ActronAir R-410A ADVANCE Split Ducted Unit User Manual
- June 3, 2024
- ActronAir
Table of Contents
- ActronAir R-410A ADVANCE Split Ducted Unit
- General Troubleshooting
- EC Fan Troubleshooting
- Indoor Fan PWM and RPM Limits Table
- **** Component Troubleshooting
- Testing Indoor Board
- Expected Control Voltage On Communication Line – InZone Board (R-410A /
- Expected Control Voltage On Communication Line – UNO Board Series
- Expected Voltage – InZone PCB To Indoor Fan
- Compressor Winding Resistance
- Condenser Fan Winding Resistance
- Other Component Coil Resistances
- EEV Resistance
- Temperature-Resistance Table For Sensors
- Pressure-Voltage Table For Pressure Transducers
- Fault and Status Codes
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
ActronAir R-410A ADVANCE Split Ducted Unit
General Troubleshooting
Fault Possible Causes The outdoor coil keeps freezing over. Faulty outdoor
coil sensor There is only one condenser fan working. Faulty fan motor.
Compressor won’t operate at 100% capacity. You can adjust your wall control
temperature so you have a large differential. This will operate the system at
100% until the temperature gets to within 4oC of the setpoint.
Note: If the system operates under Anti Freeze or Overheat Protection the
system will not operate at 100% capacity Odour in the conditioned space when
the A/C is turned on. Indoor unit has absorbed the conditioned space smells
eg. cigarette, cooking, etc.
Fault | Possible Causes | Remedies |
---|---|---|
The system does not start. | Built-in safety timers have | |
been activated. | Allow up to 5 minutes for the system to start from when it is |
turned on.
A circuit breaker may have tripped.| Check circuit breakers.
The thermostat setpoint is incorrect.| Lower the set point on cooling or raise
it on heating modes.
The master wall control timer is set.| Check the wall control timer settings.
No airflow from the outlets.| During heating operation, the hot
start function may have been activated.| During heating operation, the indoor
fan is delayed for 30 seconds or until the indoor coil reaches 25oC (whichever
occur first). This is to prevent cold drafts.
The system may be operating in a defrost cycle during the heating cycle. (LR7
will display DEFROST. NEO will display Defrosting. )| This is normal
operation during the defrost cycle to prevent cold air being blown into rooms.
Cooling/Heating is not sufficient.| The return air filter may be dirty.|
Clean the return air filter.
The outdoor unit may have an obstruction on the air inlet or outlet.| Ensure
the air inlet and air outlet on the outdoor unit is not blocked.
Check that the area around the outdoor unit is free from obstructions that may cause the airflow to recirculate.
The airflow across the indoor coil may be outside of the operating range.|
Reduce the total static pressure of the ductwork. For example increase duct
sizes, reduce tight duct work bends or increase return air grille size.
The heat load is greater than the installation design.| Perform a heat load
analysis on the conditioned space. Turn any unused zones to the off position.
Windows or doors are open.| Close windows and doors in conditioned areas.
The outside temperature is beyond the air conditioner design conditions.| When
the ambient temperature is expected to exceed the maximum design operating
temperature, turn the system on as early as possible.
The indoor fan setting may be set too low.| Change the fan speed to a higher
setting. This will increase system capacity.
Steam emitted from outdoor unit.| The outdoor unit is
going through a defrost cycle during the heating cycle.| This is normal during
the defrost operation in cold ambient conditions.
Condensation of water on the outdoor coil during heating operation.| This is
normal during heating operation. Optional drip trays can be purchased to drain
the excess water.
Set temperature cannot be adjusted.| The wall control set
temperature limits are being exceeded.| Check the upper and lower temperature
limits are set correctly.
Occasional hissing noise can be heard during the heating cycle.| This is
the sound of the gas changing direction as the system goes through a defrost
cycle.| This is a normal function of an air conditioner.
The compressor is operating but the system is not
cooling.| You are in heating mode.| Check the temperature settings.
The reversing valve has not switched between heating and cooling.| Test
reversing valve.
Remedies
Check the sensor resistance.
Jammed reversing valve.| Test the reversing valve operation.
Obstruction on the outdoor unit.| Remove obstructions.
Test the fan motor resistance.
Faulty capacitor.| Test the capacitor microfarad reading.
Faulty Outdoor PCB.| Test the PCB output voltage.
Adjust the set point less then or greater than 4oC of the indoor temperature
depending on mode of operation.
If this happens, we recommend you have the indoor unit washed by a technician.
Consult the installer from whom you purchased the air conditioner.
No P-Trap installed.| Re-pipe drain with a P-Trap.
Dry P-Trap.| Contact the installer to carry out a general service and
fill the P-Trap.
EC Fan Troubleshooting
FaultSequence of EventsPossible Causes4.Low airflow during AUTO Mode.System produces reduced airflow on Auto mode when all or minimum zones are on.System capacity has been designed to heat/cool only selected areas of the conditions space at any one time.5. Indoor fan not changing speeds when in Auto ModeWhen zones are switched on or off, airflow to active zones doesn’t increase or decrease.There is excessive static within the duct design of the active zones.6. HiS is displayed on the wall controller aftera Self-Learn has been preformed (L Series Controller only).System produces low airflow when AUTO mode is selected regardless of how many zones are open.HiS is displayed on the wall control as a indication of very high static in the connected return and supply duct which can further effect the supply air quantity during the auto mode. If there is too much static during self-learn, thenthe controller will automatically decrease the indoor fan speed until an acceptable static is achieved and the self-learn can be completed with reduced airflow.
