity Commercial Split Ducted Unit Instructions

June 17, 2024
ActronAir

CRV290T Variable Capacity Commercial Split Ducted Unit

“`html

Specifications:

  • Model Numbers: CRV290T, CRV330T
  • Product Type: Variable Capacity Commercial Split Ducted
    Unit

Product Usage Instructions:

01. Inspections

Before installation, ensure the unit undergoes thorough product
inspections to check for any damage.

02. General Information

Refer to the codes, regulations, and standards applicable to
your region for proper installation and operation.

03. Safety Instructions

Follow all safety instructions provided in the manual to prevent
accidents during installation and operation.

04. Installation Information

Follow the step-by-step installation guide provided in the
manual for a successful setup of the unit.

05. Wall Control Operation Manual Access

Refer to the wall control operation manual for detailed
instructions on controlling the unit.

06. Outdoor Unit Dimensions and Clearances

Ensure proper clearances around the outdoor unit as per the
dimensions provided to allow for efficient airflow.

Frequently Asked Questions (FAQ):

Q: Can I install the unit myself?

A: It is recommended to have a professional HVAC technician
install the unit to ensure proper setup and safety.

Q: What are the recommended electrical configurations?

A: Refer to section 10 for detailed electrical installation
instructions and recommended wiring configurations.

“`

Variable Capacity Commercial Split Ducted Unit
Installation and Commissioning Guide – Outdoor
Model Numbers
CRV290T CRV330T
IMPORTANT NOTE:
Please read this manual carefully before installing or operating your air conditioning unit.

Installation and Commissioning Guide Variable Capacity Commercial

Table of Contents

01. Inspections ……………………………………………………………………………………………………………………4

01.01. Product Inspections

4

01.02. Codes, Regulations and Standards

4

02. General Information ………………………………………………………………………………………………………..4

03. Safety Instructions …………………………………………………………………………………………………………. 5

04. Installation Information …………………………………………………………………………………………………..6

05. Wall Control Operation Manual Access ……………………………………………………………………………… 7

06. Outdoor Unit Dimensions and Clearances …………………………………………………………………………..9

06.01. Unit Dimensions and Weights

9

06.02. Minimum Service Access Areas and Airflow Clearances

10

07. Unit Lifting Procedure ……………………………………………………………………………………………………. 11

07.01. Crane Lifting Method

11

07.02. Fork Lift Method

12

08. Outdoor Unit Preparation ……………………………………………………………………………………………….12

09. Field Pipe Connection …………………………………………………………………………………………………… 14

10. Electrical Installation ………………………………………………………………………………………………………19

11. Split Unit Electrical Connection ………………………………………………………………………………………. 20

12. Maximum Cable Lengths ……………………………………………………………………………………………….. 22

12.01. Wall Controller Options

22

12.02. Wiring Configuration : Recommended

23

12.03. Wiring Configuration 2 : Alternate

24

13. Wiring Connections ……………………………………………………………………………………………………… 25

13.01. LC7-2 Wall Control Wiring Connections

25

13.02. NEO Wall Control Wiring Connections

25

13.03. LM-RS-2 Optional Sensor Wiring Connections

26

13.04. AERSS Optional Duct Sensor Wiring Connections

26

13.05. Demand Response Management (Outdoor Board)

27

14. Configuring and Commissioning Setup ……………………………………………………………………………. 28

14.01. Menu and Navigation

28

14.02. Configuring Compressor and Capacity(cnFg)

28

14.03. Configuring Control Source (CtrS)

28

14.04. Configuring Indoor Fan Setting (iduS)

29

15. Optional Output/Input Relay …………………………………………………………………………………………. 37

15.01. Filter Indication Relay Output (Indoor Board)

37

15.02. Fan Run Indication Output (Indoor Board)

38

15.03. Optional Outside Air Damper Control Output (Indoor Board)

38

16. Third Party Control Input (Indoor Board and/or Outdoor Board) ………………………………………….. 38

16.01. 0-10V Analogue Input for Compressor and Indoor Fan

39

16.02. 0-10V Analogue Input for Compressor with Fixed Indoor Fan Speed

40

16.03. Analogue Input for Fixed Compressor with Fixed Indoor Fan Speed

40

16.04. 0-10V Analogue Input for Indoor Fan with Fixed Speed Compressor

41

16.05. Run and Fault Indication Output (Outdoor Board)

42

16.06. Remote ON/OFF

42

2

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

17. Indoor Fan Table and Fan Curve ………………………………………………………………………………………. 43

17.01. EVA290T

43

17.06. EVA330T

45

18. Refrigerant Charging …………………………………………………………………………………………………….. 47

19. Maintenance ……………………………………………………………………………………………………………….. 50

20. Maintenance Frequency Checklist …………………………………………………………………………………… 52

21. Start Up and Commissioning Report ………………………………………………………………………………… 54

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

3

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

01. Inspections

01.01. Product Inspections
Check your air conditioning unit and all items against the invoice upon receiving your shipment. Inspect the unit, components and accessories for any sign of damage. If there is any damage to the unit, contact ActronAir Customer Care Department immediately on: 1300 522 722 to obtain a Goods Return Number.
Check the unit nameplate to verify the model, serial number, electrical rated specifications are correct.

01.02. Codes, Regulations and Standards
The installer and/or contractor assumes responsibility to ensure that unit installation complies with the relevant council, state / federal codes, regulations and building code standards. All electrical wiring must be in accordance with current electrical authority regulations and all wiring connections to be as per electrical diagram provided with the unit.

02. General Information

The ActronAir Ducted air conditioning units are designed for applications where superior performance, high efficiency, reliability, supply air quality and quiet operation are the prime priorities. The units are built with the latest technology, digital compressor, EC indoor fans, low-noise outdoor fans and an intelligent electronic control.
For optimum efficiency, your air conditioning unit will deliver just the right amount of cooling or heating capacity you demand. Even in extreme conditions, the unit will still supply the required demand at peak performance.

Energy Efficient Refrigeration Circuits
The ActronAir Ducted system is designed with a variable capacity refrigeration circuit that delivers only the amount of cooling or heating actually required to maintain your desired comfort at the most optimum efficiency.
The refrigeration circuit consists of: · High efficiency variable digital scroll compressor · Hydrophilic coated condenser coil designed for optimum performance and efficiency with corrugated fins and riffled
tubing · Hydrophilic coated evaporator coil designed for optimum performance and efficiency with lanced fins and riffled
tubing · Electronic expansion valve (EEV), to maintain efficiency at different operating conditions

Evaporator Section
The evaporator section has EC fans which deliver just the right amount of airflow, depending on requirements. The fans provide superior performance for your comfort at optimum efficiency: · Highly efficient variable speed EC motor that uses less energy than the traditional AC motor. · Easy indoor fan commissioning via intelligent controllers. · Low noise operation.

Condenser Section
Uses two (2) axial fans and a digital Compressor, with the following features: · Digital scroll compressor · Efficient axial fans with direct drive AC motor · Low noise operation

Electrical Section
The electrical section consists of: · EMC filters · Switchgears · 3 Phase motor protection · 7 Segment Display menu and fault code

4

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
· Adjustable indoor airflow pot · Optional soft start, BMS card, ActronAir Group Control
Durable Design and Construction
ActronAir is an Australian manufacturer with proven high quality air conditioning products. Known for their durability and reliable performance, these products are designed and built to withstand the extreme weather conditions.
The heavy gauge zinc and galvanised steel cabinet, with powder coated epoxy enamel finish, resists the toughest conditions. The louvered outdoor coil guard protects the condenser coil from any potential damage brought by hail, stones and other solid objects that may be projected to the unit.
Hydrophilic coated condenser coil fins provide protection to your heat exchangers and enhanced heat transfer with increased performance efficiency.
System Flexibility
ActronAir units are the first choice for office, schools and other air conditioning facilities applications, both for new construction or retrofitting projects.
Sustainability and Environmentally Friendly
The air conditioning system is supplied with zero ozone depleting R-410A refrigerant, which has no phase out or replacement concern.
With cooling and heating performance capacity that are among the best in the market, the ActronAir units are the solution for the reduction of energy consumption, CO2 emission, high fuel dependency and high network grid demand.
Refrigerant Handling and Accountability
ActronAir strongly urges that all service technicians make every effort possible to reduce the emission of refrigerants to the atmosphere. Everyone must act in a responsible manner to conserve refrigerants in accordance to the industry code of practice.
03. Safety Instructions
· Only licensed HVAC technicians should install and service this air conditioning equipment. Improper service or alteration by an unqualified technician could result in significant and major damage to the product or property which may render your warranty null and void. Such unqualified service could also lead to severe physical injury or death. Follow all safety instructions in this literature and all warning labels that are attached to the equipment.
· Prevailing WH&S regulations must be observed and will take precedence to the safety instructions contained on this manual. Safe work practices and environment must be the paramount importance in the performance of all the service procedures.
· Ensure that unit installation complies with relevant council regulations and building code standards. · All electrical wiring must be in accordance with current electrical authority regulations and all wiring connections to
be as per electrical diagram provided. · Secure the fans against accidental contact. Beware of pinch point and sharp edges which can cause cutting injury. · Always wear appropriate PPE, remove any dangling jewellery and protect long hair by wearing a cap. · Make sure that safety guards and panel covers are always firmly secured and not damaged before and during
operation of unit. · This appliance is not intended for use by young children or infirm persons unless they have been adequately
supervised by a responsible person to ensure that they can use the appliance safely. Young children should be supervised to ensure that they do not play with the appliance. · Installer must incorporate a means of electrical disconnection (isolator) in the sub-mains fixed wiring in accordance with the latest edition of the AS/NZS 3000 (also known as Australian Wiring Rules). · Secure the power cords and control cables that goes in/out the unit. Use the cable ties provided in the control box.
Qualifications required will be appropriate Electrical, Refrigeration and Refrigerant Handling License and Training dependent on local State/Territory regulations.

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

5

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

DANGER
Hazardous Voltage – Risk of Electrocution. TURN-OFF the power from main isolator before proceeding with any service work of the unit. Observe proper LOCK-OUT/ TAG-OUT (LOTO) procedures for electrical appliances in order to prevent accidental switching-on of the power supply.

WARNING
EC Motors are fitted with high power capacitors and can have dangerous residual voltages at motor terminals after power has been isolated. Wait at least 5 minutes after power isolation and test for any residual voltage before beginning service work.

CAUTION Beware of Rotating Fans! Ensure that indoor and outdoor fans are isolated and have come to a complete stand still before servicing the equipment. Beware of pinch point and sharp edges which can cause cutting injury. Secure the fans against accidental contact. Always wear appropriate PPE and remove any dangling jewellery and protect long hair by wearing a cap. Ensure that no loose clothing can be caught / entangled in moving parts.
VISUAL INSPECTION AND WORK ASSESSMENT Work areas and conditions must first be assessed and evaluated for any potential hazardous conditions. It is also important to be familiar with the unit parts and components before proceeding with any service task.

