signify IS-TM01 TruGroove Suspended Micro Instruction Manual

June 17, 2024
signify

signify logo Architectural Linear
IS-TM01 Suspended Direct
TruGroove suspended micro

System Overview

These instructions review how to install TruGroove suspended micro fixtures. Modules can be installed as individual 2ft, 2.5ft, 3ft, 3.5ft, 4ft, 5ft, 6ft, or 8ft standalone units, or they can be joined together to create continuous runs and patterns. The diagram below shows the components required to install a typical run of TruGroove suspended micro fixtures.

IMPORTANT: Read all instructions including fixture/sensor wiring AND mechanical details before beginning installation.

signify IS-TM01 TruGroove Suspended Micro - System
Overview

Module Lengths
TruGroove suspended micro fixtures come in the module lengths shown below. Add 0.25” for each endcap for accurate run length.signify IS-TM01 TruGroove
Suspended Micro - Housing Length

Length without endcaps feet 2.0 2.5 3.0 3.5 4.0 5.0 6.0 8.0
Inches 24.0 30.0 36.0 42.0 48.0 60.0 72.0 96.0
mm 610 762 914 1067 1219 1524 1829 2438

Mount Spacing
Fixture modules are designed for exact on-grid mounting. For non-accessible ceilings or in tile installations, mounts are adjustable within 1” of each module end.

TOOLS REQUIRED:

  • 2 Phillips screwdriver

  • 3/8” nut driver
  • Medium flat or #2 robertson screwdriver
  • Heyco PN0019(R12) crimping tool
  • Small ratchet and 1/4” socket

ATTENTION: Install in accordance with local and national building and electric codes.

Direct Installation Instructions

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interreference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

Warning! Shock Hazard!
IMPORTANT: Disconnect or turn off power before attempting any installation, service or maintenance.


Warning! Shock Hazard!
Fixture must be connected to building ground via the provided ground wire before re-connecting to mains power supply.

Power Label Location
For D/I symmetric and asymmetric fixtures, power labels can be found on light engine pans or under end louver modules.
For Direct and Surface symmetric and asymmetric fixtures, power labels can be found on upper pan.

Mounting & Power Locationsignify IS-TM01 TruGroove Suspended Micro -
Mounting & Power Location

Caution: To ensure a safe install, The variable aircraft cable mounting point must be located within 12” of the fixture end.

Installation Notes
Arrange boxed fixtures on floor in specified mounting locations, based on supplied layout drawings. Remove fixtures from boxes.
Install all ceiling mounting components and vertical aircraft cables using separate installation instruction for Aircraft Cable Mounting (supplied).

ATTENTION: Install in accordance with local and national building and electric codes.

IS-TM01
Direct Installation Instructions

Lens Removal

signify IS-TM01 TruGroove Suspended Micro - Lens
Removal

Lens Removal: To remove snap-in lens for maintenance purposes, insert a flat, smooth edged object between lens and housing (avoid screwdrivers). Twist to release pressure and remove lens. Note: Drop Lens is shipped separately

signify IS-TM01 TruGroove Suspended Micro - Symmetric
Fixture

Remove lens from fixture and set aside until fixture installation is complete. Use cotton gloves to handle lenses and keep in a clean environment.
Note: Optional Drop Lens is shipped separately.

signify IS-TM01 TruGroove Suspended Micro - Asymmetric
FixtureRemove lens and set aside until fixture installation is complete. Use cotton gloves to handle lenses and keep in a clean environment.
Remove the 2 screws securing the lower light engine and temporarily support light engine in position below fixture.
DO NOT ALLOW LIGHT ENGINE TO HANG FROM ELECTRICAL WIRES.
Save screws for re-installation later.