Fault | Sequence of Events | Possible Causes | Remedies |
---|---|---|---|
1. Auto Mode is not available. | When scrolling through | ||
fan speeds, Auto Mode is not selectable. | During commissioning, Self-Learn | ||
mode was not activated. | Carry out self learn mode. Refer LR7/LC7/ NEO |
controller operation manual.
Self learn mode failed during commissioning.| Ensure that the air is balanced
correctly (static may be too high). Refer to Installation and Commissioning
Guide-Indoor.
2. Airflow hunting during Auto and Self Learn Mode.| Indoor fan will intermittently “huff”.| Excessive static in ductwork. Duct static has changed since performing a self-learn. Ducts deteriorate, dirty filter, change in duct layout.| Reduce static where possible.
See installation guidelines on duct installation.
Clean filter and re-perform self-learn.
3. Too much airflow when minimum zones are on.| Air is blowing too
much when set to minimum zones.| Fan not set to Auto Mode.| Change fan setting
to Auto Mode
Poor air balance.| Carry out air balance and install manual dampers as
required.
Minimum duct and outlet sizes requirements not followed.| Check Installation
and Commissioning Guide-Indoor and adjust / change if necessary.
Remedies
Operate indoor fan on Low/ Med/High speed to achieve more airflow.
Excessive static in ductwork.| Reduce static where possible. Review duct
design with reference to Installation and Commissioning Guide-Indoor.
Review duct design with reference to Installation and Commissioning Guide-
Indoor.
The indoor PCB is not changing the fan PWM to adjust the fan PWM to adjust
the fan speed.| Check the output PWM from indoor PCB. An increase in fan
speed should result in a increase in the fan % PWM (duty cycle). Refer to
table below test points expected voltages.
To determine if the system may be suffering from excessive or insufficient static, check PWM & RPM values through the indoor unit dashboard on the Master Wall Controller:
- If the RPM is at its maximum value, and the PWM has not reached its requested value, this indicates a high static. (Please refer to RPM Limits in Section 0.3)
- When switching off zones, and there is little or no change in the RPM value, this indicates insufficient static within remaining active zones duct work.
Reduce static where possible. Review duct design with reference to Installation and Commissioning Guide – Indoor .
Once static has been reduced perform Self-Learn again.
Indoor Fan PWM and RPM Limits Table
Advance R-410A (UNO Board)
Unit Model | PWM % (Approx) |
---|---|
Low | Medium |
EVV140S | 35 |
EVV160S | 42 |
EVV180S | 50 |
EVV210S | 43 |
EVV240S | 44 |
Unit Model
| RPM Limits
---|---
Low| Medium| High
EVV140S| 1150| 1290| 1390
EVV160S| 1150| 1290| 1390
EVV180S| 1150| 1290| 1390
EVV210S| 1150| 1350| 1500
EVV240S| 1150| 1350| 1500
Advance R-32 (UNO-Pro Board)
Unit Model | PWM % (Approx) |
---|---|
Low | Medium |
EVV13AS | 40 |
EVV15AS | 52 |
EVV17AS | 57 |
Unit Model
| RPM Limits
---|---
Low| Medium| High
EVV13AS| 1380| 1380| 1380
EVV15AS| 1380| 1380| 1380
EVV17AS| 1380| 1380| 1380
**** Component Troubleshooting
Testing Indoor Board
- Disconnect wires from the Wall Control Communication and Outdoor Communication plugs into indoor board
- Loop the “A” terminal from the Wall Control communication plug to the “A” terminal on the Outdoor Communication Plug
- Loop the “B” Terminal from the Wall Control communication plug to the “B” terminal on the Outdoor Communication Plug
- Power the board and if the WCCOM2 LED flashes and the OUTDOORCOM1 flashes then the indoor board is communicating.
Expected Control Voltage On Communication Line – InZone Board (R-410A /
R-32)
NOTES
- If COM1 (LED1) and COM2 (LED2) are blinking, communication is occurring.
-
- Voltage sending between A-G and B-G are fluctuating, this means communication is occurring.
- Prior to measuring the control voltage ensure communication wires are properly connected to the CPU board.
Expected Control Voltage On Communication Line – UNO Board Series
(R-410A)
Expected Control Voltage On Communication Line – UNO Pro Board (R-32)
Expected Voltage – InZone PCB To Indoor Fan
Step 1.
- Measure the Indoor Fan on/off signal.
On signal = 12VDC signal between Pin 1 and 3 (red and blue wires).
Off signal = +0VDC signal between Pin 1 and 3.
Step 2.
- Set the tester to measure duty cycle .
- Set the indoor fan to a fixed speed eg High & turn all zones on.
- Measure the reading between Pin 3 and 4 (blue and yellow wires).
