ActronAir CRQ2-16AT Three-Phase Platinum Air Conditioner User Guide
- June 3, 2024
- ActronAir
Table of Contents
ActronAir CRQ2-16AT Three-Phase Platinum Air Conditioner
Model Numbers
- CRQ2-16AT / ERQ2-16AS
- CRQ3-18AT / ERQ3-18AS
- CRQ5-21AT / ERQ5-21AS
- CRQ5-24AT / ERQ5-24AS
IMPORTANT NOTE:
Please read this manual carefully before installing or operating your air
conditioning unit
Fault Finding Guide
FAULT | POSSIBLE CAUSES | REMEDIES |
---|
The system does not start.
| Built-in safety timers have been activated.| Ensure that 5 minutes
has passed from turn on time.
A breaker has turned OFF or a fuse has
blown.| Check breakers and fuses.
The thermostat set point is incorrect.| Check the wall
control settings are correct. Check the “set point” is set low enough for
cooling or high enough for heating.
The master wall controller timer setting is incorrect.| Check the
wall controller timer settings. See Operating Instructions section.
Air does not flow (Indoor unit).
| Zones might be switched off.| Check zones are switched on.
During heating operation, the hot start function may have been
activated.| During heating operation, the indoor fan is delayed for 46
seconds or until the indoor coil reaches 24 oC (whichever occur first).
This is to prevent cold drafts. Wait for 46 seconds and the **air will start
flowing.
During defrost of the outdoor coil in heating operation; the indoor fan
will not operate for several minutes. (The wall controller will display
Defrost symbol in the top left-hand of the
screen status bar. This Defrost symbol will be**
seen on all screens).
| This is normal operation during the defrost cycle to prevent cold air being blown into rooms.
Cooling/Heating is not sufficient.
| The cooling/heating function may not work effectively when the return
air filter is clogged with dust and dirt.| Clean
the return air filter.
The cooling/heating function may not work effectively if the air inlet
and air outlet on the outdoor unit are blocked.| Make sure the air
inlet and air outlet on the outdoor unit is not blocked.
Check that the area around the outdoor unit is free from obstructions that may cause the airflow to recirculate.
The airflow across the indoor coil may not be enough and the anti-freeze
protection or over heat prevention systems can lower the cycle
capacity for the unit| Reduce the total static pressure on the indoor
fan to increase airflow. For example increase duct sizes, reduce tight
duct work bends or increase return air grille size.
The cool/heat load is too great for the air conditioner.| Perform
a heat load analysis on the conditioned space. You may need to consider
upgrading your air conditioner with a larger system.
Open windows or doors will cause inefficient operation.| Close
windows and doors in conditioned areas.
Appropriate zones not turned on.| Turn on
appropriate zones (if applicable).
The outside temperature is beyond the air conditioner design
conditions.| If you know an extreme day is coming turn the air
conditioner on a few hours before ambient temperatures reach
extreme.
This should help on those few extreme days.
You may be trying to operate the whole house on Auto Fan
Mode.| Change fan mode to constant HIGH fan speed. This
increases the total fan speed. This will boost
fan capacity.
FAULT| POSSIBLE CAUSES| REMEDIES
---|---|---
Steam emitted from outdoor unit.
| This is caused by the defrosting operation of the outdoor units heat
exchanger in heating operation in cold ambient conditions.| This is
normal during the defrost operation in cold ambient conditions.
Condensation of water on the outdoor coil during heating operation.|
This is normal during heating operation. You can purchase drip trays to
contain then drain this excess water.
Set temperature cannot be adjusted.| The zone control set
temperature limits are being exceeded.| Check the upper
and lower temperature limits are set correctly. See
operation manual for details on setting upper and lower temperature
limits.
Occasional hissing noise can be heard on heating cycle.| This is
the sound of the gas changing direction as de-ice cycle begins.| This
is a normal function of an air conditioner. The unit is removing any ice
on the outdoor unit.
The compressor is running but the system is not cooling.| You are
in heating mode.| Check the temperature settings.
The reversing valve has jammed between heating and cooling.|
Replace reversing valve.
The outdoor coil keeps freezing over.| Outdoor coil sensor might
be faulty. See sensor (temperature/resistance) table and check
resistance value.| Replace faulty sensor.
May have obstruction in outdoor coil.| Remove
obstructions.
There is only one condenser fan working.| The fan is faulty. Test
the fan motor for correct voltage, check motor winding resistance, open
circuit, check capacitor, etc.| Replace faulty fan. If the
fan motor needs to be replaced and there is no one available
immediately, then just disconnect the fan electrically and cover the
faulty motors fan guard. This way the unit can still operate at reduced
capacity using 1 fan until you get a replacement fan motor.
