ActronAir CL01-2W Control Interface Installation Guide
- June 4, 2024
- ActronAir
Table of Contents
WALL CONTROL
Installation Instructions
Control Interface Model Number
CL01-2W (White) CL01-2G (Grey)
AVAILABLE AS AN OPTIONAL ACCESSORY
FOR TRI-CAPACITY MODELS ONLY
CL01-2W Control Interface
IMPORTANT NOTE:
Please read this manual carefully before installing or operating your air
conditioning unit.
That’s better. That’s Actron.
Installation Guide
CL01-2 Control Interface
Safety Precautions
- Read all instructions in this manual before operating the air conditioning unit. Failure to do so may result in damage to the unit and void your warranty.
- Turn off the power supply to the unit and follow necessary Lock Out & Tag Out procedures to ensure that the power supply is not re-energized accidentally.
- This control interface has a power supply from the ActronAir CM100 controller via screwed terminals and twisted pair data cable. Ensure that this unit is not installed on voltages other than specified.
- Make sure that the unit installation complies with all relevant council regulations and building code standards. All electrical wiring must be in accordance with current electrical authority regulations and all wiring connections must follow the electrical diagrams provided.
- WH&S rules and regulations must be observed and will take precedence during the installation process.
- Only use this Control Interface with an ActronAir air conditioner as described in this installation guide.
Specifications
- Voltage: 12VDC +/- 10%
- Operating conditions: -10 to 60°C, < 90% RH non-condensing
- Storage conditions: -20 to 70° C, < 90% RH non-condensing
- Data: RS485 / 4 Core (2 Pair) Twisted Pair 7/0.20 (AWG24) Shielded Data Cable, Maximum Cable Length up to 200m
- Dimensions – mm: 130 x 130 x 14.5 (W x H x D)
NOTE
Do not use ActronAir 4 Core Data Cable Part Numbers: 4070-003 / AMDC4 or Non-
Twisted Pair multi-core cable.
Installation
1. Remove the front cover, as shown in the diagram below
- Insert and gently twist the screwdriver into the slot at the side of the Control Interface. Do this procedure alternately between the two slots until the front of the control separates from the back cover.
- Use a large enough flat blade screwdriver to fit into the slot in order to avoid damaging the Control Interface.
2. Remove the back cover, as shown in the diagram below
- Insert and gently twist the screwdriver into the slot at the top and the bottom of the Control Interface. Do this procedure alternately between the four slots until the back cover of the control separates.
- Use a large enough flat blade screwdriver to fit into the slot in order to avoid damaging the Control Interface.
3. Mount back cover to the wall
- Mount the back cover to the wall with screws via screw holes. If required, the use of a plasterboard mounting bracket is recommended to mount the back cover to the wall.
- Ensure that the Control Interface back cover is aligned and leveled on the wall before tightening the screws.
4. Connect wiring at the back of the Control Interface
- Ensure that all wiring is tightly connected. All wiring must be in accordance with the provided wiring diagram.
5. Attach PCB casing to the back cover
- Attach the PCB casing by aligning it with the back cover mounted on the wall.
- Ensure the PCB casing makes a ‘click’ sound after mounting.
NOTE
The front cover can be removed even after installation. Press at the bottom of
the control interface and pull the front cover.
6. Attach the front cover, as shown in the diagram below
IMPORTANT
Ensure protective film is removed from the inside of the front cover before
attaching.
- After attaching the front cover, check that the Control Interface is aligned and leveled on the wall.
Wiring Diagram
Important Notes for Return Air Temperature Sensor
-
SPLIT DUCTED UNITS (CAY/EVY or ELY)
Leave the factory-fitted Return Air Temperature Sensor in place. If disconnected, a fault will be registered and displayed on the screen. See the Split System Installation Guide, Air Temperature Setup for more details. -
PACKAGE UNITS (PKY)
You must connect the factory-supplied Return Air Temperature Sensor. If not connected, a fault will be registered and displayed on the screen. Please refer to the wiring diagram provided with your unit. See the Split System Installation Guide, Air Temperature Setup for more details. -
Follow the steps for assigning sensors, below, for the weighting of influence for both the return air temperature sensor and the built-in CL01-2 sensor. Note that the Control Interface displays shown below are for Split Ducted Units, these are for illustration purposes only. Displays for Package Units are without Use INDOOR sensor parameter.
Assigning Sensor
The CL01-2 Control Interface built-in sensor can be used to read your room temperature in combination with the return air temperature sensor. This can be assigned via the Service menu, as follows:
Service Menu f. Service settings c. Thermoregulation Thermoregulation 02
Display Progression:
NOTE
Thermoregulation is under the Service settings sub-level menu and password
protected, enter the Service Password (7378) in order to access this sub-menu.
From Thermoregulation 02 sub-level menu, you have the option to use 0% up to
100% CL01-2 sensor reading as follows:
* Legend:
Room Temp. = Return Air Temp Sensor Reading
Wall Cont Temp. = CL01-2 Built-In Sensor Reading
NOTE
The Control Value is determined by the following example:
Control Value calculation at Probe weight value of 50% :
Control Value = 50% Room Temp + 50% Wall Cont Temp
= (0.5 x 18.0) + (0.5 x 26.8)
= 9.0 + 13.4
= 22.4°C (Displayed on CL01-2 as INSIDE temperature when the button is
pressed)
Important Note For Split Ducted Tri-Capacity Models:
By default, the Return Air Temperature Sensor is connected to the Indoor
Board. As an option, this can be wired to the Outdoor Board which will require
changing the sensor setting from INDOOR sensor to OUTDOOR sensor via
Thermoregulation Gfc2, as shown on the right.
Installation Guide – CL01-2 Control Interface Insert
Document: 9590-3026 Ver. 2 220907 That ’s better. That’s Actron.
actronair.com.au
1300 522 722
©Copyright 2019 Actron Engineering Pty Limited ABN 34 002767240. ®Registered
Trade Marks of Actron Engineering Pty Limited.
ActronAir is constantly seeking ways to improve the design of its products,
therefore specifications are subject to change without notice.
Document: 9590-3026 Ver. 2 Issue Date: 09/2022
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>