Installation Preparation

signify IS-TM01 TruGroove Suspended Micro - Fixture with
Louvers

Remove one louver from end of fixture by pulling gently and temporarily suspend from available holes.
Remaining louvers can be pushed to center for better access.

signify IS-TM01 TruGroove Suspended Micro - Fixture with Louvers
2

DO NOT ALLOW LOUVER TO HANG FROM ELECTRICAL WIRES.
For louver-lens combinations, remove both louver and lens. Use cotton gloves to handle lenses and keep in a clean environment.

signify IS-TM01 TruGroove Suspended Micro - Sling Mount
Installation

With module 1 on the ground, slide sling cable assembly into top fixture screw chase on both ends of the fixture.

ATTENTION: Install in accordance with local and national building and electric codes.

signify IS-TM01 TruGroove Suspended Micro - Fixture
Preparation

Attach two push pins to screw chases to secure sling cable assembly inside fixture during installation process. Gently tap each push pin into the housing leaving a 1/16” gap for easier removal later.

signify IS-TM01 TruGroove Suspended Micro - Fixture
InstallationRaise fixture to installed level and insert suspension cable inside sling cable assembly. Ensure end of aircraft cable exits from sling cable assembly as shown.signify IS-TM01
TruGroove Suspended Micro - Fixture LevellingEnsure module 1 is installed level. Do not install at an angle.

Important: Modules must be level relative to each other when joining of sections is required
IMPORTANT: LEVELING INSTRUCTIONS
For side to side leveling, loosen adjustment screw at bottom of cable gripper and slide slowly until level. When complete, re-tighten levelling screw by hand.
For vertical leveling, support bottom of fixture, press plunger on top of cable gripper and slowly lift/lower fixture to desired position. Release plunger when complete. Ensure fixture is secure before removing support.

signify IS-TM01 TruGroove Suspended Micro - Power Cord
Installation

Determine power feed location and break ½” electrical knockout at required end. Install ½” bushing from above fixture as shown. Feed power cord from above into fixture wiring cavity.

signify IS-TM01 TruGroove Suspended Micro - Power Cord Installation
2

Install and crimp provided cable metal strain relief bushing to secure power cord below fixture reflector. Use a Heyco PN0019(R12) crimping tool to ensure proper installation. If installing a standalone fixture, skip to step 13.

signify IS-TM01 TruGroove Suspended Micro - Fixture
Joining

With module 2 on the ground, tap small joiner aligners inside top screw chase. Insert larger joiner aligners inside lower screw chase as shown.
IMPORTANT: To allow for proper joining, ensure each center aligner tab is fully inserted inside module 2 housing, about ¼” past the middle point.

ATTENTION: Install in accordance with local and national building and electric codes.

signify IS-TM01 TruGroove Suspended Micro - Fixture Joining
2

Raise module 2 to installed module 1 position. Install and secure sling cable assembly of module 2 and at opposite. Remove push pins from module 1.

IMPORTANT: WIRING INSTRUCTIONS
Quick wire connectors (supplied) are used for through wiring connections between fixtures. Wire nuts (by others) are used for connection of power drops wiring to fixture wiring.

signify IS-TM01 TruGroove Suspended Micro - Fixture Joining
3

Bring modules close together, support module 2, complete wiring connections and tuck wires inside fixture wiring cavity. Engage joiner aligners from module 2 inside module 1.

signify IS-TM01 TruGroove Suspended Micro - Fixture Joining
4

Ensure all connections are secure and all wires are fully tucked inside fixture wiring cavity. Slide fixture modules together gently. Level fixtures.

FIXT = FIXTURE MODULE

signify IS-TM01 TruGroove Suspended Micro - Fixture Joining
5

Secure fixture modules together using the two #10-32 machine screws and the two self-locking #10-32 nuts supplied. Tighten until joint seam is tight.
IMPORTANT: Do not overtighten.

signify IS-TM01 TruGroove Suspended Micro - Endcap with
Sensor

Before installing the endcap, slide the sensor towards the center of the fixture to gain access. Proceed with endcap installation, step 14.

signify IS-TM01 TruGroove Suspended Micro - Drop Lens endcap
Installation

Place drop lens endcap as shown over the emboss of endcap and proceed with endcap Installation of endcap, step 14.

signify IS-TM01 TruGroove Suspended Micro - Endcap
Installation

Slide endcap onto end of fixture module and secure from below using two #8-32 X 3/8” screws. Ensure excess aircraft cable does not interfere with endcap attachment. Use ratchet to tighten screws until endcap seam is tight.
IMPORTANT: Do not overtighten.