04. Installation Information
All service technicians handling refrigerant must be licensed to handle refrigerant gases.
Recover and Recycle Refrigerants Never release refrigerant to the atmosphere! It is an offence in Australia to do so. Always recover, recycle and reuse refrigerants. When removing from the system, properly contain and identify refrigerants in its dedicated container for proper disposal and/or storage. Always consider the recycle or reclaim requirements of the refrigerant before beginning the recovery procedures. Obtain a chemical analysis of the refrigerant if necessary. Refer recovered refrigerant and acceptable refrigerant quality to existing standards and regulations.
Refrigerant Handling and Safety Consult the refrigerant manufacturer’s safety data sheet (SDS) for information on proper handling and to fully understand health, safety, storage and disposal requirements. Use the approved containment vessels and refer to appropriate safety standards. Comply with all applicable transportation standards when shipping refrigerant containers.
Service Equipment and Recovery Procedures Always use refrigerant reclaiming equipment in order to minimise refrigerant emissions. Use equipment and methods which will pull the lowest possible system vacuum while recovering and condensing refrigerant. Equipment capable of pulling a vacuum of less than 500 microns is required. Do not open the system to the atmosphere for service work until refrigerant is fully removed and/or recovered. Perform refrigeration system evacuation, prior to charging, in accordance with AIRAH / IRHACE Refrigerant handling code of practice. Let the unit stand for 1 hour and with the vacuum not rising above 500 microns. A rise above 500 microns indicates a leak from the system and a leak test is required to locate and repair any leak.
CAUTION A leak test is always required on any repaired section of the refrigeration system.

6

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
Charge refrigerant into the system only after the equipment does not leak or contain moisture. Ensure that R-410A is only charged in liquid form. Take into consideration the correct amount of refrigerant charge specified for the system to ensure efficient unit operations. When charging is complete, reclaim refrigerant from charging lines into an approved refrigerant container. Seal all used refrigerant containers with approved closure devices to prevent unused refrigerant from escaping to the atmosphere. Take extra care to maintain all service equipment directly supporting refrigerant service work such as gauges, hoses, vacuum pumps and recycling equipment.
INSTALLATION PREPARATION (Pre-Installation considerations)
The following items must be considered before beginning the unit installation: · Verify the unit capacities and ratings with the unit nameplate · Make certain the floor or foundation is level, solid and have sufficient structural strength to support the unit and
accessories weight. · Allow minimum recommended clearances for periodic maintenance and service access. · Allow sufficient space above the unit for the outdoor air discharge. Condenser air inlet, located on the coil side of the
unit, requires sufficient airflow clearance for the optimum unit performance. · Note the conditioned supply air and return air location. Ensure sufficient spaces are allocated for these purposes. · Refer connection and location of condensate drain in the unit drawing and dimensions section of this manual. · Wiring connections must be in accordance with the wiring diagram provided with the unit. · Make sure all wirings are in accordance with local electricity authority regulations and standards. · Do not install the unit close to an area where there is a danger of fire due to volatile, explosive, flammable and/or
hazardous materials. · Ensure that spaces around the unit are free from any obstructions for optimum unit performance. · Installer to ensure correct size/type that main circuit breaker and cable is installed in unit sub-mains to protect the
sub-mains and unit wiring. · Installer to ensure correctly rated residual current device (RCD) is installed as per with the latest edition of the
AS/NZS 3000 (also known as Australian Wiring Rules). · Secure the power cords and control cables that goes in/out the unit. Use the cable ties provided in the control box.
CAUTION · This outdoor unit is designed to match only with an ActronAir indoor unit as specified in the Technical Selection
Catalogue. · This unit is designed for use with R-410A refrigerant only. · The unit is supplied with factory charged R-410A refrigerant. Be aware of all the relevant regulations concerning the
handling of refrigerant.
05. Wall Control Operation Manual Access
Download from website
LC7-2
Operation Instruction can be downloaded through our website shown below.
https://www.actronair.com.au/brochures-manuals/#operating-manuals
NEO
Operation Instructions can be accessed through our website shown below.
http://neo.actronair.com.au/user-guide/Components Overview

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

7

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide
OUTDOOR UNIT COMPONENTS OVERVIEW FANS

Variable Capacity Commercial

ELECTRICAL PANEL
COIL ASSEMBLY LP SENSOR EEV ASSEMBLY HP SWITCH
COMPRESSOR DISCHARGE MUFFLER

REVERSING VALVE BALL VALVE
HP SENSOR LP SWITCH
ACCUMULATOR

OUTDOOR UNIT ELECTRICAL PANEL OVERVIEW

OUTDOOR UNIT CONTROL BOARD

CONDENSER FAN
CONTACTORS

INDOOR FAN CIRCUIT BREAKERS
CONTROL CIRCUIT BREAKER

COMPRESSOR

OVERLOAD AND

CONTACTOR

3 PHASE

POWER

PROTECTION

FACTOR

RELAY

CONTACTOR

FAN SPEED CAPACITOR/S

EARTHING BOLTS WITH WASHERS
AND NUTS

POWER FACTOR CAPACITOR
EVAP MAINS OUTPUT TERMINAL
BLOCKS
CONDENSER MAINS INPUT TERMINAL BLOCKS

8

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

06. Outdoor Unit Dimensions and Clearances

06.01. Unit Dimensions and Weights

CRV290T / CRV330T

OVERALL NOMINAL DIMENSION (H x W x L) = 1415 x 1840 x 820
MOUNTING DRAIN CONNECTION = DN 25mm PN12

r———1840 0/A———

408 —–660—

87

I

I

I

I ,,.-

1 /

I I

,_/ )

I COMP

I

‘<:___ l l

‘,
–O-UT-D-OO-R-C-O-IL——————–‘

D

D

TOP VIEW

8200/A

NOTES:

THIRD ANGLE

1. Do not scale drawing. All dimensions

are in mm unless specified. Refer to

PROJECTION

corresponding unit dimensional drawing for mounting

hole details.

2. Service Access Areas and Spaces for Airflow Clearances

given above are suggested minimum based on the

condition that the spaces around the units are free from

any obstructions and a walkway passage of 1000mm

between the units or between the unit and the outside

perimeter is available.

3. Minimum service access areas and spaces for airflow

clearances are responsibilities of the installer, ActronAir

will not be held liable for any extra charges incurred due

to lack of access and space for airflow.

4. Under all circumstances, condenser air must not

recirculate back onto condenser coil. Keep all clearance

free of any obstructions.

5. STACKING OF UNITS: Ensure that minimum airflow and

clearances are met.

6. Refer to Pipe Connection Details on Specifications Sheet.

7. MTG C-C DIST = Mounting Centre to Centre Distance.

8. Use M12 bolt for feet mounting.

141 50/A
ri-
/ J,50
DRAIN POINT ON 25mm PN12

.

:1

r

1540 (MTG C-C DIST)

SIDE VIEW

. —6-0
75 7
.:J l . . I l 150

-D –

179
c)

·· –,- ELECT. ACCESS __1 2 x 0 25.4 mm (1″)

–GAS PIPE

0 28.6 mm (1-1/8″) SWAGED

_

LIQUID PIPE

0 15.88mm (5/8″)

SWAGED

I

I

. 06

0

,..

ill35 L150 (MTG c-c DIST)_J L35

FRONT VIEW

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

9

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

06.02. Minimum Service Access Areas and Airflow Clearances

NIL – TO – MINIMUM SERVICE CLEARANCE

A

B

300 mm SERVICE / AIRFLOW
CLEARANCE
C

COMP.
OUTDOOR COIL
D
750 mm SERVICE ACCESS / AIRFLOW CLEARANCE

800 mm SERVICE CLEARANCE (COMPRESSOR
AND ELECTRICALS)
HEIGHT CLEARANCE FOR ALL UNITS = 1500mm

UNIT MODEL NUMBER
CRV290T CRV330T

UNIT WEIGHT
(KG)
263
292

CORNER WEIGHTS (KG)

A

B

C

D

48

79

61

75

52

87

66

87

10

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
07. Unit Lifting Procedure
WARNING WH&S regulations must be observed and will take precedence during lifting process.

07.01. Crane Lifting Method

Crane lifting method is recommended for high rise lifting

Provide rubber pads to prevent damage to the unit

Connect the loop ends of slings onto shackle

SPREADER BARS

OUTDOOR UNIT

Slip nylon slings through the pallet

DETAIL A

PALLET

FIG. 1

A

Equipment Required For Crane Lifting: 1. 1 x shackle 2. 2 x nylon slings 3. Spreader bars
NOTE Refer to Unit Dimension and Weight section for unit weight before selecting shackles and slings.

Procedure:
1. Slip nylon slings through the pallet as shown in Fig. 1. 2. Use a Bow or Dee shackle to connect the slings. 3. Ensure slings are protected by rubber pads or similar if slings are draped across unit edges, corners, or air grilles.
This will prevent the unit from being damaged during lifting. 4. SPREADER BAR must be used when lifting the unit. Ensure that the spreader bar is slightly larger than the base. 5. Test lift the unit to determine exact unit balance and stability before hoisting it to the installation location.

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

11

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
07.02. Fork Lift Method
DANGER Make sure rigging equipment, accessories and plant are sufficiently and safely capable to lift the unit in order to prevent potential damage to property, severe personal injury or death. Please check unit weight and weight distribution points on unit drawing dimensions section.
PROCEDURE: 1. To move the unit around with a forklift, insert the fork tines through the pallet, as shown in Fig. 2. 2. Only fork the unit through compressor end or side of the unit. (See illustration for location of compressor end).

CAUTION
DO NOT LIFT UNIT from this end.

COMPRESSOR END

FIG. 2

INSERT FORKLIFT TINES HERE

CAUTION Length of fork lift tines must pass the unit middle section, in order to safely carry the unit.

08. Outdoor Unit Preparation
NOTE It is important to remove the shipping blocks before unit operation.

Step 1. Remove Access Panel, as shown below:
OUTDOOR UNIT

ACCESS PANEL

Use allen keys Hex Recess(8mm) to remove the Access Panel

12

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide
Remove access panel as illustrated below.

Variable Capacity Commercial

Do not disconnect Earth Cable.

Earth Cable

B Removal Order: A Pull-Out 20mm B Pull-Down to remove Access Panel-Electrical
A

Remove Access Panel

WARNING
· There is an earth cable attached to the access panel. This must be disconnected first to fully remove the access panel. · You must re-connect the earth cable when re-assembling the access panel. · Live electrical within enclosure. Isolate electrical supply before removing panels. Authorised technicians access only. · Follow the procedure below when removing the shipping blocks.

Step 2. Remove the Shipping Blocks before installing Interconnection Field Pipes.

Loosen the set bolts that hold the compressors down onto the unit (4 pcs)

Remove Shipping blocks as shown below.

Loosen Bolts (4-pcs / Comp.)

GENTLY Push back the Compressor

Shipping Blocks

Pull away the Shipping Blocks

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

13

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

Tighten back the set bolts that hold the compressors down onto the unit (4 pcs)
Tighten Bolts (4-pcs / Comp.)

Braze refrigeration piping. Refer to piping sections for details of field pipe sizes and piping installation procedure.

09. Field Pipe Connection

CAUTION
The units described in this guide uses R-410A refrigerant This operates at a pressure approximately 1.6 times higher than a similar systems using R-22. When installing equipment using R-410A refrigerant, there are number of standards that must be met: · The system of this unit operates with Polyolester (POE) oil that rapidly absorbs moisture. · The maximum time any system can be opened to atmosphere is 15 minutes. · It is important to work with absolute cleanliness. · Brazing must be done with the use of Nitrogen to avoid carbon deposits into the pipes. · The system must be evacuated thoroughly to 500 microns (see evacuation procedure). · The system must always be charged with R-410A refrigerant in liquid state. · Never allow R-410A refrigerant to vent into the atmosphere. It is an offence to release refrigerant in Australia. · Always reclaim refrigerant using equipment and container dedicated for R-410A system use only. · Only qualified persons are allowed to perform any work described in this guide. · All work must be carried out in accordance with Australia and New Zealand refrigerant handling code of practice.