- Change fan speed and check for any changes in readings.
- Compare the duty cycle output to the expected PWM for each model.
NOTE
Duty cycle cannot be tested in voltage. A voltage on the PWM line indicates a
Duty Cycle is present.
Compressor Winding Resistance
COMPRESSOR WINDINGS
SINGLE PHASE
| ****
Unit Model
| Compressor Part Number/Model| Rating Of Compressor Windings
**(Ω)*
---|---|---|---
U – V| V – W| U – W
R-410A| CRV140S| 1560-476| 0.338| ** 0.338| 0.338
CRV160S
CRV180S
CRV160T| 1560-474| 0.521| 0.521| 0.521
CRV180T
CRV210T| 1560-475| 0.610| 0.610| 0.610
CRV240T
R-32| CRV13AS| 1560-477| 0.345| 0.345| **** 0.345
CRV15AS
CRV17AS
CRV13AT| 1560-478| 0.658| 0.658| 0.658
CRV15AT
CRV17AT
*Resistance value at 25 oC ambient Temperature
Condenser Fan Winding Resistance
R-410A Models
Unit Model | Fan Part Number | Rating Of Fan Windings **(Ω)*** |
---|
CRV140S CRV160S CRV180S CRV160T CRV180T
| 2505-141| Black and Blue| 97
Blue and Brown| 143
Black and Brown| 240
Any colour and earth| Open circuit
CRV210T CRV240T| 2505-130| Brown and Black| 68.2
Brown and Blue| 38.6
Black and Blue| 30.1
Any colour and earth| Open circuit
Any colour and either Gray| Open circuit
*Resistance value at 25 oC ambient Temperature
R-32 Models
Control
Voltage
| Fan Data
Wire Colour
| Fan Data
Output
| PCB JST
XHP-6 Pin
---|---|---|---
–| White| Fan Feedback| 1
–| Red| +10VDC
Supply
| 2
2 – 10
VDC
| Yellow| 0 – 10
VDC
| 3
2 – 10
VDC
| Blue| 0V
Ground
| 4
–| –| –| 5
–| –| –| 6
1.5 – 10
VDC
| Yellow – Blue| UNO Pro to Fan|
Other Component Coil Resistances
Component Name | Resistance Value **(KΩ)*** |
---|---|
Reversing valve | 2.03 |
Crankcase Heater | 1.56 |
*Resistance value at 25 oC Ambient Temperature
EEV Resistance
Resistance Between Wires | Resistance Value **(Ω)*** |
---|---|
Orange – Grey | 46 ± 3 Ω |
Red – Grey | 46 ± 3 Ω |
Yellow – Grey | 46 ± 3 Ω |
Black – Grey | 46 ± 3 Ω |
*Resistance value at 20oC Ambient Temperature
Temperature-Resistance Table For Sensors
| Ambient/Outdoor Coil/ Indoor Coil/Suction Temperature Sensor|
Discharge Line Temperature Sensor
---|---|---
Temp (°C)| Resistance (KΩ)| Resistance (KΩ)
-20| 77.5| 1053.9
-19| 73.5| 992.1
-18| 69.7| 933.0
-17| 66.1| 878.0
-16| 62.8| 827.0
-15| 59.6| 779.6
-14| 56.6| 734.7
-13| 53.8| 693.2
-12| 51.2| 654.0
-11| 48.7| 617.1
-10| 46.3| 582.5
-9| 44.1| 550.6
-8| 42.0| 520.2
-7| 40.0| 491.8
-6| 38.1| 465.2
-5| 36.3| 440.4
-4| 34.6| 416.9
-3| 33.0| 394.8
-2| 31.5| 374.1
| Ambient/Outdoor Coil/ Indoor Coil/Suction Temperature Sensor|
Discharge Line Temperature Sensor
---|---|---
Temp (°C)| Resistance (KΩ)| Resistance (KΩ)
-1| 30.1| 354.7
0| 28.7| 336.4
1| 27.4| 319.0
2| 26.2| 302.7
3| 25.0| 287.3
4| 23.9| 273.0
5| 22.9| 259.2
6| 21.9| 246.4
7| 21.0| 234.3
8| 20.1| 222.8
9| 19.2| 212.0
10| 18.4| 201.8
11| 17.6| 192.1
12| 16.9| 183.0
13| 16.2| 174.3
14| 15.5| 166.1
15| 14.9| 158.4
16| 14.3| 151.1
17| 13.7| 144.1
18| 13.2| 137.5
19| 12.7| 131.3
20| 12.2| 125.4
21| 11.7| 119.7
22| 11.2| 114.4
23| 10.8| 109.4
24| 10.4| 104.6
25| 10.0| 100.0
26| 9.6| 95.7
27| 9.3| 91.6