Trim ½” bushing as shown

signify IS-TM01 TruGroove Suspended Micro - Corner
Installation

If a corner is required, it is recommended the corner module be installed first. All corners come with a factory installed cable sling assembly in the middle.

signify IS-TM01 TruGroove Suspended Micro - Closed Pattern
Installation

If installing a square or rectangular closed pattern, it is recommended to install opposite U-shaped fixture/corner patterns first and complete the installation by bringing U-shaped sections together as shown.

Reinstall the lower led pans with the screws provided. Ensure direction of light is as shown on layout drawings.

Installation Tip: For easier installation, start on one end of the louver pressing gently on side tabs.
IMPORTANT: For asymmetric louver fixtures, orientate the arrows on the louver pan to point at the label on the outside of the housing.

signify IS-TM01 TruGroove Suspended Micro - asymmetric

ATTENTION: Install in accordance with local and national building and electric codes.

Install lenses removed in step 1. Installation Tip: For easier installation, start at a housing end or a joint by placing lens at an angle and squeezing in slightly from the other side to guide inside housing.

Once lens is positioned inside housing, starting on one end or joint, push upwards gently and work outward to complete the run.
Note: Flush lens and drop lens are installed the same way. Flush lens is shown for reference.

Installation filler plate before installing louvers. Tip: For easier installation, start by squeezing filler plate in slightly from both sides and guiding inside housing.

Installation Tip: For easier installation, start on one end of the louver pressing gently on side tabs.

Installation Tip: For easier installation of corner lenses, start at the corner and work outward to complete the run. Follow steps 19 and 20.

24. Finishing

  • Ensure all fixtures and corners are level and in line with each other.
  • Trim excess vertical aircraft cable installed in step 4.
  • If horizontal leveling is required, loosen adjustment screw shown in step 4, level fixture and re-tighten screw.
  • Check that all joint or endcap screws are installed, and all seams are tight.
  • Use spare 1/2” plug(s) provided to close any open 1/2” electrical knockout location(s) in top pan.

PRF/PRA Interact Pro Foundation/Advance Install & Setup
*not for Enterprise or Signify Commissioned projects
To configure a lighting system with Interact sensors or RF nodes;

  • Ensure the luminaires are installed and powered on.
  • Download the Interact Pro app from either Apple’s App Store (for iOS) or Google’s Play Store.

signify IS-TM01 TruGroove Suspended Micro - App
downloade

|
---|---
https://play.google.com/store/apps/details?id=com.philips.li.c4m &hl=nl| https://itunes.apple.com/nl/app/interact- pro/id1353793570?mt=8

  • Register by tapping Request access on the login screen in the app.
  • Click or scan the QR codes below to view instructions for setup.

Interact Pro Foundation
Quick Start Guidesignify IS-TM01 TruGroove Suspended Micro - qr code
3| Interact Pro Advanced
Quick Start Guide
---|---
https://sme.interact-lighting.com/web/help/prf-pra/2.3/quick- start/quickstart_foundation.html| https://sme .interact-lighting.com/web/help/prf-pra/2.3/quick- start/quickstart_advanced.html
Interact Pro Documentation| Interact Pro Setup Videosignify IS-
TM01 TruGroove Suspended Micro - qr code 6
https://sme.interact-lighting.com/web/help/prf-pra/2.3/quick- start/quickstart_foundation.html| https://www.youtube.com/playlist?list=PLik6Wr9jZkR6zuAbSDI4rRn8WpZ6M0aST
Contact Us 1-800-555-0050signify
IS-TM01 TruGroove Suspended Micro - qr code 7
https://www.usa.lighting.philips.com/support/connect/contact- us

ATTENTION: Install in accordance with local and national building and electric codes.