The system is short on gas. You have fixed the leak
and want the system to operate at 100% so gas charge can be
corrected. What can you do to ensure 100% compressor operation?| You
can adjust your wall controller temperature so you have a large differential.
This will operate at the system at 100% till the
temperature gets to within 4 oC of the set point.| Select
Cooling or heating mode. If cooling adjust set-points more than 4 oC lower
than **room temp. If Heating adjust set-points more than 4 oC higher
than room temp. Complete charging procedure until finished.**
It is recommended to run QUE test mode (cool or heat test). This can be found in the test menu in the technical menu of the QUE master control.
The indoor unit gives out odour
| This happens when smell of the room, furniture, or cigarettes are
absorbed into the unit and discharged with the airflow.| If this happens,
we recommend you to run the air conditioner on cooling for a period of time
with the doors and windows open or have the indoor unit washed by a
technician. Consult the installer from whom you bought the air
conditioner.
Check the drain is not piped into the sewerage drain line.| Re-
pipe drain with a P-Trap and connect into household drainage or storm
water drain.
EC Fan Troubleshooting
FAULT| SEQUENCE OF EVENTS| POSSIBLE CAUSES|
REMEDIES
---|---|---|---
Airflow hunting during AUTO and Self Learn Mode.
| ****
Indoor fan will intermittently “huff”.
| Excessive static in duct work.| Reduce static where possible. Review duct design with reference to ActronAir design guidelines (Service Manual, Section 23).
Too much airflow when minimum zones are on.
| ****
Air is blowing too much when in minimum zones.
| Fan not set to Auto Mode.| Change fan setting to
Auto Mode
Duct design is not air balanced correctly.| Adjust the duct design
to air balance correctly.
Minimum duct and outlet sizes requirements not followed.| Check
versus ActronAir guidelines and adjust/change if necessary.
Review duct design with reference to ActronAir design guidelines (Service Manual, Section 23).
Auto Mode is not available.
| ****
When scrolling through fan speeds, Auto Mode is not selectable.
| During commissioning, Self- Learn mode was not activated.| Carry
out self learn mode. See additional operating instruction.
Self learn failed during commissioning.| Ensure that the air is
balanced correctly (static may be too low). Review duct design
guidelines (Service Manual, Section 23).
Low airflow during Auto Mode
| ****
System produces reduced airflow on Auto mode when all or minimum zones are on.
| System capacity has been designed to heat/cool only selected areas of the
conditions space at any one time.
| Operate indoor fan on L o w / M e d/ High
speed to achieve more airflow.
Excessive static in ductwork.| Reduce static where
possible. Review duct design with reference to ActronAir design guidelines
(Service Manual, Sec.23).
Indoor fan not changing speeds when in Auto Mode.
| When zones are switched to the off position, or as the damper position of active zones close (VAV zones
only), airflow to active zones does not
reduce.
| There is insufficient static within the duct design of the active
zones.| Review duct design with reference to ActronAir design guidelines
(Service Manual, Sec. 23).
When zones are switched to the on position, or as the damper position
of active zones open (VAV zones
only), airflow to active zones does not
increase.
| There is excessive static within the duct design of
the active zones.| Review duct design with reference to ActronAir
design guidelines (Service Manual, Sec. 23).
FAULT| SEQUENCE OF EVENTS| POSSIBLE CAUSES|
REMEDIES
---|---|---|---
Indoor fan not changing speeds when in Auto Mode.
| ****
When zones are switched on or off, or as the damper position modulates
between the open and closed position (VAV zones only) of active zones open, airflow to actives zones does not increase.
| ****
The indoor PCB is not changing the fan PWM to adjust the fan PWM to adjust the fan speed.
| Check the output PWM from indoor PCB. An increase in fan speed should result in a increase in the fan % PWM (duty cycle). Refer to table below test points expected voltages. To determine if the system may be
suffering from excessive or insufficient static, check PWM and RPM values through the indoor unit dashboard on the Master Wall Controller:
• If the RPM is at its maximum value and the PWM has not reached its requested value, this indicates a high static. (Please refer to RPM Limits on next page)
• When switching off zones and there is little or not change in the RPM value, this indicates
insufficient static within remaining active zones duct work.
Expected Voltage
NOTES
If COM1 (LED1) and COM2 (LED2) are blinking, communication is happening.
Voltage sending between A-G and B-G are fluctuating, this means that the
communication is happening.
To check Output PWM in Indoor PCB
UNIT MODEL
| EXPECTED PWM % (APPROX)
---|---
LOW| MEDIUM| HIGH
ERQ2- 16AS| 49| 66| 86
ERQ3- 18AS| 62| 85| 100
ERQ5- 21AS| 42| 59| 80
ERQ5- 24AS| 44| 61| 81
- Set the tester to measure duty cycle.
- Measure the reading across PIN 3 and 4 (blue and yellow wires).
- Change fan speed and check for any changes in readings.
RPM Limits
UNIT MODEL
| RPM LIMITS
---|---
LOW| MEDIUM| HIGH
ERQ2- 16AS| 1150| 1290| 1500
ERQ3- 18AS| 1150| 1290| 1500
ERQ5- 21AS| 1150| 1290| 1500
ERQ5- 24AS| 1150| 1290| 1500
Compressor Winding
UNIT MODEL
| COMPRESSOR PART NUMBER/MODEL| RATING OF COMPRESSOR
WINDINGS (OHMS)
---|---|---
C – S| C – R| S – R
CRQ2- 16AT| ****
ZPV038LE- 4X9
| 0.521| 0.521| 0.521
CRQ3- 18AT| 0.521| 0.521| 0.521
CRQ5- 21AT| ****
ZPV050DE- 4X9
| 0.610| 0.610| 0.610
CRQ5- 24AT| 0.610| 0.610| 0.610
NOTE
Please refer to Section 13 – Operation Details on pages 40-41 of Service
Manual for Compressor Suction / Discharge Temperature Sensor Chart.
Fault and Status Codes
*QT- 1000,**
Master Controller (Main Screen)
| *ZT- 100**
Zone Controller
| Outdoor Unit CPU| ****
Category
| ****
FUNCTION / FAULT
---|---|---|---|---
OFF| OFF| oFF| Status| Unit Off or Unit
Turning Off (flashing)
Cooling (Status Bar)| Cooling| CooL| Status|
Unit Cooling Mode or Start Cooling (flashing)
Heating (Status Bar)| Heating| HEAt| Status|
Unit Heating Mode or Start Heating (flashing)
–| –| dEF3| Status| 3 min to defrost
Defrost Status| –| dEF| Status| Heating Mode –
Defrost
Heating| Heating| HEAt| Status| Heating Mode
– Indoor coil pre-heat after defrost
–| –| dEF2| Status| 2 min to defrost
–| –| dEF1| Status| 1 min to defrost
–| –| oiLr| Status| Oil returning
Flash Icon ( Stat Bar)| –| dr-1| Status|
DRM1
Flash Icon ( Stat Bar)| –| dr- 2|
Status| DRM2
Flash Icon ( Stat Bar)| –| dr- 3|
Status| DRM3
! **– Tech Menu (E02)| –| E02| IDU| Indoor Coil
IN Sensor Error (open or short circuit)
! ****– Tech Menu (E03)| –| E03| IDU| Indoor
Room Sensor Error (open or short circuit)
! ****– Tech Menu (E04)| –| E04| IDU| Indoor
Coil OUT Sensor Error (open or short circuit)
! ****– Tech Menu (E06)| –| E06| ODU| High
Discharge Temp. (Discharge Temp exceeded 138°C)
! ****– Tech Menu (E07)| –| E07| ODU| Outdoor
Coil Sensor Error (open or short circuit)
! ****– Tech Menu (E08)| –| E08| ODU| Outdoor
Discharge Sensor Error (open or short circuit)
! ****– Tech Menu (E09)| –| E09| ODU| LP
Tripped
! ****– Tech Menu (E10)| –| E10| ODU| LP Sensor
Error (open/short circuit)
! ****– Tech Menu (E11)| –| E11| ODU| HP
Tripped
! ****– Tech Menu (E12)| –| E12| ODU| HP
Sensor Error (open/short circuit)
! ****– Tech Menu (E15)| –| E15| ODU / VSD| VSD
Communication Error
! ****– Tech Menu (E18)| –| E18| ODU| Suction
Temp Sensor is Open
! ****– Tech Menu (E22)| –| E22| ODU| Ambient
Sensor Failure (open/short circuit)
! ****– Tech Menu (E26)| –| E26| VSD| Over
Current
! ****– Tech Menu (E27)| –| E27| VSD| Over
Voltage
! ****– Tech Menu (E28)| –| E28| VSD| VSD
Temperature High
! ****– Tech Menu (E29)| –| E29| VSD| Low
Supply Voltage
! ****– Tech Menu (E30)| –| E30| VSD| Trip
Lock
! ****– Tech Menu (E41)| –| E41| VSD| DC Link
Voltage Low
! ****– Tech Menu (E42)| –| E42| ODU| Envelope
protection error – Extremely low evaporating
pressure
! ****– Tech Menu (E43)| –| E43| ODU| Envelope
protection error – High compression ratio
! ****– Tech Menu (E44)| –| E44| ODU| Envelope
protection error – High condensing pressure
! ****– Tech Menu (E45)| –| E45| ODU| Envelope
protection error – Low compression ratio
! ****– Tech Menu (E50)| –| E50| ODU| Outdoor
Board configuration error
! ****– Tech Menu (E51)| –| E51| IDU / ODU|
Communication error between outdoor and indoor
units
! ****– Tech Menu (E52)| –| E52| IDU /**
Controller
| Communication error between indoor and master
controller
! **– Tech Menu (E53)| –| E53| IDU / Zone
Module| Communication error between indoor board and 8-zone
module.
! ****– Tech Menu (E60)| –| E60| VSD| Compressor
Phase Over Current
! ****– Tech Menu (E62)| –| E62| VSD| DC Bus
Over Voltage
! ****– Tech Menu (E63)| –| E63| VSD| DC Bus
Under Voltage
! ****– Tech Menu (E66)| –| E66| VSD| AC Voltage
Imbalance
! ****– Tech Menu (E67)| –| E67| VSD| Inverter
De-saturation
! ****– Tech Menu (E69)| –| E69| VSD| PFC-IGBT
Over Temp
! ****– Tech Menu (E70)| –| E70| VSD| Lost
Rotor Position
! ****– Tech Menu (E71)| –| E71| VSD| Motor
Thermistor Fault
! ****– Tech Menu (E72)| –| E72| VSD| Pre-charged
Relay Open
! ****– Tech Menu (E74)| –| E74| VSD| Compressor
Phase Over Current
QT*- 1000,**
Master Controller (Main Screen)
| *ZT- 100**
Zone Controller
| Outdoor Unit CPU| ****
Category
| ****
FUNCTION / FAULT
---|---|---|---|---
! **– Tech Menu (E75)| –| E75| VSD| Compressor
Phase Current Fold Back Timeout
! ****– Tech Menu (E76)| –| E76| VSD| Power Module
Temp. Fold Back Timeout
! ****– Tech Menu (E77)| –| E77| VSD| AC
Input Current Fold Back Timeout
! ****– Tech Menu (E78)| –| E78| VSD| Auto
Config Communication Timeout
! ****– Tech Menu (E80)| –| E80| VSD| Motor
Temp High
! ****– Tech Menu (E81)| –| E81| VSD| Board
Temp High
! ****– Tech Menu (E82)| –| E82| VSD| Power
Module Temp High
! ****– Tech Menu (E83)| –| E83| VSD| PFC-IGBT
Temp High
! ****– Tech Menu (E84)| –| E84| VSD| DSP to
PFC Communication Lost
! ****– Tech Menu (E85)| –| E85| VSD| Comms to DSP
Communication Lost
! ****– Tech Menu (E86)| –| E86| VSD| Compressor
Phase Current Imbalance
! ****– Tech Menu (E87)| –| E87| VSD| 3 Phase
PFC Current Imbalance
! ****– Tech Menu (E88)| –| E88| VSD| Micro
Electronic Fault or Drive EEPROM Fault
! ****– Tech Menu (E89)| –| E89| VSD| Motor Over
speed
! ****– Tech Menu (E90)| –| E90| VSD| Compressor
Model Configuration Error
! ****– Tech Menu (E91)| –| E91| VSD| Inverter
Temp Imbalance
! ****– Tech Menu (E92)| –| E92| VSD| PFC
Temp Imbalance
! ****– Tech Menu (E93)| –| E93| VSD| Motor
Temp Low
! ****– Tech Menu (E94)| –| E94| VSD| Board
Temp Low
! ****– Tech Menu (E95)| –| E95| VSD| Power Module
Temp Low or Sensor Open fault
! ****– Tech Menu (E96)| –| E96| VSD| PFC-IGBT
Temp Low
! ****– Tech Menu (E97)| –| E97| VSD| Comms ADC
Failure**
- PFC: Power Factor Correction
- IGBT: Insulated-Gate Bipolar Transistor
- DSP: Digital Signal Processor
- ADC: Analog to Digital Converter
THIS PAGE WAS INTENTIONALLY LEFT BLANK
©Copyright 2019 Actron Engineering Pty Limited ABN 34 002767240. ®Registered
Trade Marks of Actron Engineering Pty Limited. Document: 9590-2011-03 Ver. 2
Issue Date: 11/2022
actronair.com.au 1300 522 722
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>