Maximum allowable total equivalent field pipe length is 60 metres, see diagram below. This includes all the equivalent pipe fitting loses and vertical height difference. Vertical height difference must not exceed 20 metres. Table 1 below shows the equivalent straight pipe length of elbow fittings.

EQUIVALENT STRAIGHT PIPE LENGTH OF ELBOW FITTINGS (METRES)

PIPE SIZE NOMINAL DIAMETER

90o LONG RADIUS

90o SHORT

45o LONG RADIUS

45o SHORT

ELBOW

RADIUS ELBOW

ELBOW

RADIUS ELBOW

9.52 (3/8″)

0.24

0.36

0.09

0.14

15.88(5/8″)

0.30

0.45

0.15

0.23

19.05 (3/4″)

0.40

0.60

0.18

0.27

22.22 (7/8″)

0.46

0.69

0.21

0.32

25.4 (1″)

0.52

0.78

0.24

0.36

28.56 (1-1/8″)

0.55

0.83

0.27

0.41

14

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
Selected field pipe sizes must match the recommended sizes in table above. If the installation requires different field pipe diameter due to different application condition other than recommended, contact ActronAir for advice. Most of unit pipe connections are factory swaged to easily fit to the recommended field pipe diameter. When it is required to install other refrigeration devices, such as refrigerant drier, solenoid valve and the like, include the equivalent straight pipe length of the device in the calculation of total equivalent field pipe length. Both pipes are required to be insulated.
INDOOR UNIT

OUTDOOR UNIT

FIELD PIPE (Installer to Supply)
A

B
A = EQUIVALENT PIPE LENGTH, 60 metres (max)
B = VERTICAL HEIGHT, 20 metres (max)

Example of Total Equivalent Field Pipe Length Calculations

INDOOR UNIT
H 2
OUTDOOR UNIT

H 3
E4 V2
E 3

E 2
V1
E1 H
1

Equivalent Pipe Length = Total Horizontal Length + Total Vertical Length

+ Total Losses from Elbows

where:

H = Horizontal Length

V = Vertical Length

E = Elbow Losses (Suction)

Equivalent Pipe Length = (H + H + H ) + (V + V ) + (E + E + E + E )

123

12

1234

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

15

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

CAUTION
Above illustration shown as calculation examples only. It is the responsibility of the Installer to design an efficient refrigeration piping lay out for optimum unit performance.

TABLE 2: REFRIGERATION PIPING Outdoor Model Indoor Model
Equivalent Pipe Length Range Maximum Vertical Height Differential * Field Pipe Size Liquid Line Gas Line Outdoor Pipe Size Liquid Line Gas Line Indoor Pipe Size Liquid Line Gas Line

  • Included in maximum field pipe

metres metres
mm (inch) mm (inch)
mm (inch) mm (inch)
mm (inch) mm (inch)

CRV290T/330T EVA290T/330T
0 – 60 20
15.88 (5/8) 28.58 (1-1/8)
15.88 (5/8) swaged 28.58 (1-1/8) swaged
15.88 (5/8) swaged 28.58 (1-1/8) swaged

CAUTION
Brazing joints should only be performed whilst purging Nitrogen through the system. Failure to do so will cause carbon deposits to be left on the internal pipe surface, that in turn can cause system failure and void of warranty.

16

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

NITRO REGULATOR SET TO 2 L/S

N

I

T

R

O

G

E

N

LIQUID

A

PIPE

BRAZE JOINTS GAS PIPE

OPEN PIPE

Rubber bung into pipe opening
to create seal

DETAIL A

Installing interconnecting pipe work to indoor, nitrogen bleed procedure (First fit or rough in stage only)
1. Run interconnecting pipe work from condenser location to evaporator. 2. Release pressure in evaporator and remove caps. 3. Fit copper tube into tail, set nitro bottle and regulator up at condenser end of pipe work. 4. Fit nitrogen line into liquid line with rubber bung to seal the connection. The seal will prevent air being sucked into
pipe work. 5. Leave suction line open, set nitro regulator for nitrogen to flow through pipe work at 2 l/s flow rate @20kPa. 6. Braze required joints as quick as possible. See Diagram Above.
Installing interconnecting pipe work to outdoor, nitrogen bleed procedure (First fit or rough in stage only)
1. Starting with circuit 1 system, remove piping caps from the condenser and fit pipe work into tails. 2. Fit nitro hose onto suction ball valve and fit open hose onto liquid line post valve. 3. Set nitrogen regulator to 2 l/s flow rate through pipe work and evaporator. 4. Braze remaining joints as quick as possible. 5. Allow the brazed joints to cool and conduct leak test in the connections.

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

17

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
Pressurize the system to 2500kPa in stages. A recommended pressure test is to be performed for no less than 1 hour at 2500kPa.
NOTES · Any non-condensable product left in the system can cause the pressure in the high side of the system to increase and in
turn, the compression temperature to rise. · Moisture will result in adverse reaction in the refrigerant circuit. · The POE oil used in the R-410A compressor is hygroscopic, which means that it absorbs moisture from the air. To
prevent chemical reactions in the system, any moisture must be removed at all costs. · Oxygen (air) reacts with the compressor oil and can lead to faults such as compressor failure.
See Diagram Below:

To

N

Indoor Unit

I

BRAZE

T R

JOINTS

O

A

G

E

NITROGEN HOSE

N

DETAIL A

NITROGEN HOSE

Evacuation Procedure (Triple Evacuation)
1. Fit service gauges to the ball valves (liquid line service valve and suction line service valve). 2. Evacuate the system to 1000 microns. 3. Check vacuum with vacu stat. Break the vacuum with dry Nitrogen to 100kPa 4. Release Nitrogen pressure. Evacuate to 500 microns. 5. Check vacuum with vacu stat. Break the vacuum with dry Nitrogen to 100kPa 6. Release Nitrogen pressure. Evacuate to 500 microns. 7. Check vacuum with vacu stat. Let the unit stand for 1 hour and with the vacuum not rising above 500 microns. 8. Open valve

CLOSE ( As Shipped Position )

TO OPEN TURN ANTI-CLOCK WISE (1/4 TURN)

OPEN ( Operating Position )

TO CLOSE TURN CLOCK WISE (1/4 TURN)

18

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
10. Electrical Installation
All electrical work must be carried out by a qualified and licensed technician. Make sure all wiring is in accordance with local wiring rules. Wiring connections should be made in accordance with the wiring diagram provided.
DANGER Live Electrical Supply ! During installation of your air conditioning unit, it may be necessary to work in close proximity to live electricity. Only licensed electricians are allowed to perform these tasks. Follow all electrical safety precautions when exposed to live electrical components.
CAUTION Static Sensitive Electronic Devices ! · DO NOT handle electronic devices unless you are wearing an Anti-Static Wrist Strap that is connected to a GOOD
EARTH. Failure to protect the electronic devices from static electricity may cause unrepairable damage. · Static damaged electronic devices are NOT COVERED for replacement under warranty.
Wiring Diagram The wiring diagram specific for your air conditioning system is located on the inside panel of the control access door. Always refer all wiring installation, servicing and troubleshooting of this equipment to this diagram to ensure correct electrical connection are satisfied.
Supply and Power Requirements Procedure It is the installer’s responsibility to provide power supply wiring to the mains supply terminal strip of the outdoor unit. Make sure all wiring are in accordance with local wiring rules. Wiring should conform to all current electrical authority regulations and all wiring connections to be as per electrical diagram provided with the unit. · Confirm that the power supply available is compatible with the unit nameplate ratings. The supply power must be
within +10% to -6% of the rated voltage as per AS60038. · Protect electrical service from over current and short circuit conditions in accordance with the latest edition of the
AS/NZS 3000 “Australian / New Zealand Wiring Rules”. Size protection devices according to the electrical data of the unit and the table below. · Installer to connect an appropriate load break (AC3) isolator in sub-mains wiring. · Secure any power and control cables that enters in/exits out of the unit. Use the cable ties provided in the main electrical panel. Provide proper unit earth in accordance with local and national codes.
Main Voltage Balance Requirement Check the voltage at the mains supply terminals to determine if it is balanced. Voltage imbalance on three phase systems can cause motor overheating and premature failure. The maximum allowable imbalance is + 2.0%, should voltage imbalance exceed this value, check unit wiring connections to locate and rectify faults or contact local supply authority.

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

19

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
11. Split Unit Electrical Connection
DETAILED WIRING DIAGRAM IS PROVIDED WITH THE UNIT
Outdoor Unit: Located at the back of electrical/compressor access panel. Indoor Unit: Located at the back of electrical box cover.
1 MAINS WIRING (400VAC) (Three Phase +Neutral+Earth) 50Hz
2 INTER-CONNECTING POWER CABLE (400 VAC) (Three Phase + Neutral+Earth) 50Hz
3 DATA CABLE TO WALL CONTROL (Cat5E UTP (AWG 24) Data Cable)
4 EXTRA LOW VOLTAGE DATA CONTROL WIRING (2 Core (1 Pair) Twisted Pair, 7/0.30 (0.5mm2) Shielded Data Cable)

MAIN SWITCHBOARD
SUB MAINS CIRCUIT BREAKER (CB/RCBO/RCD) 1 SUB MAIN SUPPLY FROM DISTRIBUTION BOARD
SUB MAINS LOAD BREAK ISOLATOR
SUB-MAINS TO UNIT

INDOOR UNIT

3 DATA CABLE
WALL CONTROL

2 INTER-CONNECTING POWER CABLE
OUTDOOR – INDOOR

4 EXTRA LOW VOLTAGE DATA CONTROL WIRING (INDOOR TO OUTDOOR)

OUTDOOR UNIT

NOTES
· To minimise noise interference, Data and Power cable clearance should be maintained as much as possible (minimum 300mm).
· Above Images used for illustration purposes only.

20

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
2 Core Twisted Data Cable Shielding Instructions (ActronAir Part Number: AEDC2)
NOTES · Maintain the twist of the core wires up to the Green Terminal Plug. · Maximum strip length of outer insulation to the Green Terminal Plug is 50mm. · Make sure the cable colours used for the Data Terminal in Outdoor Unit match the Data Terminal in Indoor unit. Outdoor Unit Data Terminal (Green Plug) “Terminal A” – White Wire “Terminal B” – Black Wire “Terminal G” – Shield Wire Indoor Unit Data Terminal (Green Plug) “Terminal A (+)” – White Wire “Terminal B (-)” – Black Wire “Terminal G” – Shield Wire
Insert data cable through the lower snap bushing and first cable tie on the right hand side of the electrical panel. Connect core wires and shield wire into the Outdoor Board green terminal plug marked ” INDOOR A, B and G”. (Refer to unit wiring diagram for complete wiring connection details).

OUTDOOR BOARD TERMINAL PLUG

OUTDOOR BOARD

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

21

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

Circuit Breaker Size Recommendation

Model

Circuit Breaker Size Amps

CRV290T / CRV330T

32.0

  • Refer to latest edition of AS/ANZ 3000 or AS/ANZ 3008 Australian/New Zealand Wiring Rules to determine required cable size.

12. Maximum Cable Lengths

12.01. Wall Controller Options
Maximum of three (3) wall controllers in below combinations is allowed on unit. See below table.

Combinations
1st Option 2nd Option 3rd Option 4th Option 5th Option 6th Option 7th Option 8th Option

WC 1 NEO NEO NEO NEO NEO LC7-2 LC7-2 LC7-2

Wall Controllers WC 2
NEO NEO LC7-2 LC7-2
LC7-2 LC7-2

WC 3 LC7-2 LC7-2 LC7-2

NOTES
· NEO – Available in White (NTW-1000) and Black (NTB-1000) colours. · LC7-2 – Available in White and Grey colours. · In the instance of a combination of NEO and LC7-2 being connected together, the NEO will always need to be addressed
as C1.