28| 8.9| 87.6
29| 8.6| 83.9
30| 8.3| 80.4
31| 8.0| 77.0
32| 7.7| 73.8
33| 7.4| 70.7
34| 7.1| 67.8
35| 6.9| 65.1
| Ambient/Outdoor Coil/ Indoor Coil/Suction Temperature Sensor|
Discharge Line Temperature Sensor
---|---|---
Temp (°C)| Resistance (KΩ)| Resistance (KΩ)
36| 6.6| 62.4
37| 6.4| 59.9
38| 6.2| 57.5
39| 6.0| 55.2
40| 5.8| 53.0
41| 5.6| 50.9
42| 5.4| 48.9
43| 5.2| 47.0
44| 5.0| 45.2
45| 4.8| 43.5
46| 4.7| 41.8
47| 4.5| 40.2
48| 4.4| 38.7
49| 4.2| 37.3
50| 4.1| 35.9
51| 4.0| 34.6
52| 3.8| 33.3
53| 3.7| 32.1
54| 3.6| 30.9
55| 3.5| 29.8
56| 3.4| 28.7
57| 3.3| 27.7
58| 3.2| 26.7
59| 3.1| 25.8
60| 3.0| 24.9
61| 2.9| 24.0
62| 2.8| 23.2
63| 2.7| 22.4
64| 2.6| 21.6
65| 2.6| 20.9
66| 2.5| 20.2
67| 2.4| 19.5
68| 2.3| 18.8
69| 2.3| 18.2
70| 2.2| 17.6
71| 2.1| 17.0
72| 2.1| 16.5
73| 2.0| 15.9
74| 2.0| 15.4
75| 1.9| 14.9
76| 1.9| 14.4
| Ambient/Outdoor Coil/ Indoor Coil/Suction Temperature Sensor|
Discharge Line Temperature Sensor
---|---|---
Temp (°C)| Resistance (KΩ)| Resistance (KΩ)
77| 1.8| 14.0
78| 1.8| 13.5
79| 1.7| 13.1
80| 1.7| 12.7
81| 1.6| 12.3
82| 1.6| 11.9
83| 1.5| 11.6
84| 1.5| 11.2
85| 1.5| 10.9
86| 1.4| 10.5
87| 1.4| 10.2
88| 1.3| 9.9
89| 1.3| 9.6
90| 1.3| 9.3
91| 1.2| 9.1
92| 1.2| 8.8
93| 1.2| 8.5
94| 1.1| 8.3
95| 1.1| 8.1
96| 1.1| 7.8
97| 1.1| 7.6
98| 1.0| 7.4
99| 1.0| 7.2
100| 1.0| 7.0
101| 1.0| 6.8
102| 0.9| 6.6
103| 0.9| 6.4
104| 0.9| 6.2
105| 0.9| 6.1
106| 0.9| 5.9
107| 0.8| 5.7
108| 0.8| 5.6
109| 0.8| 5.4
110| 0.8| 5.3
111| 0.8| 5.2
112| 0.7| 5.0
113| 0.7| 4.9
114| 0.7| 4.8
115| 0.7| 4.6
116| 0.7| 4.5
117| 0.7| 4.4
| Ambient/Outdoor Coil/ Indoor Coil/Suction Temperature Sensor|
Discharge Line Temperature Sensor
---|---|---
Temp (°C)| Resistance (KΩ)| Resistance (KΩ)
118| 0.6| 4.3
119| 0.6| 4.2
120| 0.6| 4.1
Pressure-Voltage Table For Pressure Transducers
LR7-1 / LC7- 2| Outdoor Unit CPU| Category|
Function / Fault
---|---|---|---
–| Boot| Status| Unit is starting up
–| oFF| Status| Unit Off or Unit Turning Off (flashing)
COOL| CooL| Status| Unit Cooling Mode or Start Cooling (flashing)
HEAT| HEAt| Status| Unit Heating Mode or Start Heating (flashing)
Defrost Status| dEF| Status| Heating Mode – Defrost
Defrost Status| dEF3| Status| 3 min to Defrost
Defrost Status| dEF2| Status| 2 min to Defrost
Defrost Status| dEF1| Status| 1 min to Defrost
HEAT| HEAt| Status| Heating Mode – Indoor coil pre-heat after defrost
–| oiLr| Status| Oil Return Operation
Energy Saving| dr-1| Status| Demand Response Management 1
Energy Saving| dr-2| Status| Demand Response Management 2
Energy Saving| dr-3| Status| Demand Response Management 3
–| ohP| Status| Unit derating – Overheat Protection Mode
–| dtP| Status| Unit derating – Discharge Temperature Protection Mode
–| cPP| Status| Unit derating – Condenser Pressure Protection Mode
–| hSP| Status| Unit derating – High Suction Pressure Protection Mode
COOL & LOW blink 30s| Cool| Error| Anti Freeze Protection Mode
NOTE
When unit is powered up, “boot” will show in 7 segment display of outdoor
board for 30 seconds, followed by normal CPU status codes.
NEO
Wall
Controller
| LR7-1 /LC7-2
Wall
Controller
| Outdoor Unit CPU| Category / Source| ****
Function / Fault
---|---|---|---|---
E01| E01| E01| IDU| Indoor Fan RPM Feedback Error
E03| E03| E03| IDU| Indoor Room Temp. Sensor Error (Open or short circuit)
E04| E04| E04| IDU| Indoor Coil IN Temp. Sensor Error (open or short circuit)
E06| E06| E06| IDU| High Discharge Temp. (Discharge Temp exceeded 120°C)
E07| E07| E07| ODU| Outdoor Coil Temp. Sensor Error (Open or short circuit)
E08| E08| E08| ODU| Discharge Temp. Sensor Error (Open or short circuit)
E09| E09| E09| ODU| LP Switch Tripped
E10| E10| E10| ODU| LP Sensor Error (Open/short circuit)
E11| E11| E11| ODU| HP Switch Tripped
E12| E12| E12| ODU| HP Sensor Error (Open/short circuit)
E13*
| ****
E13*
| ****
E13*
| ****
ODU
| VSD HSP Connector (Jumper Pin Missing)
VSD Fault Signal
E15| E15| E15| ODU / VSD| Communication Error Between ODU to VSD
E18| E18| E18| ODU| Suction Temp. Sensor Error (Open/short circuit)
E22| E22| E22| ODU| Ambient Temp. Sensor Error (Open/short circuit)
E26| E26| E26| VSD| VSD Supply Over Current
E27| E27| E27| VSD| VSD Supply Over Voltage
E28| E28| E28| VSD| VSD Temperature High
E29| E29| E29| VSD| VSD Low Supply Voltage
E30| E30| E30| VSD| VSD Trip Lock
E41| E41| E41| VSD| VSD DC Link Voltage Low
E42| E42| E42| ODU| Envelope Protection Error
(Extreme Low Evaporating Pressure)
E43| E43| E43| ODU| Envelope Protection Error (High compression ratio)
E44| E44| E44| ODU| Envelope Protection Error (High condensing pressure)
E45| E45| E45| ODU| Envelope Protection Error (Low compression ratio)
E47| E47| E47| ODU| Compressor Torque Limit Error
E50| E50| E50| ODU| Outdoor Board Configuration Error
E51| E51| E51| IDU / ODU| Communication Error Between Outdoor to Indoor Unit
E52| E52| E52| CMI / ODU| Communication Error Between Indoor Unit to Wall
controller
E55| E55| E55| ODU| Communication Error Between BMS to ODU
E56| E56| E56| VSD| No Master Wall Controller Detected
E60| E60| E60| VSD| VSD Compressor Phase Over Current
E61| E61| E61| VSD| VSD Compressor Loss of Phase
E62| E62| E62| VSD| VSD DC Bus Over Voltage
NEO
Wall
Controller
| LR7-1 /LC7-2
Wall
Controller
| Outdoor Unit CPU| Category / Source|
Function / Fault
---|---|---|---|---
E63| E63| E63| VSD| VSD DC Bus Under Voltage
E64| E64| E64| VSD| VSD Compressor Loss of Rotor
E65| E65| E65| VSD| VSD Compressor U Phase Current Sensor Fault
E66| E66| E66| VSD| VSD AC Voltage Imbalance / AC Input Loss of Phase
E66| E66| E66| VSD| VSD Inverter De-saturation
E68| E68| E68| VSD| VSD Compressor V Phase Current Sensor Fault
E69| E69| E69| VSD| VSD PFC-IGBT Over Temp
E70| E70| E70| VSD| VSD Lost Rotor Position
E71| E71| E71| VSD| VSD Motor Temp Sensor Error
E72| E72| E72| VSD| VSD Precharge Relay Open
E73| E73| E73| VSD| VSD Compressor W Phase Current Sensor Fault
E74| E74| E74| VSD| VSD IGBT Over Current
E75| E75| E75| VSD| VSD Compressor Phase Current Fold Back Timeout
E76| E76| E76| VSD| VSD Power Module Temp. Fold Back Timeout
E77| E77| E77| VSD| VSD AC Input Current Fold Back Timeout
E78| E78| E78| VSD| VSD PFC-IGBT Temp. Low
E79| E79| E79| VSD| VSD IPM Desat Protection/Compressor HW Over Current
E80| E80| E80| VSD| VSD Motor Temp High
E81| E81| E81| VSD| VSD Board Temp High
E82| E82| E82| VSD| VSD Power Module Temp High
E83| E83| E83| VSD| VSD PFC-IGBT Temp High
E84| E84| E84| VSD| Communication Error in VSD Between DSP to PFC
E85| E85| E85| VSD| Communication Error in VSD Between Comms to DSP
E86| E86| E86| VSD| Compressor Phase Current Imbalance
E87| E87| E87| VSD| VSD 3 Phase PFC Current Imbalance
E88| E88| E88| VSD| VSD Micro Electronic or EEPROM Error
E89| E89| E89| VSD| VSD Motor Over Speed
E90| E90| E90| VSD| VSD Compressor Model Configuration Error
E91| E91| E91| VSD| VSD Inverter Temp Imbalance
E92| E92| E92| VSD| VSD PFC Temp Imbalance
E93| E93| E93| VSD| VSD Motor Temp Low
E94| E94| E94| VSD| VSD Board Temp Low
E95| E95| E95| VSD| VSD Power Module Temp Low or Sensor (Open or short
circuit)
E96| E96| E96| VSD| VSD PFC-IGBT Temp Low
E97| E97| E97| VSD| VSD Comms ADC Failure
- Applicable only for Advance R-410A (Uno Board), ** Applicable only for Advance R-32 (Uno Pro Board)
PFC: Power Factor Correction
DSP: Digital Signal Processor
IGBT: Insulated-Gate Bipolar Transistor
ADC: Analog to Digital Converter
Control Voltage | 5.0 ± 0.2 VDC |
---|---|
Output Voltage | 0.5 TO 4.5 VDC |
High Pressure Transducer | Low Pressure Transducer |
---|---|
Pressure (Kpa) | Output Voltage (VDC) |
Voltage (VDC)**
0| 0.5| 0| 0.5
125| 0.6| 50| 0.6
