CyberPower UT1500 Backup UPS Systems User Manual
- June 17, 2024
- CyberPower
Table of Contents
CyberPower UT1500 Backup UPS Systems
SAFETY INSTRUCTIONS
(SAVE THESE INSTRUCTIONS)
- This manual contains important safety instructions. Please read and follow all instructions carefully during the installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS.
- CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity-controlled indoor area free of conductive contaminants. (See the specifications for the acceptable temperature and humidity range.)
- CAUTION! To reduce the risk of overheating the UPS, do not cover the UPS’ cooling vents and avoid exposing the unit to direct sunlight or installing the unit near heat-emitting appliances such as space heaters or furnaces.
- CAUTION! Do not attach non-computer-related items, such as medical equipment, life-support equipment, microwave ovens, or vacuum cleaners to UPS.
- CAUTION! Do not plug the UPS input into its output.
- CAUTION! Do not allow liquids or any foreign object to enter the UPS. Do not place beverages or any other liquid-containing vessels on or near the unit.
- CAUTION! In the event of an emergency, press the OFF button and disconnect the power cord from the AC power supply to properly disable the UPS.
- CAUTION! Do not attach a power strip or surge suppressor to the UPS.
- CAUTION! Unplug the UPS before cleaning and do not use liquid or spray detergent.
- CAUTION! Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions.
- Keep unauthorized personnel away from batteries.
- CAUTION! The battery supply should be therefore disconnected in the plus and minus poles at the quick connectors of the battery when maintenance or service work inside the UPS is necessary.
- CAUTION! The internal battery voltage is 12Vdc. Sealed, lead-acid, 6-cell battery.
- CAUTION! When replacing the batteries, use the same number and type of batteries.
- CAUTION! Do not dispose of batteries in a fire. The battery may explode. Do not open or mutilate the battery or batteries. Released electrolytes are harmful to the skin and eyes.
INSTALLING YOUR UPS SYSTEM
UNPACKING
The box should contain the following:
- UT1500/2200E-IN: (1) UPS Unit x1; (2) USB Cable x 1; (3) Warranty Card x 1; (4)User Manual x 1 UT1500/2200E-AS: (1) UPS Unit x1; (2) USB Cable x 1; (3)User Manual x 1
- PowerPanel® Personal Edition software is available on our website. Please visit www.cyberpower.com and go to the Software Section for free download.
OVERVIEW
- The UT1500/2200E series provides automatic voltage regulation for inconsistent utility power and provides battery backup during power outages.
- The UT1500/2200E series ensures consistent power to your computer system.
HARDWARE INSTALLATION GUIDE
- Your new UPS may be used immediately upon receipt.
- However, recharging the battery for at least 8 hours is recommended to ensure that the battery’s maximum charge capacity is achieved.
- Charge loss may occur during shipping and storage.
- To recharge the battery, simply leave the unit plugged into an AC outlet.
- The unit will charge in both the on and off position.
- With the UPS unit off and unplugged, connect the computer, monitor, and any externally powered data storage device (Zip drive, Jazz drive, Tape drive, etc. into the battery power supplied outlets. DO NOT plug a laser printer, copier, space heater, vacuum, paper shredder, or other large electrical device into the battery power-supplied outlets. The power demands of these devices will overload and possibly damage the unit.
- Plug the UPS into a 2-pole, 3-wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air conditioner, refrigerator, copier, etc. Avoid using extension cords.
- Press the power switch to turn the unit on. The power on the indicator light will illuminate and the unit will “beep”.
- If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at least one piece of equipment from the battery power-supplied outlets. Wait 10 seconds. Make sure the circuit breaker/fuse is normal and then turn the UPS on.
- To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
- To store your UPS for an extended period, cover it and store it with the battery fully charged. Recharge the battery every three months to ensure battery life.
BASIC OPERATION
Front panel
- Power Switch
- Press the switch for 2 seconds to turn the UPS ON or OFF.
- Led Indicators
- This LED is illuminated when the UPS is working.
- Battery Capability Led Indicators
- Indicate the battery capability from the bottom up
Back panel
- USB Port to PC
- This port allows connection and communication from the USB port on the computer to the UPS unit. The UPS communicates its status to the PowerPanel® Personal Edition software.
- Communication Protection Ports
- Communication protection ports will protect any standard modem, fax, telephone line, or network cable
- Input Circuit Breaker
- The circuit breaker provides optimal overload protection.
- Input power cord
- Connect to utility power.
- Battery Backup & Surge Protected Outlets
- Provide battery backup and surge protection. They ensure power is provided to connected equipment over a while during a power failure.
TECHNICAL SPECIFICATIONS
Model| UT1500E| UT1500EI| UT1500E| UT1500E| UT2200E| UT2200EI| UT2200E|
UT2200E
---|---|---|---|---|---|---|---|---
Capacity (VA)| 1500| 2200
Watt (W)| 900| 1320
Input
Voltage Range| 165~290Vac
Nominal Frequency| 50 Hz
Output
On Battery Output Voltage| Simulated Sine Wave at 230Vac +/-5%
On Battery Output Frequency| 50 Hz +/-1%
Overload Protection| Breaker / Fuse
Physical
Total # of UPS Receptacles| 4 SCHOKO| 6 IEC| 4 ASIAN| 4
INDIA| 4 SCHOKO| 6 IEC| 4 ASIAN| 4 INDIA
Dimensions (W x H x D)(mm)| ** 148 X 178 X 298
Weight (kg)| 9.1 kg| 10.8 kg
Battery
Sealed Maintenance Free Lead Acid Battery| ** RBP0089 x2| ** RBP0090 x2
Typical Recharge Time| 8 Hours
Warning Diagnostics
Indicators| Power On / Using Battery
Audible Alarms| On Battery, Low Battery, Overload, Fault
Surge Protection
Network/ Phone/ Fax/ Modem Protection| ** YES
Communication
PowerPanel® Personal Edition Software| ** Windows 8/7/Vista/XP/2000, Server
2012/2008/2003, Linux
Environmental
Operating Temperature| 0°C to 40°C
Operating Relative Humidity| ** 0 to 90%
Management
Auto-Charger| Yes
Auto-Restart| Yes
DEFINITIONS FOR ILLUMINATED LED INDICATORS
LED | Alarm | Condition |
---|---|---|
On | Off | Normal |
Flash | Beep Twice | Utility Failure – The UPS is providing battery power to |
outlets.
Flash| Rapid Beeping| Utility Failure – The UPS is providing battery power.
The rapid beeps indicate the battery will run out of power shortly.
On/Flash| Constant Tone| Overload – Occurs when connected equipment exceeds
the rating of the unit. Turn the UPS off and unplug at least one piece of
equipment from the UPS.
TROUBLESHOOTING
Problem | Possible Cause | Solution |
---|---|---|
The UPS does not perform the expected runtime. | Batteries are not fully | |
charged. | Recharge the battery by leaving the UPS plugged in. | |
The battery is slightly worn out. | Contact CyberPower Systems Technical |
Support.
The UPS will not turn on.| The unit is not connected to an AC outlet.| The
unit must be connected to a 220-240V outlet.
The battery is worn out.| Contact CyberPower Systems Technical Support.
Mechanical problem.| Contact CyberPower Systems Technical Support.
Outlets do not provide power to equipment| The fuse is blown or the breaker is
tripped due to overload.| Turn the UPS off and unplug at least one piece of
connected equipment. Unplug the power cord of the UPS then replace the blown
fuse with a spare one or press the circuit breaker knob. Connect the power
cord then turn the UPS on. Make sure that your spare fuse meets the
specifications.
Batteries are discharged| Allow the unit to recharge for at least 4 hours.
The unit has been damaged by a surge or spike.| Contact CyberPower Systems
Technical Support.
- For more information, visitwww.cyberpower.com
- All rights reserved. Reproduction without permission is prohibited.