22

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
12.02. Wiring Configuration : Recommended

NOTES

· Diagram shown below is a general representation only. Refer to individual unit wiring diagram for complete wiring connection details.
· Long runs beside Mains cables or TV antenna cables should be avoided. · Wiring configuration for LR7-1 and LC7-2 wall controller is the same. · Daisy connection is not allowed for the NEO wall controller. · Two Ferrite Clips*, if supplied, are to be placed 200mm and 400mm from the NEO controller.

NEO WALL CONTROLLER 1
(OPTIONAL)

NEO WALL CONTROLLER 2
(OPTIONAL)

LC7-2 WALL CONTROLLER 3
(OPTIONAL)

INDOOR UNIT

2a

2b

2c

  • 2 Ferrite Clips

  • 2 Ferrite Clips

5

NOTES

NEO SENSE (OPTIONAL)

· Max. of 16 NEO Sense per System. · NEO Sense is battery powered.

· NEO Sense is available in White (NSW-10)

4

and Black (NSB-10).

LM-RS-2 (OPTIONAL)

1
DATA CONTROL CABLE

3
AERSS (OPTIONAL)

Item 1 to 4 4 to 2a, 4 to 2b, 4 to 2C 4 to 3
Description LC7-2 and NEO Field Control Wiring
Indoor to Remote Sensor Indoor to Outdoor Data Cable

Description Outdoor PCB to Indoor PCB Indoor PCB to Wall Controller Indoor PCB to Wall Controller Indoor PCB to Remote Sensor

Maximum Cable Length 100 m 90 m 100 m 100 m

Cable Type Cat5E UTP (AWG 24) Data Cable Cat5E UTP (AWG 24) Data Cable 2 Core (1 Pair) Twisted Pair, 7/0.30 (0.5mm2) Shielded Data Cable

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

23

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

12.03. Wiring Configuration 2 : Alternate
LC7-2 WALL CONTROL 1
(OPTIONAL)

LC7-2 WALL CONTROL 2
(OPTIONAL)

LC7-2 WALL CONTROL 3
(OPTIONAL)

INDOOR UNIT

2a

2b

2c

4
LM-RS-2 (OPTIONAL)

1
DATA CONTROL CABLE

3
AERSS (OPTIONAL)

NOTES
· Diagram shown above is a general representation only. Refer to individual unit wiring diagram for complete wiring connection details.
· Long runs beside Mains cables or TV antenna cables should be avoided where possible.

Item

Description

1 to 4

Outdoor PCB to Indoor PCB

4 to 2a

Indoor PCB to Wall Control 1

4 to 2c

Indoor PCB to Wall Control 3 (last controller)

4 to 3

Indoor PCB to Remote Sensor

  • Maximum Daisy Chain connection is up to 2 wall Controls.

Maximum Cable Length 100 m 100 m
75m total (Daisy Chain)* 100 m

Description LC7-2 Field Control Wiring Indoor to Remote Sensor Indoor to Outdoor Data Cable

Cable Type Cat5E UTP (AWG 24) Data Cable Cat5E UTP (AWG 24) Data Cable 2 Core (1 Pair) Twisted Pair, 7/0.30 (0.5mm2) Shielded Data Cable

24

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

13. Wiring Connections
13.01. LC7-2 Wall Control Wiring Connections

WALL CONTROL WIRING

POWER: – BROWN / ORANGE

485 A: – BLUE

485 B: – BLUE-WHITE

GND:

– BROWN-WHITE / ORANGE-WHITE

NOT USED: – GREEN / GREEN-WHITE

INDOOR CONTROL
BOARD
WALL CONTROLLER +12V A B G

BR / OR BL
BL-WH BR-WH / OR-WH

WALL CONTROL

WC-1 Power
485 A 485 B GND

BR / OR BL
BL-WH BR-WH / OR-WH

CUT OFF GR / GR-WH

13.02. NEO Wall Control Wiring Connections
NOTE Two FERRITE CLIPS, if supplied, should be installed 200 mm away and FERRITE 2 should be 400 mm away from the Wall Control.

13.02.01. NEO RJ45 Wiring

WALL CONTROL

RJ45

TWC-1

+12V A B G

WALL CONTROL

RJ45

TWC-2

+12V A B G

FERRITE 1 200 mm away
from the Wall Control
FERRITE 2 400 mm away
from the Wall Control FERRITE 1 200 mm away from the Wall Control
FERRITE 2 400 mm away
from the Wall Control

INDOOR CONTROL
BOARD
WALL CONTROLLER

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

25

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

13.02.02.

NEO Hard Wiring

WALL CONTROL
RJ45
+12V A B G

WALL CONTROL WIRING

POWER: – BROWN / ORANGE 485 A: – BLUE

485 B: – BLUE-WHITE

GND:

– BROWN-WHITE / ORANGE-WHITE

NOT USED: – GREEN / GREEN-WHITE

FERRITE 1 should be 200 mm away and FERRITE 2 should be 400 mm
away from the Wall Control

CUT OFF GR / GR-WH

WALL CONTROLLER +12V A B G

INDOOR CONTROL
BOARD

13.03. LM-RS-2 Optional Sensor Wiring Connections

REMOTE SENSOR WIRING
PAIR 1: – BLUE / BLUE-WHITE PAIR 2: – ORANGE / ORANGE-WHITE PAIR 3: – GREEN / GREEN-WHITE PAIR 4: – BROWN / BROWN-WHITE
NOTE: · PAIR 1 AND 2 USED FOR ILLUSTRATION PURPOSES
ONLY. · CUT OFF AND TERMINATE ANY UNUSED PAIRS TO
ENSURE NO WIRING IS LEFT EXPOSED.

INDOOR CONTROL
BOARD
TEMP SENSORS S1 S2 S3 COM

PAIR 1 PAIR 1 PAIR 1 PAIR 2 PAIR 2 PAIR 1 PAIR 2 PAIR 1 PAIR 2 PAIR 1

OPTIONAL SENSOR 3
LM-RS

OPTIONAL SENSOR 2
LM-RS

OPTIONAL SENSOR 1
LM-RS

13.04. AERSS Optional Duct Sensor Wiring Connections

REMOTE SENSOR WIRING
PAIR 1: – BLUE / BLUE-WHITE PAIR 2: – ORANGE / ORANGE-WHITE PAIR 3: – GREEN / GREEN-WHITE PAIR 4: – BROWN / BROWN-WHITE
NOTE: · PAIR 1 AND 2 USED FOR ILLUSTRATION PURPOSES
ONLY. · CUT OFF AND TERMINATE ANY UNUSED PAIRS TO
ENSURE NO WIRING IS LEFT EXPOSED.

PAIR 1 PAIR 1 PAIR 1 PAIR 2 PAIR 2 PAIR 1 PAIR 2 PAIR 1 PAIR 2 PAIR 1

INDOOR CONTROL
BOARD
TEMP SENSORS S1 S2 S3 COM

OPTIONAL SENSOR 3

OPTIONAL SENSOR 2

OPTIONAL SENSOR 1

AERSS

AERSS

AERSS

WIRE JOINER

WIRE JOINER

26

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
13.05. Demand Response Management (Outdoor Board)
NOTE Third Party Control Option is not available if Demand Response Management (DRM) is used.
CONDENSER CPU
BOARD
COM / +12V DRM 3 / COMP2 DRM 2 / FAN DRM 1 / HEAT

DR M Control Inputs DEMAND RESPONSE MANAGEMENT

1. Route DRM input cables into the Unit (as per previous wiring installation procedure) . 2. Connect cables into terminals (as shown above and as per wiring diagram provided with the unit).

DRED VOLTAGE FREE CONTACTS

ODU CPU BOARD

COM / +12V DRM 3 / COMP DRM 2 / FAN DRM 1 / HEAT

DEMAND RESPONSE ENABLING DEVICE (DRED) AS4755 COMPLIANT DEVICE
(OPTIONAL)

DEMAND RESPONSE MANAGEMENT

DEMAND RESPONSE ENABLING DEVICE CIRCUIT DIAGRAM

DEMAND MANAGEMENT MODE
DRM1
DRM2 DRM3

DESCRIPTION OF MODE ALLOWABLE RANGE (%)
Compressor Off Mode
Maximum 50% power use mode with 0 to < 50% allowable power use range
Maximum 75% power use mode with 0 to < 75% allowable power use range

OPERATING MODE
Compressor ONLY will cycle OFF and remain off for the entire Demand Response event. All other functions will operate as normal (i.e. Indoor Fan)
Compressor 0 to < 50% operation range for the total Demand Response event.
Compressor 0 to < 75% operation range for the total Demand Response event.

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

27

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

14. Configuring and Commissioning Setup

14.01. Menu and Navigation

diS (Display)

Display system’s status and settings

SEr (Service)

Service use only

02.00 = Family cnFg
02.33 = Capacity

Ct. 0 = 3rd Party

Ct. 1 = Wall Control (default)

CtrS Ct. 2 = Basic BMS

Ct. 3 = Wall Control + Basic BMS

Ct. 4 = Advanced BMS

FP1 = IDU Fan Low PWM setting

FP2 = IDU Fan Med PWM setting

FP3 = IDU Fan High PWM setting

Fr1 = IDU Fan Low RPM setting

SEt (Settings) iduS

Fr2 = IDU Fan Med RPM setting Fr3 = IDU Fan High RPM setting FPd = IDU Fan Defrost PWM setting

FPc = IDU Reduced Airflow PWM setting

FiL = IDU Fan Filter Hours setting

Econ = IDU Econ 0-10V Output setting

FnSE = Indoor Fan Setting

HtSt = HotStart On/Off

no = Soft Start not enabled (default) SoFt
YES = Soft Start enabled

no = Indoor Fan and Compressor (default) run
YES = Compressor only

Hi = High Start-up Speed (default) odFs
Lo = Low Start-up Speed

DISPLAY

MENU
ENTER OUTDOOR BOARD
BACK
MENU Scroll through the items at the same menu level. Increment the value being set. ENTER Go into the selected menu. Lock in selected value. BACK Go back to the parent menu. Press and hold to go back to main menu

  • Family and Capacity are the representative values only and may vary depend on the model purchased as seen below table. Do not change setting.
    Family and Capacity Table

CRV290T CRV330T

Model Family
02

Capacity (kW)

29

33

14.02. Configuring Compressor and Capacity(cnFg)
Configure the compressor type and capacity. The unit is factory configured. Do not change this setting.
14.03. Configuring Control Source (CtrS)
This commissioning is applicable for BMS and other Wall Control. Configurable settings are as follows:
Third Party Control The unit can be controlled by a non-ActronAir wall control. To do this, CtrS on the Outdoor Board has to be set to Ct. 0. For connection details, see the wiring diagram supplied with the outdoor unit.

28

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
Wall Control ActronAir offers NEO and LC7-2, wall controls that can control the available features and maximise the function and operation of the air conditioner. To do this, CtrS on the Outdoor Board must be set to Ct. 1.
Basic BMS The unit can be connected to a network through a BMS card (ICUNO- MOD). This allows the unit to be operated in the same way the as the NEO and LC7-2 does. To do this, CtrS on the Outdoor Board must be set to Ct. 2.
Wall Control + Basic BMS The unit can be connected to a network (Basic BMS) and at the same time be controlled using the NEO or LC7-2 controller. Priority will be given to the most recent command. To do this, CtrS on the Outdoor Board must be set to Ct. 3.
Advanced BMS The unit can be connected for system that requires customised functions not included in the existing software or logic in the Outdoor Board but still retaining the safety logic. To do this, CtrS on the Outdoor Board must be set to Ct. 4.
14.04. Configuring Indoor Fan Setting (iduS)
The fan settings may be configured using three options: the Condenser CPU Board,NEO, LC7-2 Wall Control and Third Party Control.
14.04.01. Indoor Fan Speed Commissioning
The Variable Capacity Commercial indoor fan operation is supplied as a single speed system, with speed settings model dependent. This speed is adjustable via outdoor board and the NEO or LC7-2 wall control (when connected). Refer to the fan curve and the fan table section of each models fan speed setting. When the NEO or LC7-2 wall control is connected, the option of a 3-speed indoor fan is available to be programmed. The default speed settings for each of the three speeds (High, Medium and Low) are also shown in the table below. See Option 2: via Outdoor Board. For more details see Option 1: via Wall Control (NEO or LC7-2).
NOTE ActronAir do not recommend adjusting the RPM limit. Before making any changes, please contact ActronAir Technical Support on 1800 119 229.

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

29

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

Option 1: via LC7-2 Wall Control
Summary : Enter Service Menu Select Menu 03

Select 1-Speed or 3-Speed Indoor Fan

If required, adjust the PWM of 1-Speed Setting

If required, adjust the MED PWM of 3-Speed Setting
If required, adjust the MED RPM of 3-Speed Setting

If required, adjust the LOW RPM of 3-Speed Setting
If required, adjust the HIGH PWM of 3-Speed Setting

If required, adjust the LOW PWM of 3-Speed Setting
If required, adjust the HIGH RPM of 3-Speed Setting

If required, adjust the REDUCED AIRFLOW Setting

If required, adjust the DEFROST FAN Setting

Enable / Disable CONTINUOUS Fan Setting

If required, adjust the HOT START FAN Setting

EXIT Service Menu

Procedure: 1. Press and hold the REPEAT and the TIMER buttons for 3 seconds then release to enter Service Menu.

2. Press the button to scroll through to Service Menu 03.

3. Press the PROG button to enter Service Menu 03. Display will show the indoor fan speed selection.
NOTES 1 Speed indicated with number 1 and MED being illuminated. 3 Speed indicated with number 3 and LOW, MED and HIGH being illuminated.

1- Speed Indoor Fan DEFAULT

3- Speed Indoor Fan

30

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

4. Press the

or buttons to select 1 or 3-Speed indoor fan setting. Then press the PROG button to

accept the selection.

5. Display will show the current PWM (speed) setting. Also displayed are MED, FAN and the 1 to signify that you

are about to change the fan speed of 1-speed fan setting. Press the

or buttons to adjust the single

speed indoor fan PWM. Then press the PROG button to accept.

NOTES
It is not possible to skip this step even if 3-speed fan setting was selected. Either adjust the PWM or accept the default setting.

6. Display shows LOW, MED, HIGH, 3 and FAN. With LOW blinking to signify current LOW PWM settings for

3-speed fan. Press the

or buttons to adjust the PWM setting. Then press the PROG button to

accept.

NOTE

Default setting and adjustable range may vary depending on indoor models.

7. Next display will show the RPM setting for LOW SPEED. Press the setting. Then press the PROG button to accept.

or buttons to adjust the RPM

NOTES
· The RPM numbers displayed should be multiplied by 10 to get the actual RPM setting. Example here is 110 x 10 = 1100 RPM.
· ActronAir do not recommend adjusting the RPM limit. · Before making any changes, please contact ActronAir Technical Support on 1800 119 229.

8. Repeat Steps 6-7 to set MED and then HIGH PWM and RPM limit settings. 9. Press EXIT button twice to leave the service menu.

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

31

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

Option 2: via Outdoor Board The outdoor PCB has a 7 segment display, with 3 adjacent buttons, used for commissioning the indoor fan.

MENU SEt iduS
FP1 FP2 FP3 Fr1 Fr2 Fr3

PWM / RPM

EVA290T

EVA330T

38

47

52

67

70

92

1200

1400

1500

1750

1800

2100

SPEED SETTING

3 – SPEED

1 – SPEED

Low PWM

Med PWM

Med PWM

High PWM

Low RPM

Med RPM

Med RPM

High RPM

Procedure:
1. Using the MENU and the ENTER buttons, navigate to SEt (Settings) iduS (Indoor Settings). 2. If required, adjust and set FP1 (Low PWM), FP2 (Medium PWM) and FP3 (High PWM). 3. If required, adjust and set Fr1 (Low RPM Limit), Fr2 (Medium RPM Limit) and Fr3 (High RPM Limit).

NOTE
FP1 (Low PWM), FP2 (Medium PWM), FP3 (High PWM) are adjustable settings within PWM high and low range limits. Refer to Section 15 for more details.

Option 3: Third Party Control
(0-10V Fan)
1. On the Outdoor Board, set Control Source to Third Party. Using the MENU and the ENTER buttons, navigate to SEt (Settings) CtrS (Control Source).
2. Use the MENU button to navigate to 0 to select Third Party Control as the control source. Press the ENTER button to save the setting.
3. On the Indoor Board, set the first dip switch to ON and also ensure dip switch 2 in ON.

4. Indoor Fan operation is now operational via 0-10V Third Party Control. For airflow and static pressure, see the fan curve and the fan table section for reference. Adjustable airflow range will vary from model to model.
(Fixed Speed) 1. On the Outdoor Board, set Control Source to Third Party. Using the MENU and the ENTER buttons, navigate to
SEt (Settings) CtrS (Control Source). 2. Use the MENU button to navigate to 0 to select Third Party Control as the control source. Press the ENTER
button to save the setting.
NOTES Adjustable airflow range will vary from model to model. Medium Speed is the speed setting for 1-speed Fan.

32

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
3. If medium speed setting (1-speed fan setting) is required to be changed, using the MENU and the ENTER buttons, navigate to SEt (Settings) iduS (Indoor Settings) FP2 and Fr2.
4. On the Indoor Board, ensure that all dip switches are set as per below image.

5. Indoor Fan operation is now operational via Third Party Control (1-speed).

14.04.02. Defrost Fan Setting
This feature allows the installer to set the indoor fan speed (PWM) during defrost mode. By default, this is set to 0 PWM (Fan Off) to avoid cold air draft. However, in some applications, continuous air circulation maybe required even when the system went to defrost cycle.
The Defrost Indoor fan speed (PWM) is can be set through the LC7-2 wall control or Outdoor PCB. Procedures are shown below:

Option 1: LC7-2 Wall Control

1. Press and hold the REPEAT and the TIMER buttons for 3 seconds then release to enter Service Menu. The display will show the Service Menu 01.

2. Press the 03.

or buttons to scroll to Service Menu 03. Press the PROG button to enter the Service Menu

3. Press the PROG button 9 x times to enter the Defrost Fan Settings.

4. Press the

or buttons to select the desired indoor fan PWM then press the PROG button to accept.

The available range is from 10 to 100. OFF means that the indoor fan is OFF during the defrost cycle. The sample

screen below shows the indoor fan to 20.

5. Press the EXIT button twice to go back to the original status display.

Option 2: Outdoor Unit CPU Board 1. Using the MENU and the ENTER buttons, navigate to SEt (Settings) iduS (Indoor Settings) FPd (Defrost
PWM) 2. Keep pressing the MENU button to select the desired indoor fan speed PWM is shown. By default, the indoor fan
PWM is set to 0 and it is adjustable from 0 to 100.
Note: 0 means the indoor fan is off during the defrost cycle.
3. Press the ENTER button to confirm the PWM settings. 4. Press the BACK button three times to go back to the original status display.

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

33

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

14.04.03. Reduced Airflow
This feature allows the system to run at lower airflow down to 20% (below system normal application range) when the compressor is not active (cycle off). This feature is useful to reduce the indoor fan power consumption during system operation but maintain the essential air circulation in the room. Note that if Continuous Fan is enabled, it takes precedent over the Reduced Airflow.
The available airflow range of reduced airflow is presented on the fan table Reduced Airflow (Compressor Off) on the next pages. By default, this option is enabled and set to 20 PWM. To turn OFF or change the PWM value:

Option 1: LC7-2 Wall Control

1. Press and hold the REPEAT and the TIMER buttons for 3 sec then release to enter Service Menu. The display will show the Service Menu 01.

2. Press the 03.

or buttons to scroll to Service Menu 03. Press the PROG button to enter the Service Menu

3. Press the PROG button 10x times to enter the Reduced Airflow Settings.

4. Press the

or buttons to select the desired indoor fan PWM then press the PROG button to accept.

The available range is from 20 to 100. OFF means that this function is disabled. The sample screen below shows

the indoor fan is set to 30 PWM.

5. Press the EXIT button once to go back to the original status display.
Option 2: Outdoor Unit CPU Board 1. Using the MENU and the ENTER buttons, navigate to SEt (Settings) iduS (Indoor Settings) FPc (Reduced
PWM) 2. Keep pressing the MENU button to select the desired indoor fan speed PWM is shown. By default, the indoor fan
PWM is set to 20 and it is adjustable from 20-100. Note: 0 means the Reduce Airflow Mode is disabled. 3. Press the ENTER button to confirm the PWM settings. 4. Press the BACK button three times to go back to the original status display.

14.04.04. Hot Start (Draft Reduction)
Hot Start is a feature only applicable in the heating cycle, that delays the indoor fans start-up. This allows the indoor coil to heat up before the indoor fan starts so an initial cold draft is prevented. When Hot Start is disabled the compressor and fan will start at approximately the same time.
LC7-2 Wall Control 1. Press and hold the REPEAT and TIMER buttons for 3 seconds then release to enter Service Menu. The display will
show Service Menu 01.

34

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

2. Press the

or buttons to scroll to Service Menu 03. Press the PROG button to enter the Service

Menu 03.

3. Press the PROG button 11 x times to enter the Hot Start Settings.

4. Press the

or buttons to enable/disable the hot start operation.

5. Press the PROG button to accept the Hot Start setting. 6. Press the EXIT button once to return to the Main Screen.

14.04.05. Air Filter Hours
This feature allows the installer to change the alarm time of Filter Notification. By default, the time before the filter alarm notification will appear is set to 200 hours. This is adjustable from 0 to 990 hrs.
Outdoor Unit CPU Board 1. Using the MENU and the ENTER buttons, navigate to SEt (Settings) iduS (Indoor Settings) FiL (Filter) 2. Keep pressing the MENU button to select the desired filter notification alarm time is shown. By default, alarm
time is set to 200 hrs and is adjustable from 0 to 9900 Note: 0 means the Filter Alarm is disabled 3. Press ENTER button to confirm the alarm time settings. 4. Press the BACK button twice to go back to the original status display.
NOTE Setting up ” Air Filter Hours’ is only available through Outdoor Unit CPU Board.

14.04.06. Outside Air Damper
This feature allows to set the optional outside air damper opening. The available output signal is from 0 to 10V.

Option 1: LC7-2 Wall Control

1. Press and hold the REPEAT and the TIMER buttons for 3 sec then release to enter Service Menu. The display will show the Service Menu 01.

2. Press the 10.

or buttons to scroll to Service Menu 10. Press the PROG button to enter the Service Menu

3. Press the PROG button enter economy damper menu.

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

35

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

4. Press the

or buttons to enable economy damper, then press PROG to accept.

5. Press the PROG button enter economy damper setting.

6. Press the

or buttons to adjust the voltage output in 0.1V increments (0 to 10V) , then press PROG to

accept. Sample below shows 3.0V output.