375| 0.8| 150| 0.8
625| 1| 250| 1
875| 1.2| 350| 1.2
1125| 1.4| 450| 1.4
1375| 1.6| 550| 1.6
1625| 1.8| 650| 1.8
1875| 2| 750| 2
2125| 2.2| 850| 2.2
2375| 2.4| 950| 2.4
2625| 2.6| 1050| 2.6
2875| 2.8| 1150| 2.8
3125| 3| 1250| 3
3375| 3.2| 1350| 3.2
3625| 3.4| 1450| 3.4
3875| 3.6| 1550| 3.6
4125| 3.8| 1650| 3.8
4375| 4| 1750| 4
4625| 4.2| 1850| 4.2
4875| 4.4| 1950| 4.4
5125| 4.6| 2050| 4.6
5375| 4.8| 2150| 4.8
5625| 5| 2250| 5
Fault and Status Codes
Status Codes
Fault Codes
Fault Code Troubleshooting
Fault Code | Description | Possible Causes | Remedies |
---|---|---|---|
E03 Indoor Room Temp. Sensor Error | E03 will be displayed on | ||
all connected wall controls every time the unit is switched on. | Faulty wall | ||
sensor or cable | Replace faulty sensor or cable | ||
E04 Indoor Coil In Temp. Sensor Error | No preheat on start up (heating | ||
mode only), indoor fan will come on straight away. | Indoor coil sensor is open | ||
or short circuit. | Replace indoor sensor |
After de-ice, indoor fan will start after 30 seconds.
E04 will be displayed every time it is switched on.
E06 High Discharge Temperature| The compressor discharge temperature
(Cdt) has exceeded 138˚C and the system has been stopped. When the temperature
has normalised to 80˚C or 8 minutes delay has been finished, the controller
will attempt to return to normal conditions.| Under charged with refrigerant.|
Check for refrigerant leaks and repair.
E07 Outdoor Coil Temp. Sensor Error| Outdoor fans will operate on high
speed only (while unit is running).| Outdoor coil sensor is open or short
circuit.| Replace outdoor coil sensor
E07 will be displayed every time the system is switched on.| Faulty sensor.|
Check the sensor resistance.
E08 Discharge Temp. Sensor Error| The reading of the discharge
temperature sensor (Cdt) is not within the specified sensor range of -60 °C to
+200°C.| Discharge temperature sensor is open or short circuit.| Replace
discharge temperature sensor.
Faulty sensor.| Check the sensor resistance.
Fault Code| Description| Possible Causes| Remedies
---|---|---|---
E09 LP Switch Tripped| Low Pressure Control will cut out the
system (i.e. stop the compressor and fans) if a pressure less than 165kPa is
detected. Compressor
stops for 5 minutes for the 1st and 2nd trip. If the low pressure switch trips out three times in a row, then the unit will remain off for 15 minutes before attempting to re-start. For the system to restart after a Low Pressure cut out, the pressure switch needs to detect a pressure greater than 330kPa.
| Insufficient airflow over indoor coil during cooling operation| Check indoor
fan operation to ensure sufficient airflow is flowing across the indoor coil.
Undercharged with refrigerant| Check for refrigerant leaks and repair.
Insufficient airflow over outdoor coil during heating operation| Check for
dirty outdoor coil and inspect outdoor fan operation.
Blockage in refrigeration system| Remove blockage from refrigeration system.
Dirty filter| Clean Filter.
E10 LP Sensor Error (open/short circuit)| The reading of the suction
pressure transducer is not within the specified sensor range.| Faulty wiring
or defective transducer.| Replace the transducer. Correct the wiring.
E11 HP Switch Tripped| High Pressure Control will cut out
the system (i.e. stop the compressor and fans) if a pressure greater than
4502kPa is detected. Compressor stops for 5 minutes for the 1st and 2nd trip.
If the high pressure switch trips out three times in a row, then the unit will
remain off for 15 minutes before attempting to re-start. For the system
to restart after a High Pressure cut out, the pressure switch needs to detect a pressure less than 3509kPa.
| Insufficient airflow over indoor coil during heating operation| Check indoor
fan operation to ensure sufficient airflow is flowing across the indoor coil
Overcharged with refrigerant| Check for refrigerant leaks and repair.
Insufficient airflow over outdoor coil during cooling operation| Check for
dirty outdoor coil and inspect outdoor fan operation
Blockage in refrigeration system| Remove blockage from refrigeration system
Dirty filter| Clean Filter
E12 HP Sensor Error (open/ short)| The reading of the condenser
pressure transmitter is not within the specified sensor range.| Faulty wiring
or defective transducer.| Replace the transducer. Correct the wiring
E13 VSD Fault Signal| E13 will be displayed on the ODB when
the VSD sends a fault signal to the ODB.| VSD overheating.| Ensure proper
airflow/ cooling over the drives heat- sink.
Incorrect supply voltage| Ensure line voltage is > 187 VAC. Check system for
lose connections or hot joints.
VSD HP loop open circuit| Ensure that the drives HP bypass in connected.
E15
Communication Error Between ODU to VSD
| No communication data received for 20 seconds.| Check modbus communication
cable connection.| Make the communication cable connection correct.
Power cycle the drive.
Fault Code| Description| Possible Causes| Remedies
---|---|---|---
E18 Suction Temp. Sensor Error (Open/short circuit)| The reading of
the suction temperature sensor (Sst) is not within the specified sensor
range.| Suction temperature sensor is open or short circuit.| Replace suction
temperature sensor.
Faulty sensor.| Check the sensor resistance.
E22 Ambient Temp. Sensor Error (Open/ short circuit)| The reading of the
ambient temperature sensor is not within the specified sensor range.| Ambient
temperature sensor is open or short circuit.| Replace ambient temperature
sensor.
Faulty sensor.| Check the sensor resistance.
E26 VSD Supply Over Current| The drive has encountered an
over current event and has stopped operation.| An over current can be
triggered by low voltage.| Rectify low voltage power supply.
Check if the compressor is operating within specified pressure limits.| Find
the root cause for not operating the compressor in the specified limits.
Faulty drive.| Replace drive if the problem still persists.
E27 VSD Supply Over Voltage| The drive has encountered an
over voltage event.| Measure the input voltage to the drive. It should not be
more than 575VAC.| Input voltage should be rated value range.
Check if the compressor is operating within specified pressure limits.| Find
the root cause for not operating the compressor in the specified limits.
E28 VSD
Temperature High
| The drive has encountered an over temperature condition and has stopped
operation.| Verify proper airflow over the heat-sink of the drive.| Remove any
obstructions.
Check if the compressor is operating within specified pressure limits.| Find
the root cause for not operating the compressor in the specified limits.
Check the mounting screws on the drive, If the problem, still persists replace
the drive.| Make sure they are tight.
E29 VSD Low
Supply Voltage
| The drive has encountered an under-voltage event.| Measure the input
voltage to the drive. It should not drop below 295VAC.| Input voltage should
be rated value range.
Check if the compressor is operating within specified pressure limits.| Find
the root cause for not operating the compressor in the specified limits.
E30 VSD Trip Lock| Certain faults have a trip limit| VCD Drive trips
lock because of multi errors. Refer to Ourdoor Board history to diagnose more
for related error code| Reset the power supply
E41 VSD DC Link
Voltage Low
| The drive has encountered an DC bus voltage low.| Check the AC power
supply.| Make correct supply voltage.
Check if the compressor is operating within specified pressure limits.| Find
the root cause for not operating the compressor in the specified limits or
restart the drive again.
Fault Code| Description| Possible Causes| Remedies
---|---|---|---
E42 and E45 Envelope Protection Error| As the compressor starts, it will
wait until the compressor envelope control start delay has expired. Once the
delay has expired, only then will the compressor start to track the floating
point which is defined by HP/LP saturation temperature with respect to the
selected compressor envelope (the compressor envelope has been divided in to the four parts
– Extreme low evaporating pressure, High compression ratio, High condensing pressure, Low compression ratio.
In the case of when the compressor operates outside the envelope boundaries, there is an allowable time of which the compressor may continue to operate – these time restrictions are tabulated below.
The compressor will turn off if the allowable time-out expires. After 180 seconds, the UNO controller will auto reset according to the respective error code and start again to user define mode.
System can trip on any of the four envelope protection error code:
| |
E42 : Unit will trip on this error code if compressor is running outside
the envelope boundary on extremely low evaporating pressure side for 20sec.|
Same as E09| Same as E09
E43: Unit will trip on this error code if compressor is running outside
the envelope boundary on high compression ratio side for 3sec.| Insufficient
airflow over indoor coil during heating operation| Check indoor fan operation
to ensure sufficient airflow is flowing across the indoor coil
Under or overcharged with refrigerant| Amend gas charge until charge is
correct
E44: Unit will trip on this error code if compressor is running outside
the envelope boundary on high condensing pressure side for 3sec.| Same as E11|
Same as E11
E45: Unit will trip on this error code if compressor is running outside
the envelope boundary on low compression ratio side for 90sec.| System may be
running outside the operating limits.| Make sure system should not be operated
outside the operating range.
Outdoor fan relay might be stuck on the high speed.| Replace the outdoor
board.
E47 Compressor Torque Limit Error| Motor torque has exceeded its
limits| Compressor running outside the operating limits.| Airflow across the
indoor or outdoor coil is not proper.
Overcharged with refrigerant.| Amend gas charge until charge is correct
Fault Code| Description| Possible Causes| Remedies
---|---|---|---
E50 Outdoor Board Configuration Error| UNO Board has not been
configured.| Outdoor board is not configured| Configured the outdoor board
correctly
E51
Communication Error Between ODU to VSD
| Communication between outdoor and indoor board.
Outdoor board has not been configured correctly.
| Faulty outdoor and indoor board or cable.
Outdoor board is not configured.
| Replace the faulty board. Configured the outdoor board correctly.
E52 Fault IDU – Wall Control
Communication Error
| Communication error between wall control and indoor board.| Faulty wall
controller or cable| Replace faulty wall controller or cable
Conflicting address with controller assignment or two controls have the same
assignment number| Re-assign controllers correctly
E55
Communication Error Between BMS to ODU
| ICUNO-MOD to Outdoor Board Communication Fault.| Faulty ICUNO-MOD| Replace
faulty ICUNO-MOD
Incorrect Control Mode set on Outdoor Board| Ensure correct control mode is
set
E56 No Master Wall Control Detected| No Master Wall Control (C-1) is
detected. System will lock out until a C-1 assignment is detected.| Master
Controller (C-1) Faulty| If an additional Wall Control (C-2 or C-3) is
available, remove the faulty Master controller and re-assign one of the
available controllers to C-1
Connected controller/s have not been assigned as C-1| Re-assign a connected
controller to C-1
E60 VSD
Compressor Phase Over Current
| Compressor Phase Over Current| Check the U/V/W connections on drive side.|
Make them correct.
Check the compressor motor windings
Check if the compressor is operating within specified pressure limits.| Find
the root cause for not operating the compressor in the specified limits.
Sensor on Drive not reading properly| Replace Drive
E62 VSD DC Bus
Over Voltage
| DC Bus Over Voltage| Check the DC bus voltage if it is > 800VDC.|
Check if the compressor is operating within specified pressure limits.| Find
the root cause for not operating the compressor in the specified limits.
E63 VSD DC Bus
Under Voltage
| DC Bus Under Voltage| Check the DC bus voltage if it is < 300VDC.|
Check if the compressor is operating within specified pressure limits.| Find
the root cause for not operating the compressor in the specified limits.
Fault Code| Description| Possible Causes| Remedies
---|---|---|---
E70 VSD Lost Rotor Position| Lost Rotor Position| Check the U/V/W
connections on drive side.| Make them correct.
Check the compressor motor windings|
Check if the compressor is operating within specified pressure limits.| Find
the root cause for not operating the compressor in the specified limits.
System over charge| Make it correct.
E71 VSD Motor Temp Sensor Error| AC Input Current Fold Back Timeout|
Check if the line voltage if it is < 187VAC|
Check if the compressor is operating within specified pressure limits.| Find
the root cause for not operating the compressor in the specified limits.
Faulty drive| Replace drive.
E76 VSD Power Module Temp. Fold Back Timeout| Power Module
Temp. Fold Back Timeout| Verify proper airflow over the heat-sink of the
drive.| Remove any obstructions.
Check if the compressor is operating within specified pressure limits.| Find
the root cause for not operating the compressor in the specified limits.
Check the mounting screws on the drive, If the problem, still persists replace
the drive.| Make sure they are tight.
E78 VSD
Auto Config Communication Timeout
| Auto Config Communication Fault Timeout. Baud rate or Parity of the system
controller not matching with drive.| Drive is not configured.| Replace the
drive
E82 VSD Power Module Temp High| Power Module Temp. High| Verify
proper airflow over the heat-sink of the drive.| Remove any obstructions.
Check if the compressor is operating within specified pressure limits.| Find
the root cause for not operating the compressor in the specified limits.
Check the mounting screws on the drive, If the problem, still persists replace
the drive.| Make sure they are tight.
E85
Communication Error in VSD Between Comms to DSP
| COM MCU and DSP Communication Lost| Check mod-bus communication cable
connections.| Refer wiring diagram & correct it.
Faulty drive| Replace the drive.
E86 Compressor Phase Current Imbalance| Compressor Phase Current
Imbalance| Check the U/V/W connections on drive side.| Make them correct.
Check the compressor motor windings|
Check if the compressor is operating within specified pressure limits.| Find
the root cause for not operating the compressor in the specified limits.
System over charge| Make it correct.
Fault Code| Description| Possible Causes| Remedies
---|---|---|---
E88 VSD Micro Electronic or EEPROM Error| Microelectronic
Fault / EEPROM fault. DSP self-check error.| Drive configure issue.| Restart
the drive and fault should go away.
Faulty drive.| Replace the drive.
E90 VSD
Compressor Model Configuration Error
| Compressor Model Configuration Error| Drive configuration issue.| Replace
the drive.
E95 VSD Power Module Temp Low or Sensor (Open or short circuit)|
Power Module Temp. Low or Sensor Open fault| Verify proper airflow over the
heat-sink of the drive.| Remove any obstructions.
Check if the compressor is operating within specified pressure limits.| Find
the root cause for not operating the compressor in the specified limits.
Check the mounting screws on the drive, If the problem, still persists replace
the drive.| Make sure they are tight.
©Copyright 2019 Actron Engineering Pty Limited ABN 34 002767240. ®Registered Trade Marks of Actron Engineering Pty Limited. ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Document: 9590-2015-03 Ver. 2 Issue Date: 11/2022
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>