Sensors in Rows

Single Sensor Controlling Whole Row

  1. Purple & brown (or purple & grey/pink) control wires MUST be connected between fixtures.
    Note:
    • A maximum of 8 drivers can be wired to one sensor; confirm fixture driver count with factory.signify IS-TM01 TruGroove Suspended Micro - Sensors in
Rows 1 Multiple Sensors Controlling Separate Zones in a Row

  2. Purple & brown (or purple & grey/pink) control wires MUST NOT be connected between zones.
    Notes:
    • A maximum of 8 drivers can be wired to one sensor; confirm fixture driver count with factory.
    • Only one sensor is allowed on a wired zone. (Sensors can be paired together wirelessly via a mobile app).signify IS-TM01 TruGroove Suspended Micro -
Sensors in Rows 2

Sensor Spacing

  • For correct operation, sensors should be placed a minimum distance of 8ft apart.
  • Wireless sensors should be placed no further than 40ft apart for good wireless signal connection.

signify IS-TM01 TruGroove Suspended Micro - Sensors in Rows
3

Important Consideration When Using Sensors in a Row

  • For fixtures with wireless sensors (CS, SB or RA options):
    DO NOT connect fixture purple & brown (or purple & grey/pink) control wires to an external dimming switch.
    Fixture mains wiring should not be connected to a circuit with an external on/off switch.
    Remote Sensor

  • For best aesthetic condition, place sensors at ends of row only so as not to break the continuous lens.

  • For better occupancy coverage in longer rows, sensors may be placed mid run, but keep in mind this will break the continuous lens into discrete sections. Alternatively, remote sensor may be used, note the same wiring rules will apply.

ATTENTION: Install in accordance with national and local building and electrical codes.

Occupancy Sensor Coverage:

Note: Longer dimension of detection area (Y1, Y2) is parallel to longer dimension of the luminaire.

signify IS-TM01 TruGroove Suspended Micro - Occupancy Sensor
Coverage

Daylight sensor
The light sensor measures the total amount of light in a circular field of approximately 80% of the PIR  detection area. The following aspects should be observed during installation:

  • Minimum distance from the window ≥2ft (0.6m).
  • Prevent light reflections from outside entering the sensor (for example sunlight reflection on a car hood) as this will lead to incorrect light regulation.

As a guideline the formula 0.72 x H can be used to calculate the minimum distance between the window and sensor whereby H is the height from the bottom of the window to the sensor.

signify IS-TM01 TruGroove Suspended Micro - Daylight
sensor

The detection area for the movement sensor can be roughly divided into two parts:

  • Minor movement (person moving ≤3ft/s or 0.9m/s).
  • Major movement (person moving ≥3ft/s or 0.9m/s).

Photosensor spatial response

signify IS-TM01 TruGroove Suspended Micro - Photosensor spatial
response

ATTENTION: Install in accordance with local and national building and electric codes.

© 2021 Signify Holding. All rights reserved. The information provided herein is subject to change, without notice. Signify does not give any representation or warranty as to the accuracy or completeness of the information included herein and shall not be liable for any action in reliance thereon. The information presented in this document is not intended as any commercial offer and does not form part of any quotation or contract, unless otherwise agreed by Signify.

Signify North America Corporation
400 Crossing Blvd, Suite 600
Bridgewater, NJ 08807
Telephone: 855-486-2216

Signify Canada Ltd.
281 Hillmount Road,
Markham, ON, Canada L6C 283
Telephone: 800-668-9008

All trademarks are owned by Signify Holding or their respective owners.

11/21/2023
www.ledalite.com
RevE
www.signify.comsignify logo
2

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals