CyberPower CP900AVRa Replacement Batteries Instructions
- June 1, 2024
- CyberPower
Table of Contents
CP900AVRa Replacement Batteries
“`html
Product Information:
Specifications:
-
Models: CP900AVRa, CP1200AVRa, CP1350AVRLCDa, CP1500AVRTa,
LX1100G, LX1325GU, LX1500GU, CST135XLU, CST150XLU -
Intelligent LCD Series, AVR Series
-
Standby Series Models: CP600LCD, CP825LCD, CP800AVR,
CP685AVR-G, RT650, RT650EI, CP825AVR-G, CP685AVRLCD-G,
CP825AVRLCD-G, AVRG750U, AVRG900U, AVRG750LCD, AVRG900LCD
Product Usage Instructions:
Battery Replacement Instructions:
CyberPower encourages environmentally sound methods for disposal
and recycling of its UPS and batteries. Please dispose of and/or
recycle your UPS and batteries in accordance with the local
regulations of your state.
Important Safety Instructions:
Read and follow the important safety instructions before
servicing the batteries. Visit CyberPower official website
www.cyberpower.com or contact your dealer for more information on
battery replacement.
CAUTION! Use only the specified CyberPower
replacement battery or battery pack. Do not dispose of batteries in
a fire as they may explode. Do not open or mutilate batteries as
released material can be harmful to the skin and eyes.
Before replacing the battery, take the following
precautions:
- Remove watches, rings, or other metal objects.
- Use tools with insulated handles.
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Determine if the battery is inadvertently grounded and remove
the source from ground if so.
Battery Replacement Steps for Different Models:
For Models CP600LCD, CP825LCD, CP800AVR, CP685AVR-G, RT650,
RT650EI, CP825AVR-G, CP685AVRLCD-G, CP825AVRLCD-G, AVRG750U,
AVRG900U, AVRG750LCD, AVRG900LCD:
-
Place the UPS on its top and remove the retaining screw.
-
Slide the battery compartment cover completely off the
unit. -
Remove the battery from the compartment and disconnect the
battery wires. Install the replacement battery by connecting the
red wire to the positive terminal and the black wire to the
negative terminal of the battery. -
Slide back the battery compartment cover and tighten the
retaining screw.
For Models CP850AVRLCD, CP1000AVRLCD:
-
Place the UPS on its side and remove the retaining screw.
-
Slide the battery compartment cover completely off the
unit. -
Remove the battery from the compartment and disconnect the
battery wires. Install the replacement battery by connecting the
red wire and black wire to the positive and negative terminal of
the battery. Put the battery back into the compartment. -
Slide back the battery compartment cover and tighten the
retaining screw. Charge the unit for 8 hours to ensure expected
runtimes.
For Models CP850AVRLCD, CP1000AVRLCD:
-
Place the UPS on its side and locate the battery compartment
cover on the bottom of the UPS. Remove the retaining screws and
pull off the battery compartment cover. -
Remove the battery from the compartment and disconnect the
battery wires. Install the replacement batteries by connecting the
red wire and black wire to the same color wires from the battery
pack. Put the battery pack into the compartment.
FAQs:
Q: Can I use non-CyberPower replacement batteries?
A: It is recommended to use only specified CyberPower
replacement batteries or packs to ensure proper function and
safety.
“`
Battery Replacement Instructions
CyberPower encourages environmentally sound methods for disposal and recycling of its UPS and batteries. Please dispose of and/or recycle your UPS and batteries in accordance to the local regulations of your state.
MODEL: CP900AVRa, CP1200AVRa, CP1350AVRLCDa,
CP1500AVRTa, LX1100G, LX1325GU, LX1500GU,
CST135XLU, CST150XLU
1
2
IMPORTANT SAFETY INSTRUCTIONS
Read and follow the important safety instructions before servicing the
batteries. Visit CyberPower o~cial website www.cyberpower.com or contact your
dealer for more information on battery replacement.
CAUTION! Use only the specified CyberPower replacement battery, or battery
pack. CAUTION! Do not dispose of batteries in a fire. The batteries may
explode. CAUTION! Do not open or mutilate batteries. Released material is
harmful to the skin and eyes. It may be toxic.
Take the following precautions before replacing the battery: 1. Remove
watches, rings, or other metal objects. 2. Use tools with insulated handles.
3. Wear rubber gloves and boots. 4. Do not lay tools or metal parts on top of
batteries. 5. Determine if battery is inadvertently grounded. If
inadvertently grounded, remove source from ground. CONTACT WITH ANY PART OF A
GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK. The likelihood of such shock
can be reduced if such grounds are removed during installation and maintenance
(applicable to equipment and remote battery supplies not having a grounded
supply circuit).
Intelligent LCD Series, AVR Series
Standby Series
MODEL: CP600LCD, CP825LCD, CP800AVR, CP685AVR-G,
MODEL: RT650, RT650EI
CP825AVR-G, CP685AVRLCD-G, CP825AVRLCD-G,
AVRG750U, AVRG900U, AVRG750LCD, AVRG900LCD
1
2
1
2
3
1. Place the UPS on its top and remove the retaining screw (figure 1).
2. Slide the battery compartment cover completely o of the unit (figure 2).
3. Remove the battery from the compartment and disconnect the battery wires
from the battery. Install the replacement battery by connecting the red wire
to the positive (+) terminal and the black wire to the negative (-) terminal
of the battery. (figure 3)
4. Slide the battery compartment cover over the battery and tighten the
retaining screw.
5. Charge the unit for 48 hours to ensure the UPS performs expected
runtimes.
MODEL: CP850AVRLCD, CP1000AVRLCD
1
2
3
3
4
1. Place the UPS on its side and remove the retaining screw. 2. Slide the
battery compartment cover completely o of the unit. 3. Remove the battery from
the compartment and disconnect the
battery wires from the battery. 4. Install the replacement battery by
connecting the red wire and
black wire to the positive (+) and negative (-) terminal of the battery. Put
the battery back into the compartment. 5. Slide back the battery compartment
cover and tighten the retaining screw. 6. Charge the unit for 8 hours to
ensure the UPS performs expected runtimes.
1. Place the UPS on its side and locate the battery compartment cover on the
bottom of the UPS. Remove the four (4) retaining screws and pull the battery
compartment cover o the UPS (figure 1 & 2).
2. Remove the battery from the compartment and disconnect the battery wires
from the batteries. Install the replacement batteries by connecting the red
wire and black wire to the same color wires from the battery pack. Put the
battery pack into the compartment (figure 3).
3. Slide the battery compartment cover over the battery and tighten the
retaining screw. Charge the unit for 48 hours to ensure the UPS performs
expected runtimes.
1
2
Smart APP Intelligent LCD Series
MODEL: OR500LCDRM1U, OR700LCDRM1U, OR1000LCDRM1U, OR1500LCDRM1U
1
2
3
MODEL: CPS1500AVR
1
2
! WARNING
BATT
BATUTSEINRGY
LOAD
AVR
POONWER
! WARNING
BATT
BATUTSEINRGY
LOAD
A V R
POONWER
3
! WARNING
BATT
BATUTSEINRGY
LOAD
AVR
POONWER
3
Smart APP SINEWAVE Series
MODEL: PR750LCD, PR750 JP, PR750ELCD
1
2
AVR Series
MODEL: BRG850AVRLCD, BRG1000AVRLCD, CP850AVRLCDa,
CP1000AVRLCDa
1
2
MODEL: CP900AVR, CP1200AVR, CP1500AVRT, CP1285AVRLCD, CP1350AVRLCD, CP1500AVRLCD
1
2
3
4
3
4
1. Place the UPS on its side.
2. Remove the front panel retaining screws located on the bottom of the UPS.
3. Slide the battery compartment cover (front panel) completely o of the
unit.
4. Disconnect the battery wires from the battery and remove the battery from
the compartment.
5. Install the replacement battery by connecting the red wire (+) and black
wire (-) to the same color connectors from the battery pack. Put the battery
back into the compartment.
6. Slide back the battery compartment cover and tighten the retaining screws.
7. Charge the UPS for 8-16 hours to ensure the UPS performs expected
runtimes.
MODEL: BRG1350AVRLCD, BRG1500AVRLCD, CP1500AVRLCDa
1
2
3
4
5
6
1. Place the UPS on its side to locate and remove the front panel retaining
screw from the bottom of the UPS.
2. Slide the cover (front panel) towards the bottom of the UPS.
3. Detach the cover from the unit.
4. Disconnect the cable located at the top of the cover and remove the cover
from the unit.
5. Disconnect the battery wires from the batteries.
6. Remove the batteries from the compartment.
7. Install the replacement batteries by connecting the red and black wires to
the same color wires from the battery pack. Put the battery pack back into the
compartment.
8. Replace the battery compartment cover and tighten the retaining screw.
9. Charge the unit for 4-8 hours to ensure the UPS performs expected
runtimes.
1. Place the UPS on its side.
2. Remove the front panel retaining screws located on the bottom
of the UPS.
3. Slide the battery compartment cover (front panel) completely
o of the unit.
4. Disconnect the battery wires from the batteries and remove the
batteries from the compartment.
5. Install the replacement batteries by connecting the red wire (+) and
black wire (-) to the same color connectors from both the upper and
lower battery pack. Put the batteries back into the compartment.
Note: Make sure both batteries are new and replaced at the
same time to ensure maximum battery lifespan.
6. Slide back the battery compartment cover and tighten the
retaining screws.
7. Charge the UPS for 8-16 hours to ensure the UPS performs
expected runtimes.
4
5
MODEL: PR1500LCD, PR1500 JP, PR1500ELCD
1
2
3
4
MODEL: PR2200LCD, PR3000LC, PR2200ELCD, PR3000ELCD
1
2
3
4
3
4
4
5
4
! WARNING
BATT
BATUTSEINRGY
LOAD
A V R
POONWER
5
! WARNING
BATT
BATUTSEINRGY
LOAD
AVR
POONWER
5
6
(+) Red (-) Black
7
8
(-) Black (+) Red
1. Remove the right side front panel.
2. Remove the three retaining screws for the cable protection cover and
remove the cover.
3. Disconnect the black and red cable.
4. Remove the one retaining screw holding the battery pack in place.
5. Remove the battery pack.
6. Install the new battery pack. Assemble the screws, cover, cable and front
panel in the reverse order of the previous steps. Charge the unit for 4-8
hours to ensure the UPS performs expected runtimes.
MODEL: OR1500LCDRM2U, OR2200LCDRM2U OR1500LCDRTXL2U, OR2200LCDRTXL2U OR1500LCDRT2U, OR2200LCDRT2U
1
2
3
1. Remove the right side front panel.
2. Remove the two retaining screws for the cable protection cover and remove
the cover.
3. Disconnect the black and red cable.
4. Remove the four retaining screws holding the battery pack in place.
5. Remove the battery pack.
6. Install the new battery pack. Assemble the screws, cover, cable and front
panel in the reverse order of the previous steps. Charge the unit for at least
12 hours to ensure the UPS performs expected runtimes.
1. Place the UPS on its side and remove the two retaining screws located on
the bottom of the UPS.
2. Slide the battery compartment cover completely o the unit.
3. Remove the battery which is located on the right side from the compartment
and disconnect the battery wires from the right side of the battery.
4. Slide the remaining battery from the left side to the right side of the
compartment.
5. Remove the remaining battery from the compartment and disconnect the
battery wires from it.
6. Install the “left side” replacement battery by connecting the yellow wire
(+) to the red connector from the battery and the black wire (-) to the black
connector from the battery. Place the battery into the left side of the
compartment.
7. Install the “right side” replacement battery by connecting the red wire
(+) to the red connector from the battery and yellow wire (-) to the black
connector from the battery. Place the battery into the right side of the
compartment.
Note: Make sure both batteries are new and replaced at the same time to ensure
maximum battery lifespan.
8. Slide back the battery compartment cover and tighten the retaining screws.
9. Charge the UPS for 8-16 hours to ensure the UPS performs expected
runtimes.
4
5
6
1. Remove the right side front panel.
2. Remove the three retaining screws for the cable protection cover and
remove the cover.
3. Remove the two retaining screws from the cable connectors.
4. Disconnect the black and red cable.
5. Remove the four retaining screws holding the battery pack in place.
6. Remove the battery pack.
7. Install the new battery pack. Assemble the screws, cover, cable and front
panel in the reverse order of the previous steps. Charge the unit for at least
12 hours to ensure the UPS performs expected runtimes.
6
7
8
Copyright © 2023 Cyber Power Systems, Inc. All rights reserved.
R 750VA
3
R
4
R
1. Remove the front panel of the UPS. 2. Pull out both round knobs and remove
the battery compartment
cover completely o of the unit. 3. Remove the batteries from the compartment.
4. Disconnect the battery wires from the batteries. 5. Install the replacement
batteries by connecting the wire bundle
(composed of one red wire and one black wire) to the connector from the
battery pack. Put the batteries back into the compartment. 6. Re-install the
battery compartment cover and push both round knobs back into place. Put the
front panel back on the UPS. 7. Connect to AC power and charge the new
batteries for up to 16 hours to insure a full charge.
1. Remove the front panel of the UPS.
2. Remove two screws from the battery compartment cover and slide the cover
completely o of the unit.
3. Remove the batteries from the compartment. Disconnect the battery wires
from the batteries.
4. Install the replacement batteries by connecting the wire bundle (composed
of one red wire and one black wire) to the connector from the battery pack.
5. Put the batteries back into the compartment. Re-install the battery
compartment cover and tighten the retaining screws. Put the front panel back
on the UPS.
6. Connect to AC power and charge the new batteries for up to 16 hours to
insure a full charge.
MODEL: PR2000SL JP, PR3000SL JP, PR2200LCDSL, PR3000LCDSL, PR2200ELCDSL, PR3000ELCDSL, M550L, M750L, M1100XL
1
2
MODEL: PR1000LCD, PR1000 JP, PR1000ELCD
1
2
3
4
1. Remove the front panel of the UPS and two screws from the battery
compartment cover and slide the cover completely o of the unit.
2. Pull out the battery pack on the outside from the compartment. Disconnect
the battery connector from the batteries.
3. Before removing the battery pack on the inside, unlock the cable tie and
pull out the battery wires. Disconnect the battery connector from the
batteries.
4. Install the replacement battery pack on the inside by connecting the wire
bundle connector (composed of one red wire and one black wire) to the
connector from the battery pack. Lock the battery wires back with the cable
tie.
5. Install the replacement batteries on the outside by connecting the wire
bundle connector (composed of one red wire and one black wire) to the
connector from the battery pack. Put the battery pack on the outside back into
the compartment.
6. Re-install the battery compartment cover and tighten the retaining screws
and put the front panel back on the UPS.
7. Connect to AC power and charge the new batteries for up to 16 hours to
insure a full charge.
Note: The battery pack on the outside has a fuse, while the battery pack on
the inside does not.
MODEL: PR750LCDRM1U, PR1000LCDRM1U, PR750ELCDRT1U, PR1000ELCDRT1U
1
2
3
3
4
1. Remove the front panel of the UPS.
2. Remove two screws from the battery compartment cover and slide the cover
completely o of the unit.
3. Remove the batteries from the compartment. Disconnect the battery wires
from the batteries.
4. Install the replacement batteries by connecting the wire bundle (composed
of one red wire and one black wire) to the connector from the battery pack.
5. Put the batteries back into the compartment. Re-install the battery
compartment cover and tighten the retaining screws. Put the front panel back
on the UPS.
6. Connect to AC power and charge the new batteries for up to 16 hours to
insure a full charge.
9
1. Remove the front panel of the UPS. 2. Remove two screws from the battery
compartment cover and
slide the cover completely o of the unit. 3. Remove the batteries from the
compartment. 4. Disconnect the battery wires from the batteries. 5. Install
the replace batteries by connecting the red wire (+) and
black wire (-) to the same color connectors from the battery pack. 6. Put the
batteries back into the compartment. 7. Re-install the battery compartment
cover and tighten the
retaining screws. 8. Put the front panel back on the UPS. 9. Connect to AC
power and charge the new batteries for up to 16
hours to insure a full charge.
10
4
5
1. Remove the right side front panel. 2. Remove the two retaining screws for
the cable protection cover
and remove the cover. 3. Disconnect the black and red cable. 4. Remove the one
retaining screw holding the battery pack in place. 5. Remove the battery pack.
6. Install the new battery pack. Assemble the screws, cover, cable
and front panel in the reverse sequence of the above steps. Charge the unit
for at least 12 hours to ensure the UPS performs expected runtimes.
11
MODEL: PR1000ELCDRT2U, PR1500ELCDRT2U,
PR2200ELCDRT2U, PR1000LCDRT2U,
PR1000LCDRTXL2U, PR1500LCDRT2U,
PR2200LCDRT2U
1
2
3
!
4
5
MODEL: PR5000ELCDRTXL5U, PR6000ELCDRTXL5U, PR5000LCDRTXL5U, PR6000LCDRTXL5U
1
2
3
4
5
1. Remove the right side front panel. 2. Remove the two screws for the cable
protection cover. 3. Disconnect the red and black cables. 4. Remove the four
retaining screws holding the battery pack in place. 5. Remove the battery
pack. 6. Install the new battery pack. Assemble the screws, cover, cable
and front panel in the reverse order of the previous steps. Charge the unit
for at least 12 hours to ensure the UPS performs expected runtimes.
MODEL: PR3000ELCDRT2U, PR1000ELCDRTXL2U,
PR1500ELCDRTXL2U, PR2200ELCDRTXL2U,
PR1000LCDRTXL2Ua, PR1500LCDRTXL2U,
PR2200LCDRTXL2U, PR3000LCDRT2U,
PR3000LCDRTXL2U
1
2
1. Remove the front panel. 2. Remove the two retaining screws of the cable
protection cover
and remove the cover. 3. Pull the plastic sticker out slowly to remove the
battery module. 4. Put the new battery modules back into the compartment. 5.
Tighten the screws and replace the cable protection cover and
the front panel.
MODEL: PR500LCDRT1U, PR750LCDRT1U, PR1000LCDRT1U, PR1000LCDRT1U JP
1
2
3
3
4
5
6
1. Remove the two screws and remove the right panel.
2. Disconnect the battery connector.
3. Remove the two retaining screws and remove the battery cover. Install new
battery pack. Assemble the screws, cover, connector and front panel in the
reverse order of previous steps. Charge the unit for at least 12 hours to
fully charge the battery.
1. Remove the six retaining screws, and remove the front panel from
the UPS.
2. Remove the two retaining screws for the cable protection cover
and remove the cover.
3. Remove the two retaining screws from the cable connectors.
4. Disconnect the black and red cable.
5. Remove the three retaining screws holding the battery pack in place.
6. Remove the battery pack.
7. Install the new battery pack. Assemble the screws, cover, cable
and front panel in the reverse order of the previous steps. Charge
the unit for at least 12 hours to ensure the UPS performs expected
runtimes.
12
13
MODEL: PR750RT2U, PR1000RT2U, PR1500RT2U, PR2000RT2U, PR2200RT2U, PR3000RT2U, PR750RTXL2U, PR1000RTXL2U, PR1500RTXL2U, PR2000RTXL2U, PR2200RTXL2U, PR3000RTXL2U, PR2200RTXL2UA, PR3000RTXL2UA, PR2200RTXL2UHVA, PR3000RTXL2UHVA, PR750ERT2U, PR1000ERT2U, PR1500ERT2U, PR2000ERT2U, PR2200ERT2U, PR3000ERT2U, PR750ERTXL2U, PR1000ERTXL2U, PR1500ERTXL2U, PR2000ERTXL2U, PR2200ERTXL2U, PR3000ERTXL2U, PR2200ERTXL2UA, PR3000ERTXL2UA
1
2
3
PFC SINEWAVE Series
MODEL: OR750PFCLCD, OR1000PFCLCD, OR1500PFCLCD
1
2
3
4
1. Remove the front panel of the UPS. 2. Remove two screws from the battery
compartment cover and
slide the cover completely o~ of the unit. 3. Remove the batteries from the
compartment. 4. Disconnect the battery wires from the batteries. 5. Install
the replacement batteries by connecting the red wire (+) and
black wire (-) to the same color connectors from the battery pack. 6. Put the
batteries back into the compartment. 7. Re-install the battery compartment
cover and tighten the
retaining screws. 8. Put the front panel back on the UPS. 9. Connect to AC
power and charge the new batteries for up to 16
hours to insure a full charge.
1. Remove the faceplate and unscrew the thumbscrews on toolless battery
access door and then open the door. Note: The thumbscrews are designed to be
fixed on the door, do not remove them from the metal cover.
2. Disconnect the battery and battery management module connector and remove
the battery pack.
3. Insert the new battery pack. Assemble the connectors, thumbscrews and
faceplate. Recharge the unit for at least 12 hours to ensure the UPS performs
expected runtime.
Reminder: Battery Change Date is optional setup information for users to
record the installation date of battery pack. It can be adjusted through LCD
module in Advanced Setup Menu or through software.
MODEL: OR1000PFCRT2U, OR1500PFCRT2U, OR2200PFCRT2U
1
2
3
4
5
6
1. Remove the right side front panel.
2. Remove the three retaining screws for the cable protection cover and
remove the cover.
3. Remove the two retaining screws from the cable connectors.
4. Disconnect the black and red cable.
5. Remove the four retaining screws holding the battery pack in place.
6. Remove the battery pack.
7. Install the new battery pack. Assemble the screws, cover, cable and front
panel in the reverse order of the previous steps. Charge the unit for at least
12 hours to ensure the UPS performs expected runtimes.
MODEL: CP850PFCLCD, CP1000PFCLCD, CP550EPFCLCD, CP900EPFCLCD
1
2
3
4
1. Turn the UPS on its side. Remove the retaining screw located on the bottom
of the UPS.
2. Slide the battery compartment cover completely o~ of the unit.
3. Remove the batteries from the compartment.
4. Disconnect the battery wires from the batteries.
5. Install the replacement batteries by connecting the red wire (+) and black
wire (-) to the same color connectors from the battery pack. Put the batteries
back into the compartment.
6. Slide back the battery compartment cover and tighten the retaining screw.
Recharge the UPS for 8-16 hours to fully charge the battery.
MODEL: CP1350PFCLCD, CP1300EPFLCD
1
2
3
4
1. Turn the UPS on its side. Remove the front panel retaining screws located
on the bottom of the UPS.
2. Slide the battery compartment cover (front panel) completely o~ of the
unit.
3. Remove the batteries from the compartment.
4. Disconnect the battery wires from the batteries.
5. Install the replacement batteries by connecting the red wire (+) and black
wire (-) to the same color connectors from the battery pack. Put the batteries
back into the compartment.
6. Slide back the battery compartment cover and tighten the retaining screws.
Recharge the UPS for 8-16 hours to fully charge the battery.
MODEL: CP1500PFCLCD, CP1500EPFLCD
1
2
3
4
1. Turn the UPS on its side. Remove the front panel retaining screws located
on the bottom of the UPS.
2. Slide the battery compartment cover (front panel) completely o~ of the
unit.
3. Remove the batteries from the compartment.
4. Disconnect the battery wires from the batteries.
5. Install the replacement batteries by connecting the wire bundle (composed
of one red wire and one black wire) to the connector from the battery pack.
Put the batteries back into the compartment.
6. Slide back the battery compartment cover and tighten the retaining screws.
Recharge the UPS for 8-16 hours to fully charge the battery.
14
15
16
17
FTTx Series
MODEL: CSN27U12V-NA2, CSN27U12V-NA3, CSN27U12V-NA3-G, CSN27U12V-XL
1
2
3
MODEL: CS24C12V2-E
1
2
Extended Battery Modules
Smart APP SINEWAVE Series
3 MODEL: BP48V45ART2U, BP48V75ART2U
MODEL: PR750LCD3C
1
2
3
1
2
1. Remove the battery cover.
2. Disconnect battery cable connector to remove battery.
3. Replace with new battery and re-connect the battery connector.
4. Make sure battery is fixed properly in the compartment and close the
battery cover.
MODEL: DTC36U12V-NA3-G
1
2
3
1. Remove the case screw. 2. Open the battery cover. 3. Loosen the battery strap. 4. Disconnect battery cable connector to remove battery. 5. Replace with new battery and re-connect the battery connector. 6. Tighten the battery strip 7. Close the battery cover and tighten the case screw.
1. Slide o~ the battery cover at the back of the DTC36U12V unit. 2. Remove
the battery from the enclosure. 3. Disconnect both battery cable connectors.
4. Install the new battery by connecting the red lead to the positive
terminal and the black lead to the negative terminal. 5. Slide the battery
back into the normal operation. 6. Replace battery cover to resume normal
operation.
4
5
PUSH
3
4
5
1. Remove the front panel on the right side. 2. Remove the front panel on the
left side. 3. Disconnect the black and red wire from the battery. 4. Remove
the cover and then remove the eight retaining screws. 5. Pull out the old
battery packs and replace them with the new
ones. Recharge the unit for at least 12 hours to ensure the Extended Battery
Module performs expected runtime and then connect the Extended Battery Module
to your UPS.
Reminder: Check and modify the Extended Battery Module Quantity setting on
your UPS through the LCD module, PowerPanel® Business software or RMCARD
interface (if installed) to ensure the UPS reports an accurate runtime.
MODEL: BP48VP2U01, BP48VP2U02, BP48VP2U03, BP48VP2U04
1
2
3
1. Push the buckle and remove the front panel of the UPS. 2. Loosen the screw
and remove the battery compartment plate. 3. Remove the batteries from the
compartment. 4. Press the buckle to remove the battery connector from the
batteries. 5. Install the replacement batteries and reconnect the battery
connectors. *CAUTION! The side with the buckle should be facing up.
6. Put the batteries back into the compartment. 7. Re-install the battery
compartment plate and tighten the screw
back into place. 8. Put the front panel back on the UPS. 9. Connect to AC
power and charge the new batteries for up to 8
hours to insure a full charge.
1. Disconnect the Extended Battery Module from your UPS, remove the faceplate
and unscrew the screws on battery cover and then remove the battery cover.
2. Disconnect the battery and battery management module connector.
3. Insert the new battery pack. Assemble the connectors, screws, battery
cover and faceplate. Recharge the unit for at least 12 hours to ensure the
Extended Battery Module performs expected runtime and then connect the
Extended Battery Module to your UPS.
Reminder: Check and modify the Extended Battery Module Quantity
setting on your UPS through the LCD module, PowerPanel® Business
software or RMCARD interface (if installed) to ensure the UPS reports
an accurate runtime.
18
19
20
21
Cyber Power Systems, Inc.
www.cyberpower.com
For USA and Canada: 4241 12th Ave East, Suite 400 Shakopee, MN 55379 Toll-
free: 877-297-6937
For all other regions: Please visit our website for local contact information.
22
K01-0000611-04
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>