7. Press the EXIT button once to go back to the original status display.
Option 2: Outdoor Unit CPU Board 1. Using the MENU and the ENTER buttons, navigate to SEt (Settings) iduS (Indoor Settings) Econ(0 to 10V
Output) 2. Keep pressing the MENU button to select the desired opening (in voltage). By default, this is set to 0 (damper
closed). Adjustable setting is from 0 to 10V. (Note that in LED 7 segment display, 10.0V will show 100. 3. Press ENTER to confirm the desired damper voltage. Press BACK button to leave the Menu. 4. Press the BACK button three times to go back to the original status display.

14.04.07. Fan Continuous ON/OFF
This feature allows the user to access Continuous Fan Operation. Disabling this will hide the function from the wall control. By default, this function is enabled. To disable, follow the instruction below.

LC7-2 Wall Control

1. Press and hold the REPEAT and the TIMER buttons for 3 sec then release to enter Service Menu. The display will show the Service Menu 01.

2. Press the 03.

or buttons to scroll to Service Menu 03. Press the PROG button to enter the Service Menu

3. Press the PROG button 7 x times to enter the Fan Continuous Settings.

36

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

4. Press the

or buttons to select OFF. Then press the PROG button to accept.

5. Press the BACK button twice to go back to the original status display. NOTE Setting up “Fan Continuous ON/OFF” is only available through LC7-2 Control.

14.04.08. Compressor Soft Start Option
If an ActronAir compressor soft starter (sold separately) will be installed, it is necessary to enable this in OD Board Menu. However, if the soft starter is already pre-installed with the unit (“-Z Option”), no set up is necessary.
Procedure:
1. Using the MENU and the ENTER buttons, navigate to SEt (Settings) SoFt (Soft Start Settings). 2. If required, press MENU to navigate to YES. By default, this is set to no.

14.04.09. Run and Fault Indication Output
Run Output is configurable to indicate that the unit is running. There are two configurations in which this can be set Either the compressor or the Indoor Fan only is running Only Compressor is running. By default, this is set to no, where indicator will turn on when either on ID Fan Only Operation mode or Compressor is running. To set up to compressor run indication only, in OD Board Menu follow below steps.

Procedure: 1. Using the MENU and the ENTER buttons, navigate to SEt (Settings) 2. If required, press MENU to navigate to YES.

run (Unit Operation Indicator Settings).

15. Optional Output/Input Relay

15.01. Filter Indication Relay Output (Indoor Board)
Allows for optional connection for Filter Indication Relay (10A/240V). Option to use either normally open or normally close relay.
NOTE To reset the alarm notification via Outdoor Board (no LC7-2 connected) , set the time again to clear/reset the filter alarm output.

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

37

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

INTERNAL FAN SPEED

0-10V FAN INPUTS PWM FAN OUTPUT MANUAL FAN SPEED POT ADJUST ON STANDARD DIP OFF 1 2 3 4 5 6 7 8 SWITCH SETTINGS

DISPLAY

)

FILTER INDICATION

NC NO

AMB COIL SENSOR TEMP
AMB COIL SENSOR TEMP
COM

(240V

OPTIONAL FILTER INDICATION RELAY
OUTPUT (240VAC 10AMax)

N/O OUTPUT INPUT VOLTAGE
N/C OUTPUT

AUX SENSOR

S1 COM S2

AMB COIL SENSOR TEMP

15.02. Fan Run Indication Output (Indoor Board)
Allows for optional Fan Run Indication (12VDC)

INDOOR COIL TEMP SENSOR

OPTIONAL FAN RUN INDICATION OUTPUT

+12V DC
OUTPUT
COM

+12V COM 0-10V COM

COIL AMB TEMP SENSOR

AUX OUT ECON OUT

15.03. Optional Outside Air Damper Control Output (Indoor Board)
This feature allows to set the optional outside air damper opening (0-10V). To set-up, see 14.04.06 Outside Air Damper Section.

AUX OUT ECON OUT

OPTIONAL OUTSIDE AIR
DAMPER CONTROL OUTPUT

0-10VDC
OUTPUT
COM

+12V COM 0-10V COM

COIL

AMB

TEMP SENSOR

16. Third Party Control Input (Indoor Board and/or Outdoor Board)
This option allows Fan, Compressor and Reversing Valve to be controlled by a Third Party Control. There are two ways on how the Indoor Fan may be controlled, using 0-10V Analogue Input or Fixed Indoor Fan Speed.
NOTE · Demand Response Management (DRM) is not available if Third Party Control Option is used. · Make sure control source has been configured for Third Party Control (Refer to section 14.03).

38

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
16.01. 0-10V Analogue Input for Compressor and Indoor Fan
Indoor Fan Connection (Indoor Board) On the Indoor Board, set the first dip switch to ON.

FAN IN AUX IN

THIRD PARTY 0-10VDC

INDOOR FAN INPUT

0-10V

CONTROL

COM

COM

INPUT

0-10V

COM

Input (DC)
0.0V to 0.99 V 1.0V to 1.49 V 1.5V to 9.5 V 9.5V to 10 V

Output
0% 0 or 20% 20% to 100%
100%

Fan Status
Off Off or On
On On

Compressor and Reversing Valve Connection (Outdoor Board)

THIRD PARTY COMPRESSOR CONTROL INPUT

0-10V INCPOUMT
0-1C0VODMC INPUT

+12+V1D2VCDC
HEAT

+12V COM
DRM3 COMP DRM2 FAN DRM1 HEAT

INPUT 0-G100V-1G0V

Input (DC) 0 – 0.99 V 1 – 1.49 V 1.5 – 9.5 V 9.5 – 10 V

Output 0%
0 or 20% 20% to 100%
100%

Compressor Status Off
Off/On (hysteresis) On On

NOTES
· As the compressor turns ON and the Indoor fan signal is not available then indoor fan will start to run on medium PWM speed.
· If the compressor turns ON, during reduced fan operation, the controller will increase the fan speed to the “low PWM fan limit” if it is running less than the low PWM Limits .
· Indoor fan low and high PWM limits depends upon the model. Refer to Section 17 for more details. · The Voltage can be linearly interpolated using the above table to determine the desired PWM or unit output.

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

39

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
16.02. 0-10V Analogue Input for Compressor with Fixed Indoor Fan Speed
This feature allows for the Indoor Fan to be controlled externally (ON/OFF only). Fan, Compressor and Reversing Valve Connection (Outdoor Board) On the indoor board ensure dip switch ONE is OFF.

THIRD PARTY COMPRESSOR CONTROL INPUT

0-10V INCPOUMT I0CN-OP10UMVT

+12VDC

INDOOR FAN HEAT

INPUT 0-1G0V0-1G0V

+12V COM
DRM3 COMP DRM2 FAN DRM1 HEAT

NOTES
· As the compressor turns ON and the Indoor fan signal is not available then indoor fan will start to run on medium PWM speed.
· Indoor fan operation when fan signal is available: – Compressor ON : Indoor fan will run on medium speed. – Compressor OFF : Indoor fan will run on reduce airflow operation.

16.03. Analogue Input for Fixed Compressor with Fixed Indoor Fan Speed
This feature allows for both Compressor and Indoor Fan to be controlled externally (ON/OFF only).
Fan, Compressor and Reversing Valve Connection (Outdoor Board) On the indoor board ensure dip switch ONE is OFF.

THIRD PARTY COMPRESSOR CONTROL INPUT

+12VDC
COMPRESSOR INDOOR FAN HEAT

+12V COM
DRM3 COMP DRM2 FAN DRM1 HEAT

40

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

NOTES · As the compressor turns ON and the Indoor fan signal is not available then indoor fan will start to run on medium
PWM speed. · Indoor fan operation when fan signal is available:
– Compressor ON : Indoor fan will run on medium speed. – Compressor OFF : Indoor fan will run on reduce airflow operation.
16.04. 0-10V Analogue Input for Indoor Fan with Fixed Speed Compressor
This feature allows for the compressor to be controlled externally (ON/OFF only).
Indoor Fan Connection (Indoor Board)

THIRD PARTY

INDOOR FAN

COM

CONTROL

0-10VDC

INPUT ID FAN INPUT

0-10V COM AUX IN

Input (DC)
0.0 V to 0.99 V 1.0 V to 1.49 V 1.5 V to 9.5 V 9.5 V to 10 V

Output
0% 0 or 20% 20% to 100%
100%

Fan Status
Off Off or On
On On

Fan, Compressor and Reversing Valve Connection (Outdoor Board)

THITRHDIRDPPAARRTTY Y COMCOPMRPREESSSSOOR R COCNOTNRTROOLL IINNPPUTUT

+12+V12VDC COMPCROEMPSRSESOSORR
HEHAETAT

+12V COM
DRM3 COMP DRM2 FAN DRM1 HEAT

NOTES
· As the compressor turns ON and the Indoor fan signal is not available then indoor fan will start to run on medium PWM speed.
· If the compressor turn ON, during reduced fan operation, the controller will increase the fan speed to the “low PWM fan limit” if it is running less than the low PWM Limits.
· Indoor fan low and high PWM limits depends upon the model. · The Voltage can be linearly interpolated using the above table to determine the desired PWM or unit output. · Compressor turns on with 100% speed request.

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

41

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

16.05. Run and Fault Indication Output (Outdoor Board)
To activate, the unit must be wired as illustrated below. If required, a fault output connection terminal is also available to show any error/fault with the a/c system.
RUN/FAULT relay outputs (230VAC/5A MAX) connection

OUTPUT INDICATORS
RUN OUTPUT VOLTAGE INPUT
FAULT OUTPUT

CONDENSER CPU BOARD
RUN COM
FAULT

Run Output is configurable to indicate that the unit is running. There are two configurations in which this can be set:

· Either the compressor or the Indoor Fan only is running · Only Compressor is running.

By default, this is set to turn on when either indoor fan or compressor is operating. To set up to compressor run indication only, in OD Board Menu follow below steps.

1. Using the MENU and the ENTER Buttons on the outdoor PCB, navigate to SEt (Settings) tion Indicator Settings).
2. If required, press MENU to navigate to YES.

run (Unit Opera-

16.06. Remote ON/OFF

To activate, the unit must be wired as illustrated below. This will enable unit to be turned ON and OFF from the Outdoor board.

TURNING THE SYSTEM ON AND OFF BY REMOTE METHOD

NOTE
The system must be operating in Wall Controller only (control mode 1) or BMS + Wall Controller (control mode 3) for this function to work.

OPTIONAL REMOTE ON OFF SWITCH

CONDENSER CPU BOARD
COM 12V

Status 1: The system is Off and the remote switch/relay has been left in the open position.
1. Close remote switch/relay. 2. System will start in approximately 1 minute. Turning the system On Status 2: The system is Off and the remote switch/relay has been left in the closed position. 1. Open remote switch/relay for a minimum of 5 seconds. 2. Close remote switch/relay. 3. System will start in approximately 30 seconds.
Status 3: The system is On and the remote switch/relay has been left in the closed position.
1. Open remote switch/relay. 2. System will turn Off in approximately 1 minute. Turning the system Off Status 4: The system is On and the remote switch/relay has been left in the open position. 1. Close remote switch/relay for a minimum of 5 seconds. 2. Open remote switch/relay. 3. System will turn Off in approximately 30 seconds.

42

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

17. Indoor Fan Table and Fan Curve

17.01. EVA290T

APPLICATION RANGE (COMPRESSOR ON)

EXTERNAL STATIC PRESSURE (Pa)

AIRFLOW
(l/s)
1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 1750 1800

50

% PWM

W

33

333

36 380

38 408

40 434

43 484

45 507

48 559

51

612

53

641

56 694

59 750

62 797

66 877

100

% PWM

W

38 452

40 480

42 508

45 559

47 587

50 639

52 671

55 730

58 785

61 838

64 890

67 945

70 1000

150

% PWM

W

42 557

44 585

47 642

49 670

51 700

54 763

57 822

59 848

62 903

66 989

69 1048

72 1106

75 1163

200

% PWM

W

46 668

48 698

51 760

53 794

55 826

58 886

61 943

64 1000

67 1060

70 1121

73 1181

77 1271

79 1316

250

% PWM

W

50 787

52 821

54 859

57

919

60 981

63 1037

66 1091

69 1156

72 1205

75 1276

79 1344

83 1414

88 1497

300

% PWM

W

54

905

56

950

60 1003

62 1069 66 1107

71

1171

74 1225

78 1292

83 1355

88 1426

93 1500

99 1551

REDUCED AIRFLOW *(COMPRESSOR OFF)

EXTERNAL STATIC PRESSURE (Pa)

AIRFLOW
(l/s)
350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150

50

% PWM

W

100

% PWM

W

MOTOR / BLOWER LIMIT

21

226

22 233

20

179

24

260

21

186

25

265

23

212

27 294

25

235

29

321

27

261

31

347

29

286

33

374

31

310

35

398

150

% PWM

W

20 242

22 274

23 282

24 290

26 320

28

351

29 357

31

386

33 414

35 440

37 472

39 502

200

% PWM

W

21

291

22 301

23 310

25

341

26 351

28 385

30 416

31 423

33 454

35 483

38 542

40 574

42 606

44 637

250

% PWM

W

20 295

22

331

23 330

25

371

27 406

28 418

30 452

31 460

33 493

35 524

37 563

40 622

42 656

44 689

46 719

48 754

300

% PWM

W

21

333

23

372

24

381

26

408

28

439

30

480

32

521

34

555

35

561

37

592

39

621

41

675

43

710

45

744

48 804

50

831

52

874

NOTES

  • Reduced fan airflow is the airflow during compressor OFF operation (optional feature) W = Indoor Fan Power, Watts PWM = Pulse Width Modulation Setting, % PWM (Adjustable through the NEO, LC7-2 Control Interface or Outdoor Board).

Default Fan Speed Value at 100 Pa

Speed

Default PWM

High PWM (%)

70 (adjustable)

Medium PWM (%)

52 (adjustable)

Low PWM (%)

38 (adjustable)

Indoor Fan PWM Limits

High PWM (%)

99

Low PWM (%)

33

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

43

Doc. No.0525-066 Ver. 8 240213

44

Installation and Commissioning Guide
FAN CURVE

EXTERNAL STATIC PRESSURE (Pa)

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

300

250 200

150

100

50

0 30% PWM

1200

1250

35% PWM 1300

AIRFLOW (l/s)

40% PWM

52% PWM

45% PWM

50% PWM

55% PWM

1350

1400

1450

1500

1550

1600

Nominal Airflow = 1500 l/s

APPLICATION RANGE

99509%%9%PPWWPMWM M 85% PWM 80% PWM

75% PWM

60% PWM

70% PWM
65% PWM

1650

1700

1750

1800

Variable Capacity Commercial

Notes: 2. Performance Fan Curve shown is at Dry Coil Condition. 3. Airflow should be reduce with respect to the moisture content in the air. 4. All data provided does not include filters. Please review filter manufacturer for application. 5. 2.5 m/s face velocity point will occur at 2150 l/s.

Installation and Commissioning Guide Variable Capacity Commercial

17.06. EVA330T

APPLICATION RANGE (COMPRESSOR ON)

EXTERNAL STATIC PRESSURE (Pa)

AIRFLOW
(l/s)
1400 1450 1500 1550 1600 1650 1700 1750 1800 1850 1900 1950 2000 2050 2100

50

% PWM

W

42 463

45 509

48 559

50 601

53 649

55 695

58 733

62 803

65 862

69 926

72 988

75 1058

79 1134

83 1206

87 1304

100

% PWM

W

47 589

49 630

52 677

54 725

57 776

61

831

64 888

67 947

70 1006

73 1076

77 1148

80 1223

84 1305

88 1387

92 1474

150

% PWM

W

51 707

53

755

55 800

59 853

62 908

65 965

68 1026

71 1087

74 1154

78 1228

81 1305

85 1389

89 1468

92 1556

96 1638

200

% PWM

W

54 835

58 896

60 935

63 992

66 1045

69 1104

72 1167

75 1235

78 1308

82 1376

86 1457

89 1533

94 1624

99 1721

250

% PWM

W

59 961

62 1011

65 1075

68 1112

70 1184

74 1243

78 1316

83 1401

88 1474

93 1557

98 1639

300

% PWM

W

71

1118

74

1172

78 1225

82 1288

85 1354

90 1419

95 1506

99 1564

MOTOR / BLOWER LIMIT

REDUCED AIRFLOW *(COMPRESSOR OFF)

EXTERNAL STATIC PRESSURE (Pa)

AIRFLOW
(l/s)
350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250 1300 1350

50

% PWM

W

100

% PWM

W

MOTOR / BLOWER LIMIT

21

217

22 230

20

176

24

257

21

183

25

263

23

209

27

291

25

232

29

318

27

259

31

345

29

282

33

375

31 308 35 402

33

335

37

431

35

361

39

457

37

387

42

513

40 426 44 541

150

% PWM

W

20 236

21

247

23 278

24 286

26 316

27

323

29 352

31

383

33

415

34 420

36 449

39 503

41 536

44 594

46 623

48 659

200

% PWM

W

21

287

22 297

23 307

25 338

26 347

28 380

30 410

31

418

33 453

35 486

36 492

38 524

41 585

43 618

46 678

48 708

50 737

52 780

250

% PWM

W

20 289

22 322

23

337

25 370

26 378

28 415

30 446

31 454

33 492

35 524

37

561

38 568

40 600

43 669

46 727

48 764

50 794

52 832

54 888

56 918

300

% PWM

W

12

174

23

347

25

393

26

403

28

431

30

476

32

499

34

532

35

561

37

580

39

615

42

665

44

714

47

763

50 804

52

845

55

887

57

929

60

969

64 1024

67 1065

NOTES

  • Reduced fan airflow is the airflow during compressor OFF operation (optional feature) W = Indoor Fan Power, Watts PWM = Pulse Width Modulation Setting, % PWM (Adjustable through the NEO, LC7-2 Control Interface or Outdoor Board).

Default Fan Speed Value at 100 Pa

Speed

Default PWM

High PWM (%)

92 (adjustable)

Medium PWM (%)

67 (adjustable)

Low PWM (%)

47 (adjustable)

Indoor Fan PWM Limits

High PWM (%)

99

Low PWM (%)

42

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

45

Doc. No.0525-066 Ver. 8 240213

46

EXTERNAL STATIC PRESSURE (Pa)

Installation and Commissioning Guide
FAN CURVE

300

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

250

200

99% PWM

95%

PWM

150

100

50

0

40% PWM

1400

1450

45% PWM 1500

AIRFLOW (l/s)

50% PWM

1550

1600

55% PWM

67% PWM

60% PWM

65% PWM

70% PWM

75% PWM

80% PWM

85% PWM

1650

1700

1750

1800

APPLICATION RANGE

Nominal Airflow = 1750 l/s

1850

1900

1950

2000

90%

PWM

2050 2100

Notes:

7. Performance Fan Curve shown is at Dry Coil Condition.

8. Airflow should be reduce with respect to the moisture content in the air.

9. All data provided does not include filters. Please review filter manufacturer for application.

2.5 m/s face velocity point will occur at 2150 l/s.

Variable Capacity Commercial

Installation and Commissioning Guide Variable Capacity Commercial

18. Refrigerant Charging
· The units detailed on this guide are factory charged with R-410A refrigerant. Should there be need to add or remove refrigerant, it is recommended to follow the charging method explained below.
· Never allow R-410A refrigerant to vent into the atmosphere. It is an offence to release refrigerant in Australia. Always reclaim refrigerant using equipment and container dedicated for R-410A system use only.
· All work must be carried out in accordance with Australia and New Zealand refrigerant handling code of practice. · Only qualified technicians are allowed to perform any work described in this guide and specifically work related to
addition or removal of refrigerant. · R-410A refrigerant must always be charged in liquid state. · Only during the compressor running condition the system can be charged through the suction service port on the
compressor suction line. · Changes in refrigerant charge must be noted to a label that is fixed to the unit for future reference.

CAUTION
The system of this unit operates with POE oil that rapidly absorbs moisture. The maximum time any system can be opened to atmosphere is 15 minutes.

Model
CRV290T CRV330T

REFRIGERANT CHARGE DETAILS (R-410A)

Refrigerant Charge (g)
9,600 11,300

Pre-charged Length (m)
5 5

Additional Refrigerant Field Fipe Sizing (mm)

per metre

Liq.

Gas

165

5/8″ (15.88) 1-1/8″ (28.6)

165

5/8″ (15.88) 1-1/8″ (28.6)

Charging Method: Subcooling and Superheat

Parameters: LLT = Liquid Line Temperature

SLT = Suction Line Temperature

SCT = Saturated Condensing Temperature SST = Saturated Suction Temperature

Cooling and Heating Operation:
Adjust the refrigerant charge to obtain the correct superheat and subcooling for optimal performance as follows:
1. Ensure that air filters are fitted and total system airflow is achieved. (Air filters are not supplied with the unit, it is the responsibility of the installing contractor to provide and fit adequate return air and outside air filters).
2. Connect service gauges to the schrader valves. 3. Start the unit in cool mode ensuring that compressors are in 100% operation before taking service gauges reading.
Allow the system to stabilise for next 15-30 minutes before recording.

Record the discharge pressure, suction pressure, liquid line temperature and suction line temperature for all of the refrigeration circuits:

Discharge Pressure = ____ kPa

Suction Pressure = __ kPa

Liquid Line Temperature (LLT) = ____ °C

Suction Line Temperature (SLT) = ___ °C

NOTE Accurate pressure and temperature measuring tools should be used to achieve satisfactory results.

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

47

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide

See Diagram Below

SERVICE GAUGES

Variable Capacity Commercial

DISCHARGE SCHRADER VALVE
SUCTION SCHRADER VALVE

R-410A * Refrigerant Container

  • Use weighing scale when adding or removing refrigerant charge.

NOTE
For illustration purpose only. Valve location may vary depending on unit model.

Checking for Subcooling:
1. From the R-410A Pressure/Temperature Chart record the corresponding Saturated Condensing Temperature (SCT) at the given discharge pressure.
2. Calculate the system subcooling using the formula below: Subcooling = SCT – LLT
3. If subcooling is within the range (see charging table), there is no need to add/remove refrigerant. · If subcooling is lower than minimum, the system is undercharged, it is necessary to add refrigerant. · If subcooling is higher than maximum, the system is over charged . It is necessary to remove refrigerant.
Allow the systems to stabilise (15-30 mins) and repeat the step 1-3 until subcooling falls within the range specified in the Subcooling and Superheat Table .
Checking for Superheat:
Maintaining the correct superheat is important for ensuring the evaporator is achieving maximum capacity and avoiding excessive liquid refrigerant returning to the compressor.
1. From the R-410A Pressure/Temperature Chart record the corresponding Saturated Suction Temperature (SST) at the given suction pressure.
2. Calculate the system superheat using the formula below: Superheat = SLT -SST

48

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

3. If superheat is within the range (see charging table below), there is no need to add/remove refrigerant. · If superheat is lower than minimum, it means that liquid refrigerant may be returning to compressor. It is necessary to remove refrigerant or check EEV settings.
· If superheat is higher than maximum, it means that refrigeration capability of evaporator is not fully maximised. It is necessary to add refrigerant charge or check EEV settings.

Allow the systems to stabilise (15-30 mins) and repeat the step 1-3 until superheat falls within the range specified in the table below.

Models
CRV290T CRV330T

SUBCOOLING AND SUPERHEAT TABLE

Nominal Indoor

Cooling

Airflow (L/S) Subcooling

Superheat

Heating

Subcooling

Superheat

1500

7 ±1

3 ±1

12 ±1

2 ±1

1750

8 ±1

4 ±1

13 ±1

6 ±1

R-410A PRESSURE / TEMPERATURE CHART

Temp oC -60 -59 -58 -57 -56 -55 -54 -53 -52 -51 -50 -49 -48 -47 -46 -45 -44 -43 -42 -41 -40 -39 -38 -37 -36 -35 -34 -33 -32 -31 -30 -29

Pressure KPa -34.4 -30.7 -26.8 -22.8 -18.6 -14.2 -9.6 -4.8 0.8 5.3 10.7 16.3 22.2 28.2 34.0 40.9 47.8 54.8 62.1 69.6 77.4 85.5 93.9 102.5 111.5 120.8 130.4 140.3 150.5 161.1 171.9 183.3

Temp oC -28 -27 -26 -25 -24 -23 -22 -21 -20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3

Pressure KPa 194.9 206.9 219.2 231.9 245.1 258.7 272.6 286.9 301.7 316.9 332.6 348.7 365.2 382.3 399.7 417.7 436.2 455.1 474.6 494.6 515.1 536.2 557.8 579.9 602.6 625.9 649.8 674.3 699.4 724.9 751.3 778.3

Temp oC 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35

Pressure KPa 805.9 834.1 862.9 892.6 922.8 953.8 985.4
1017.8 1050.9 1084.7 1119.2 1154.6 1190.7 1227.5 1265.2 1303.6 1342.9 1382.9 1423.9 1465.7 1508.3 1551.8 1596.2 1641.4 1687.6 1734.6 1782.6 1831.6 1881.5 1932.3 1984.1 2036.9

Temp oC 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67

Pressure KPa
2090.7 2145.5 2201.3 2258.2 2316.1 2375.1 2435.1 2496.2 2558.5 2621.8 2686.2 2751.8 2818.5 2886.4 2955.5 3025.7 3097.2 3169.9 3243.7 3318.9 3395.2 3472.9 3551.8 3631.9 3713.5 3796.3 3880.5 3965.9 4052.8 4140.9 4230.6 4321.5

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

49

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

Maintenance
This section describes the procedures that must be performed as a part of normal maintenance PROG. Regular servicing of equipment by licensed technician is highly recommended. Regular servicing of your unit helps in maintaining its optimum performance and reliability. The checklist and service periods provided on this manual are guides only, as some sites may require more frequent servicing.
Always disconnect electrical power to the unit before performing these procedures. It is always a safe practice to observe all safety warnings and cautions when conducting maintenance tasks.

DANGER Live Electrical Connections ! It may be necessary to work with live electrical components on certain maintenance tasks. Only licensed electricians and qualified technicians are allowed to perform these tasks.
Beware of Rotating Fan Blades ! Always make sure that all power supply, to the Outdoor Fans are turn-off and isolated.
Observe WH&S safety procedures, do not wear loose clothing and any jewellery when working near the fans. Wear PPE whenever performing any maintenance procedures. Observe all necessary procedures when working on a confined space.

WARNING Hazardous Voltage ! Always make sure that all power supply, including remote controls, are disconnected before performing maintenance. Observe proper LOCK-OUT/TAG-OUT (LOTO) procedures to ensure that power cannot be inadvertently energised. Failure to disconnect power before maintenance procedures can result in serious injury and/or death.
EC Motors are fitted with high power capacitors and can have dangerous residual voltages at motor terminals after power has been isolated. Wait at least 5 minutes after power isolation and test for any residual voltage before beginning service work.
Annual Maintenance Checklists · Perform general maintenance inspections. · Perform scheduled start-up checks. · Leak test refrigerant circuits. · Inspect contacts of all contactors and relays. Replace all worn contacts as required. · Inspect, clean and tighten all electrical connections. · Check fans for balanced operation. Make sure that there are no loose screws / bolts, no fan blades interference and
no damage to the fans and guards. · Inspect the air filters, clean or replace as required. · Clean and repaint any corroded panel section. · Ensure no blockage of airflow through variable speed drive.

50

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial
Cleaning the Condenser Coils
Clean the coils at least once a year or more frequently if unit is located in a dusty and dirty environment, in order to maintain your system’s proper operating performance. High discharge pressures are good indication that the coils need cleaning. When using detergent or solvents to clean the coils, follow the manufacturer’s instructions to avoid potential damage to the coils and to the unit.
To clean the refrigerant coils, use a soft brush and water spray, such as garden hose or pressure washer with low pressure nozzle.
WARNING Do Not Use High Alkaline Detergent! When using detergent for coil cleaning, ensure that the alkaline level is no higher than 8.5, which can cause corrosion damage to the coils.
No Water into the Drive! Ensure consideration is given to the possibility of water entering the electrical compartments during cleaning of the condenser coil.
Coil Cleaning Procedures · Disconnect power to the unit. · Remove the louvered panels from the unit to gain access to the air inlet side of the coils. · Use a soft brush to remove loose dirt and debris from both sides of the coils. · Straighten bent coil fins with fin comb. · Prepare the detergent solutions according to the manufacturer’s instructions. · Spray solution at a 90o angle to the coils, keeping a minimum nozzle spray angle of 15°, with at least a 1800mm
distance from the coils and 600 psi pressure. · Spray leaving air side of the coils first then the air inlet side. Allow the solution to stand on the coils for five minutes. · Rinse both sides of the coils with cool clean water. · Inspect the coils, if they are still dirty, repeat the cleaning procedure. · Clean and wipe dry the outer and inner sides of the unit, the refrigerating parts and other components. · Ensure that the condensate drain lines are not blocked. · Reinstall all unit panels, covers and guards. · Restore electrical power to the unit.

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

51

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

20. Maintenance Frequency Checklist

ELECTRICAL

Parts

Service Frequency 1 3 6 1 2 3 4 5 Detail of Service Check Mth Mth Mth Yr Yrs Yrs Yrs Yrs

Printed Circuit Boards

Visual Inspection

Service Methods
Tighten Terminals as necessary on printed circuit boards

Electrical Connections

Check all electrical terminals, mains, communications, etc

Re-tighten if loose.

INDOOR UNIT

Parts
Casing / Panels and Frames
Insulation
Fan
Motor
Heat Exchanger

Service Frequency 1 3 6 1 2 3 4 5 Detail of Service Check Mth Mth Mth Yr Yrs Yrs Yrs Yrs

Visual check for damage, rust and dust accumulation.

Service Methods
For highly corrosive environment, wash panels quarterly with water and neutral detergent solution. Wax panels. Repair / re-paint where
required.

Visual check for insulation conditions.

Repair / replace insulation material.

Visual check for run out of balance and dust attached

Clean off dust as necessary to negate possibility of fan running
out of balance

Visual check on wiring.

Measure insulation resistance

Insulation resistance check

to earth with insulation tester. Insulation resistance should be more

to be carried out annually

than 1M.

Check for clogging by dust. Check for leaks / damage.

Clean air inlet side as necessary. Straighten any bent fins using fins
comb.

Drain Pan/

Condensation

line

Check for obstructions and free flow of water

Clean to eliminate obstructions/ sludge and check condition of pan.
Pour water to ensure free flow.

Filter*

Check for clogging by dust.

Clean Filter

Temperature Readings

Measure air on and air off

Ducting

Inspect duct works for air gaps.

*1-3 month, subject to operating conditions and environment.

Place temperature probe in return and supply air of unit.
Re-tape any loose ducts.

52

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

OUTDOOR UNIT

Parts
Casing / Panels and Frames

Service Frequency 1 3 6 1 2 3 4 5 Detail of Service Check Mth Mth Mth Yr Yrs Yrs Yrs Yrs

Visual check for damage, rust and dust accumulation.

Service Methods
For highly corrosive environment, wash panels quarterly with water and neutral detergent solution. Wax panels. Repair / re-paint where
required.

Insulation

Fan

Motor

Heat Exchanger

Condensate

Drain Line

(if available)

Compressor

Refrigeration

Operational

Readings

Safety Devices

Visual check for insulation conditions.

Repair / replace insulation material.

Visual check for run out of balance and dust attached
Visual check on wiring. Insulation resistance check to be carried out annually
Check for clogging by dust. Check for leaks / damage.

Clean off dust as necessary to negate possibility of fan running out
of balance
Measure insulation resistance to earth with insulation tester. Insulation resistance should be
more than 1M.
Clean air inlet side as necessary. Straighten any bent fins using fins
comb.

Check for obstructions and free flow of water
Check for high / low pressure. Measure insulation resistance. Check compressor for abnormal noise/vibrations

Clean to eliminate obstructions/ sludge and check condition of drain line. Pour water to ensure free flow.
Measure insulation resistance. Should be more than 1M.

Make note of operational Check operating pressures, record reading in test cool/heat superheat and subcooling values

Check calibration of safety

Check resistance of sensors,

devices such as HP and LP pressure cut in / cut out of pressure

controls, sensors, etc

controls

Faults

Check for any previous fault Investigate any causes for previous

history on unit.

faults, reset fault history.

Outdoor

Fan Speed

Capacitor

Check for any bulge on the capacitors & capacitance.

Make it electrically safe prior to measure the capacitor capacitance.
Measured capacitance should be with in the printed tolerances on the
capacitor.

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

53

Doc. No.0525-066 Ver. 8 240213

Installation and Commissioning Guide Variable Capacity Commercial

21. Start Up and Commissioning Report

INSTALLATION INFORMATION

CUSTOMER

Name: Address:

INSTALLER

Name: Address:

Site Address:

Tel. Number: Tel. Number: Date Installed:

Model:

Serial Number:

CIRCUIT TEMPERATURE SETTINGS AND AMBIENT TEMPERATURE

SYSTEM 1

SYSTEM 2

Supply Air Temperature

°C Supply Air Temperature

Return Air Temperature

°C Return Air Temperature

Suction Temperature

°C Suction Temperature

Discharge Temperature

°C Discharge Temperature

Condenser Coil Temperature

°C Condenser Coil Temperature

Ambient Temperature

°C

INDOOR FAN SETTINGS
Indoor Fan Current Indoor Fan Airflow Set Static

Amps Outdoor Fan Current l/s Indoor Fan PWM Pa

Check No Active Error Codes on the Unit

Checked:

Date Checked:

°C °C °C °C °C
Amps %

NOTES
Ensure to record operational settings on this table for future reference. Keep this manual in a safe place and readily available for service technicians.

54

Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit

Doc. No.0525-066 Ver. 8 240213

THIS PAGE WAS INTENTIONALLY LEFT BLANK

Refrigerant Trading Authorisation No.: AU06394
©Copyright 2019 Actron Engineering Pty Limited ABN 34 002767240. ®Registered Trade Marks of Actron Engineering Pty Limited. ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Installation and Commissioning Guide – Split Ducted Variable Capacity Commercial Outdoor Unit Doc. No.0525-066 Ver. 8 240213

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals