PACIFIC ENERGY T6 LE Alderlea Wood Stove Instruction Manual

June 16, 2024
Pacific Energy

OPERATING AND
INSTALLATION
INSTRUCTIONS

T6 LE Alderlea Wood Stove


MODEL:
ALDERLEA T6 LE

IMPORTANT: THESE INSTRUCTIONS ARE TO REMAIN WITH THE HOMEOWNER
TESTED and LISTED to: CAN/ULC S627 AND UL 1482

SAFETY NOTICE
If this stove is not properly installed, a house fire may result. For your safety, follow the installation instructions.
Contact local building or fire officials about restrictions and installation inspection requirements in your area.
Meets the Environmental Protection Agency’s 2020 Particulate Emission Standards (Crib Wood).

WARNING
HOT GLASS WILL CAUSE BURNS.
DO NOT TOUCH GLASS UNTIL COOLED.
NEVER ALLOW CHILDREN TO TOUCH GLASS.
PLEASE SAVE THESE INSTRUCTIONS This manual describes the installation and operation of the True North, TN10 Freestanding wood heater. This heater meets the 2020 U.S. Environmental Protection Agency’s crib wood emission limits for wood heaters sold after May 15, 2015. Under specific test conditions this heater has been shown to deliver heat at rates ranging from 16,102 to 41,275 Btu/hr.
NOTE: WE STRONGLY RECOMMEND THAT SMOKE AND CARBON MONOXIDE DETECTORS BE INSTALLED IN THE AREA WHERE THE HEATER IS TO BE INSTALLED.
If smoke detectors have been previously installed, you may notice that they are operating more frequently. This may be due to curing of stove paint or fumes caused by accidentally leaving the fire door open. Do not disconnect the detectors.
SAFETY NOTICE: If this stove is not properly installed, a house fire may result. For your safety, follow the installation instructions. Contact local building or fire officials about restrictions and installation inspection requirements in you area.
Please read this entire manual before you install and use your new room heater. Failure to follow instructions may result in property damage, bodily injury, or even death.

Rating Label

PLEASE SAVE THESE INSTRUCTIONS
This manual describes the installation and operation of the Pacific Energy, ALDERLEA T6 LE Freestanding wood heater.
Model ALDERLEA T6 LE: 1.8 g/hr.
SAFETY NOTICE: If this stove is not properly installed, a house fire may result. For your safety, follow the installation instructions. Contact local building or fire officials about restrictions and installation inspection requirements in you area.
Please read this entire manual before you install and use your new room heater. Failure to follow instructions may result in property damage, bodily injury, or even death.
Efficiency and BTU Output

EPA Certified Emissions 1.8 grams per hour
LHV Tested Efficiency 1 80%
HHV Tested Efficiency 2 74%
EPA BTU Output 3 16,102 to 41,275 btu/hr
Maximum Wood Length 20 inches
Ideal Wood Length 16-18 inches
Fuel Seasoned Cord wood
  1. Weighted Average Lower Heating Value (LHV) efficiency as tested using CSA B415 Performance testing of solid-fuelburning heating appliances. LHV assumes the moisture is already in a vapour state so there is no loss of energy
  2. Weighted Average Higher Heating Value (HHV) efficiency as tested using CSA B415 Performance testing of solid-fuelburning heating appliances. HHV includes the energy required to vaporize the water in the fuel
  3. The range of BTU outputs is based on efficiency using CSA B415 Performance testing of solid-fuel-burning heating appliances and burn rates from the low and high EPA tests using Douglas Fir dimensional lumber.

Experience will give you the right settings for proper combustion and efficient burning. Remember the correct air inlet setting is affected by variables such as type of wood, outside temperature, chimney size and weather conditions. With practice, you will become proficient in operating your heater and will obtain the performance for which it was designed.

Safety

WARNING: This product can expose you to chemicals including ceramic bers, which are known to the state of California to cause cancer, and to carbon monoxide, which is known to the state of California to cause birth defects or other reproductive harm.
For more information, go to www.p65warnings.ca.gov.
This warning is applicable to all
PACIFIC ENERGY FIREPLACE PRODUCTS
CAUTION: Never use gasoline, gasoline type lantern fuel, kerosene, charcoal lighter fluid or similar liquids to start or “freshen up” a fire in this heater. Keep all such liquids well away from the heater while it is in use.
Instruct all members of your family on the safe operation of the heater. Ensure they have enough knowledge of the entire system if they are expected to operate it. Stress the section on chimney fires and the importance of following the steps outlined “In Case of Chimney Fire”.

Chimney Smoke and Creosote Formation
When wood is burned slowly, it produces tar and other organic vapours, which combine with expelled moisture to form creosote. The creosote vapours condense in the relatively cool chimney flue of a slow burning fire. As a result, creosote residue accumulates on the flue lining. When ignited, this creosote makes an extremely hot fire. The chimney connector and chimney should be inspected periodically (at least once every two months) during the heating season to determine if a creosote buildup has occurred. If creosote has accumulated (3 mm. or more), it should be removed to reduce the risk of a chimney fire.

  1.  Highest smoke densities and emissions occur when a large amount of wood is added to a bed of hot coals and the air inlet is closed. The heated wood generates smoke, but without ample air, the smoke cannot burn. Smoke-free, clean burning requires small fuel loads, two or three logs at a time or 1/4 to 1/2 of fuel load and leaving the air inlet relatively wide open, especially during the first 10 to 30 minutes after each loading, when most of the smoke generating reactions are occurring. After 30 minutes or so, the air inlet can be turned down substantially without excessive smoke generation. Wood coals create very little creosote-producing smoke.
  2.  The cooler the surface over which the wood smoke is passing, the more creosote will be condensed. Wet or green wood contributes significantly to creosote formation as the excess moisture that is boiled off cools the fire, making it difficult for the tars and gases to ignite, thus creating dense smoke and poor combustion. This moisture-laden smoke cools the chimney, compounding the problem by offering the smoke the ideal place to condense.

In summary, a certain amount of creosote is inevitable. Regular inspection and cleaning is the solution. The use of dry, seasoned wood and ample combustion air will help to minimize annoying smoke emissions and creosote buildup.

Chimney Fires
The dangerous side effect of excessive creosote buildup is a chimney fire. This causes much higher than normal temperatures in the chimney and on its exterior surfaces. Temperatures inside the chimney can exceed 2000°F (1100°C). Ignition of nearby or touching combustible material is more likely during a chimney fire. Proper clearances are critical to prevent damage during such a fire.
Chimney fires are easy to detect; they usually involve one or more of the following:

  • Flames and sparks shooting out of the top of the chimney
  • A roaring sound
  • Vibration of the chimney

To Avoid a Chimney Fire

  1. Burn wood cleanly. Do not burn wet wood or turn down the unit too quickly after loading.
  2. Do not let creosote build up to a point where a chimney fire is possible.
  3. Do not have fires in the heater that may ignite chimney fires. These are excessively hot fires, such as when burning household trash, cardboard, Christmas tree limbs, or even ordinary fuel wood; (eg. with a full load on a hot bed of coals and with the air inlet wide open for more time than is needed to completely char a fresh fuel load.)
  4. The Chimney and connector pipe should be inspected /cleaned periodically.

In Case of a Chimney Fire

  1. Prepare to evacuate to ensure everyone’s safety. Have a well understood plan of action for evacuation. Have a place outside where everyone is to meet.
  2. Close air inlet on stove.
  3. Call local fire department. Have a fire extinguisher handy. Contact your local municipal or provincial fire authority for further information on how to handle a chimney fire. It is most important that you have a clearly understood plan on how to handle a chimney fire.
  4. After the chimney fire is out, the chimney must be cleaned and checked for stress and cracks before starting another fire. Also check combustibles around the chimney and the roof.
    • The services of a competent or certified installer, (certified by the Wood Energy Technical Training program (WETT) – in Canada, Hearth Education Foundation (HEARTH) – in U.S.A.,) are strongly recommended.

Curing of the Paint Finish
To acheive the best finish, the paint on your stove must be baked on. When burning your stove for the first 2-3 times it is very important that the room be well ventilated. Open all windows and doors. Smoke and fumes caused by the curing process may cause discomfort to some individuals.
WARNING: Never use chemicals or any other volatile liquid to start a fire. Do not burn garbage, or flammable fluids such as gasoline, naptha, or engine oil.

Operation

CAUTION: Hot while in operation. Keep children, clothing and furniture away. Contact may cause skin burns.
WARNING: Always keep loading door closed when burning. This heater is not designed for open door burning.
WARNING: No alteration or modification of the combustion air control assembly is permitted. Any tampering will void warranty and could be very hazardous.
WARNING: Do not use grates or andirons to elevate the fuel. Burn directly on the fire bricks. Replace broken or missing bricks. Failure to do so may create a hazardous condition.
Wood Selection
This heater is designed to burn natural wood only. Higher efficiency and lower emissions generally result when burning air-dried seasoned hardwoods, as compared to softwoods or to green or freshly cut hardwoods.
Wood should be properly air dried (seasoned) for six months or more. Wet or undried wood will cause the fire to smoulder and produce large amounts of smoke and creosote. Wet wood also produces very little heat and tends to go out often. Wood should be stored under cover away from open flame or heat sources.
DO NOT BURN :

• Salt water wood * • Treated wood
• Wet or green wood • Coal/charcoal
• Garbage* • Solvents
• Lawn clippings/yard waste • Unseasoned wood
• Railroad ties • Manure or animal remains
• Materials containing rubber, including tires • Materials containing plastic
• Construction or demolition debris • Materials containing asbestos
• Waste petroleum products, paints, paint thin- ners, or asphalt products

Paper products, cardboard, plywood, or particleboard.

  • These materials contain chlorides which will rapidly destroy metal surfaces and void warranty.
    Burning these materials may result in the release of toxic fumes or render the heater ineffective and cause smoke.
    Do not burn anything but wood. Other fuels, eg. charcoal, can produce large amounts of carbon monoxide, a tasteless, odorless gas that can kill. Under no circumstances should you attempt to barbecue in this heater.
    The prohibition against burning these materials does not prohibit the use of fire starters made from paper, cardboard, saw dust, wax and similar substances for the purpose of starting a fire in an affected wood heater.
    How to Test Your Wood
    Add a large piece of wood to the stove when it has a good large bed of coals. It is dry if it is burning on more than one side within one minute. It is damp if it turns black and lights within three minutes. If it sizzles, hisses and blackens without igniting in five minutes it is soaked and should not be burnt

Lighting a fire
WARNING: Never use chemicals or any other volatile liquid to start a fire.

  1. Adjust air control to “High” position(all the way to the left) and open door.
  2. Place crumpled newspaper in the centre of the heater and crisscross with several pieces of dry kindling. Add a few small pieces of dry wood on top.
  3. Ignite the paper and leave the door ajar approximately 1/2″(13mm) – 1″(25mm) until the wood kindling is fully engulfed in flame.
  4. After the kindling is fully engulfed add a few small logs. Close door.
  5. Begin normal operation after a good coal base exists and wood has charred.

Normal Operation
WARNING: This wood heater has a manufacturer-set minimum low burn rate that must not be altered.
It is against federal regulations to alter this setting or otherwise operate this wood heater in a manner inconsistent with the operating instructions in this manual.

  1. Set air control to a desired setting. If smoke pours down across the glass (waterfall effect) this indicates you have shut the control down too soon or you are using too low a setting. The wide range control panel makes finding the desired setting for your application easy. As every home’s heating needs vary (ie. insulation, windows, climate, etc.) the proper setting can only be found by trial and error and should be noted for future burns.
  2. To refuel, adjust air control to high, and give the fire time to brighten. Open the door slowly, this will prevent back puffing.
  3. Use wood of different shape, diameter and length (up to 18″(457mm)). Load your wood endwise and try to place the logs so that the air can flow between them. Always use dry wood.
  4. Do not load fuel to a height or in such a manner that would be hazardous when opening the door.
  5. For extended or overnight burns, unsplit logs are preferred. Remember to char the wood completely on maximum setting before adjusting air control for overnight burn.
    • Burn wood only, dry and well seasoned. The denser or heavier the wood when dry, the greater its heat value. This is why hardwoods are generally preferred. Green or wet wood will cause a rapid buildup of creosote. If you feel it is necessary to burn wet or unseasoned wood, do so only with the air inlet set open enough to maintain a good strong fire and fairly high chimney temperatures. Do not attempt to burn overnight using green wood or wet wood. Wet wood can cause up to 25% drop in heater output, as well as contributing significantly to creosote buildup.

DO NOT OVER FIRE THIS HEATER: Attempts to achieve heat output rates that exceed heater design specifications can result in permanent damage to the heater and chimney. A glowing red, top or vent pipe are indications of over firing. Failure to rectify an over firing condition can be hazardous and may void the manufacturer’s warranty.

Restarting After Extended or Overnight Burns

  1. Open door and rake hot embers towards the front of the heater. Add a couple of dry, split logs on top of embers, close door.
  2. Adjust air control to high and in just a few minutes, logs should begin burning.
  3. After wood has charred, reset air control to desired setting.
  4. To achieve maximum firing rate, set control to high “H”. Do not use this setting other than for starting or preheating fresh fuel loads.

Proper Draft

  1. Draft is the force which moves air from the appliance up through the chimney. The amount of draft in your chimney depends on the length of the chimney, local geography, nearby obstructions and other factors.
  2. Too much draft may cause excessive temperatures in the appliance. An uncontrollable burn or a glowing red stove part or chimney indicates excessive draft.
  3. Inadequate draft may cause back puffing into the room and plugging of the chimney. Smoke leaking into the room through appliance and chimney connector joints indicates inadequate draft.

Remember the correct air inlet setting is affected by variables such as type of wood, outside temperature, chimney size and weather conditions.

Ash Removal

Caution: Ashes are to be removed only when the heater is cold. Whenever ashes get 3″(76mm) to 4″(102mm) deep in your firebox, and when fire has burned down and cooled, remove excess ashes. Leave an ash bed approximately 1″ (25 mm) deep on the firebox bottom to help maintain a hot charcoal bed.
Ash Clean out system:
The ash dump handle is located under the ash lip on the left hand side. To operate ash dump, pull handle out 1/2″(13mm) and turn clockwise. This will unlock the ash dump and allow it to open. Hold handle open while pulling ashes into the opening. Avoid large embers as these still contain heat value. Release handle and push in to lock. Ensure ash dump door is properly engaged. Fill the cavity with the remaining ash level with the firebox floor. Lift and pull out ashpan and discard ashes into metal container. Replace ashpan and ensure it is seated properly.
Do not burn with ash dump door open. Doing so will create a hazardous condition. Always leave about 1″(25mm) of ash when cleaning.
Disposal of Ashes
Ashes should be placed in a metal container with a tight fitting lid. The closed container of ashes should be placed on a non-combustible floor or on the ground, well away from all combustible materials, pending final disposal. If the ashes are disposed of by burial in soil or otherwise locally dispersed, they should be retained in closed container until all cinders have thoroughly cooled. Other waste should not be placed in this container.

Maintenance

WARNING: Never use chemicals or any other volatile liquid to start a fire. Do not burn garbage, or flammable fluids such as gasoline, naptha, or engine oil.
WARNING: ONLY USE MATERIALS SUPPLIED BY MANUFACTURER WHEN DOING MAINTENANCE OR REPLACEMENTS.

  1. If glass becomes darkened through slow burning or poor wood, it can readily be cleaned with fireplace glass cleaner when stove is cold. Never scrape with an object that might scratch the glass. The type and amount of deposit on the glass is a good indication of the flue pipe and chimney buildup. A light brown dusty deposit that is easily wiped off usually indicates good combustion and dry, well-seasoned wood and therefore relatively clean pipes and chimney. On the other hand, a black greasy deposit that is difficult to remove is a result of wet and green wood and too slow a burning rate. This heavy deposit is building up at least as quickly in the chimney.

  2. DOOR GASKETS – The gasket used by Pacific Energy (1/2″(13mm) medium density fiberglass rope) requires only light pressure to seal. This will prolong seal life. It is important that the door seal be maintained in good condition. Periodically inspect seals and replace if necessary. Follow the instructions included in the kit, obtainable from your nearest Pacific Energy dealer.

  3. DOOR GLASS – Do not slam loading door or otherwise impact glass. When closing door, make sure that no logs protrude to impact the glass. If the glass gets cracked or broken, it must be replaced before using the stove. Replacement glass can be obtained from your dealer. Use 20-1/8″(511mm) x 11-7/8″(302mm) x 5 mm. Ceramic glass only. Do not substitute with any other type.
    • To remove broken glass, undo the four retaining screws and remove clamps and frame, noting position for re-assembly. Remove all particles of glass . Be careful as they are very sharp. Install new glass complete with gasket. Replace frame, clamps and screws.
    CAUTION:
    – do not overtighten, tighten screws very carefully
    – do not clean glass when hot
    – do not use abrasive cleaners on glass

  4. The area where boost combustion air enters the firebox must be kept clear of excessive ash buildup which will block air flow. This area is at the front of the firebox.

  5. Do not store wood within heater installation clearances, or within the space required for fuel loading and ash removal. Keep the area around the heater clean and free of loose combustibles, furniture, newspapers, etc.

  6. If the plated door requires cleaning, use mild soap and water only. Use of abrasive cleaners will void warranty.

  7. Establish a routine for the fuel, woodburning and firing technique. Check daily for creosote buildup until experience shows how often you need to clean to be safe.

  8. Be aware that the hotter the fire, the less creosote is deposited. Weekly cleaning may be necessary in mild weather, even though monthly cleaning is usually enough in the coldest months when burning rates are higher. When wood is burned slowly, it produces tar and other organic vapours, which combine with expelled

Maintenance Checks

Check the following parts for damage such as cracks, excessive corrosion, burned out sections and excessive warping: (See website for descriptions and more detail)
Weekly:

  • Firebrick – Visual, for cracking.
  • Door Gasket – sagging, placement, damage.

Monthly

  • Brick rail tabs and brick rails.
  • Air riser tube in the back of the firebox.
  • Back side of airwash chamber.
  • Baffle locking pin.
  • Boost tube cover.

When Cleaning the Chimney System:

  • Top baffle board/blanket.
  • Baffle.
  • Top heat shield and mounting bolt.
  • Baffle Gasket.
  • Brick Rails.
  • Manifold.

Blower:

  • The blower should be cleaned out a minimum every six months by using a vacumn on the grill openings in the back and bottom of the blower casing to remove any dust and debris.

Baffle:

  • Some warping of the baffle is normal(up to 1/4” or .65cm). Replace if the baffle has permanent warping greater than this or has cracking or breakage.
  • Please contact your Dealer if you experience any of the damage listed above. Continuing to operate your stove with broken parts may accelerate damage to other parts and may void your warranty

Baffle Removal

Chimney connector pipe should be disconnected from stove to clean and inspect. Only if this is not possible should you remove baffle assembly.
DO NOT OPERATE WITH BAFFLE ASSEMBLY OR INSULATION REMOVED.
Removal:
Remove retaining pin at the back top of the firebox, just under the baffle. Lift baffle up and pull forward to disconnect from the supply tube. Tilt baffle sideways to drop down and remove from firebox. Inspect gasket between baffle and supply tube. If necessary, replace with gasket #139.5 available from your Pacific Energy dealer. Re-install baffle assembly in reverse order. The two side pieces of insulation must be tight against the side rails.

Assembly

Crate Removal

  1. Carefully remove wood top and supports.
  2. Remove plastic cover.
  3. Using a 7/16″ wrench, remove lag bolts that secure stove body to bottom pallet.
  4. Place stove body carefully on its back.
  5. Using two 3/4″ wrench, remove 1″ x 1/2″ bolts and save for later use.
  6. Remove pallet retaining brackets from stove bottom.

Dimensions

Floor Protector

The stove may be installed on a combustible floor provided noncombustible ember protection is used.
This protection must extend as follows:I

In USA: 16″ (406 mm) to the front and 8″ (203 mm) to the sides of the fuel loading door opening. (Figure 3). This protection is also required under the chimney connector and 2″ (51 mm) beyond each side if using any horizontal venting.

Residential Installation

Clearances:

Clearances may be reduced with various heat shielding/insulating materials. Consult CSA B365 or NFPA 211 and local fire codes and authorities for approval. For close clearances, use a listed double-wall connector.
NOTE: local/national codes or regulations may override some guidelines in this manual
The services of a competent or certified installer, (certified by the Wood Energy Technical Training program (WETT) – in Canada, Hearth Education Foundation (HEARTH) – in U.S.A.,) are strongly recommended.
Warning: Under no circumstances is this heater to be installed in a makeshift or “temporary” manner. It may be fired only after the following conditions have been met.
DO NOT ATTEMPT TO CONNECT THIS HEATER TO ANY AIR DISTRIBUTION DUCT.
Outside combustion air or fresh air into the room may be required in your area, consult local building codes (see Combustion Air section).
Chimney and Connector

  • The chimney system must be a ULC-S629 or UL-130HT listed Stainless chimney or a Masonry chimney suitable for use with solid fuel, that is lined, in good condition and meets fire and building codes.
  • The chimney flue size should be the same as the stove outlet (6 inches) for optimal performance. Reducing or increasing the flue size may adversely affect stove performance.
  • Chimney flue exit is to be 3 feet (1 m.) above roof and two feet (0.6 m.) above highest projection within 10 feet (3 m.).
  • The installation must meet all local codes.
  • Do not connect this unit to a chimney flue serving another appliance. Minimum system height is 15 feet (4.6 m.) (measured from base of appliance).

BOTH CHIMNEY SYSTEM AND CONNECTOR MUST BE LISTED TO:
IN CANADA – ULC S-641 LISTED double wall connector and ULC-S629 LISTED CHIMNEY,
IN USA – UL-103 HT LISTED CONNECTOR AND CHIMNEY
When using a Double-Wall Connector

  • Use a listed double-wall connector.
  • If a listed chimney and double-wall connector are to be connected to the stove, install all components as per the chimney/connector manufacturer’s installation requirements.

When using a Single-Wall (smoke pipe) Connector
The single wall pipe section must be:

  • If you are using smoke pipe/chimney connector in conjunction with the listed chimney system, consult local/national fire or building codes for connector installation. Follow the chimney manufacturer’s complete instructions for the installation of the chimney system.
  • As short and straight as possible, use six inch diameter, 24 gauge black pipe that is clean and in new condition.
  • Installed with the crimped or male ends pointing down. (This will carry any liquid creosote or condensation back into the stove) and secured at every joint and collar with 3 sheet metal screws.
  • The chimney connector shall not pass through an attic, roof space, closet or similar concealed space, floor, or ceiling. Where passage through a wall, or partition of combustible material is desired, the installation shall conform to CAN/CSA-B365, Installation Code for Solid-Fuel-Burning Appliances and Equipment

Installation Procedure

  1. Select the position for your wood stove based on the clearances diagram. Position the stove and floor protection.
  2. Mark the position for the hole in the ceiling and roof by using a string and plumb-bob hanging over the exact center of the stoves flue pipe.
  3. Check that the intended location will not interfere with floor joists, ceiling joists or rafters before proceeding further. Adjust if necessary and reconfirm the clearance’s from the stove to combustibles.
  4. Carefully follow the directions of the listed chimney for installation of the chimney system from the ceiling through to the rain cap. This may include framing in holes etc.
  5. Start installing smoke pipe (chimney connector), slip crimped edge of the pipe inside the stove collar. Use holes provided in collar to secure pipe with two screws.
  6. Install the remaining lengths of pipe one on top of the other up to the finished height of the chimney and using the manufacturers approved adapter, secure to each other. A slip section can make this easier.

Combustion Air
Intake or combustion air can be supplied to the stove in one of two ways. Consult your local building code or CAN/CSA-B365, Installation Code for Solid- Fuel-Burning Appliances and Equipment before proceeding.
Outside air supply – (Necessary for mobile home installation, optional for residential installation.) Outside air may be drawn from either underneath the stove or from behind.

  • To draw outside air through the floor – This hole must get its air from a ventilated crawl space or be extended with duct to the outdoors (see Figure #3, Page 7). The use of outside combustion air for residential installation requires the unit to be secured to the structure to prevent dislodging of the air duct. Cut or drill a hole in the floor, (large enough to fit 4″ metal flex venting) behind the ash box enclosure.
    Once the stove is in place, attach the 4″ Intake Starter to the Ash Box Enclosure. Connect to the floor with the 4″(100mm) i.d. metal flex pipe.

  • To draw outside air from behind the stove, Use a 4″(100mm) Air intake . Cut or drill the recomeneded size hole through a wall behind the unit. Install the 4″ Intake Starter over the hole in the rear of the Ash Box enclosure. Attach metal flex between the starter and the Air Intake.

  • Room air supply – The stove will draw its air from the room through the opening in the Ash Box Enclosure and into the firebox intake.
    Note: The living space around the heater must be well ventilated with good air circulation. Anything that may cause a negative pressure can cause gases or fumes to be pulled into the living area. During extremely cold weather, and especially when burning at very slow rates, the upper parts of the exposed chimney may ice up, partially blocking the flue gases. If blockage occurs, flue gases may enter living space.

Through Wall Installations
(as per NFPA 211-2013)
ATTENTION: VAPOUR BARRIER MUST BE MAINTAINED WHEREVER CHIMNEY OR OTHER COMPONENTS PENETRATE TO THE EXTERIOR OF THE STRUCTURE. SEE LOCAL BUILDING CODES FOR PROPER AND APPROVED METHODS OF MAINTAINING VAPOUR BARRIER. Minimum Clearance 12 in. (305mm) to combustibles
System A. Minimum 3.5 in. (90 mm) thick brick masonry wall framed into combustible wall with a minimum of 12 in. (305 mm) brick separation from clay liner to combustibles. Fireclay liner (ASTM C 315, Standard Specifications for Clay Fire Linings, or equivalent), minimum 5/8 in. (16 mm) wall thickness, shall run from outer surface of brick wall to, but not beyond, the inner surface of chimney flue liner and shall be firmly cemented in place.

Minimum Clearance 9 in. (229mm) to combustibles
System B. Solid-Insulated, listed factory-built chimney length of the same inside diameter as the chimney connector and having 1 in. (25.4 mm) or more of insulation with a minimum 9 in. (229 mm) air space between the outer wall of the chimney length and combustibles.
The inner end of the chimney length shall be flush with the inside of the masonry chimney flue and shall be sealed to the flue and to the brick masonry penetration with non-water-soluble refractory cement. Supports shall be securely fastened to wall surfaces on all sides.
Fasteners between supports and the chimney length shall not penetrate the chimney liner.

Minimum Clearance: 6 in. (152mm) to combustibles
System C. Sheet steel chimney connector, minimum 24 gauge [0.024 in. (0.61 mm)] in thickness, with a ventilated thimble, minimum 24 gauge [0.024 in. (0.61 mm)] in thickness, having two 1 in. (25.4 mm) air channels, separated from combustibles by a minimum of 6 in. (152 mm) of glass fiber insulation. Opening shall be covered, and thimble supported with a sheet steel support, minimum 24 gauge [0.024 in. (0.61 mm))] in thickness.
Supports shall be securely fastened to wall surfaces on all sides and shall be sized to fit and hold chimney section. Fasteners used to secure chimney section shall not penetrate chimney flue liner.

Minimum Clearance: 2 in. (51mm) to combustibles
System D. Solid-Insulated, listed factory-built chimney length with an inside diameter 2 in. (51 mm) larger than the chimney connector and having 1 in. (25.4mm) or more of insulation, serving as a pass-through for a single-wall sheet steel chimney connector of minimum 24 gauge [0.024 in. (0.61 mm)] thickness, with a minimum 2 in. (51 mm) air space between the outer wall of chimney section and combustibles.
Minimum length of chimney section shall be 12 in. (305 mm). Chimney section concentric with and spaced 1 in. (25.4 mm) away from connector by means of sheet steel support plates on both ends of chimney section.
Opening shall be covered, and chimney section supported on both sides with sheet steel supports of minimum 24 gauge [0.024 in. (0.61 mm)] thickness.
Supports shall be securely fastened to wall surfaces on all sides and shall be sized to fit and hold chimney section. Fasteners used to secure chimney section shall not penetrate chimney flue liner.

Optional Blower

The optional blower kit (kit #WODC.BLOWB) is equipped with a three prong power cord and may be installed at any time. Follow installation instructions supplied with the kit. Route power supply cord away from heater.
Electrical rating: 115 volts A.C.-1.02 amps.
Fan output rating: 140 CFM
Blower Operation
Proper blower speed matched with air control setting will ensure peak performance from your stove. Operate as follows:

  • Air control set to “L” (low), operate blower speed control on “Low”.
  • Air control set between “L” and “H” (low and high), operate blower speed control at desired setting.

Automatic: To operate the blower automatically, set the rocker switch on the side of the fan housing to “Auto” and set the speed control to desired setting. This will allow the fan to turn on as the stove heats up to operating temperature. It will also shut the blower off after the fire has gone out and the unit cooled to below a useful heat output range.
Manual: To manually operate the blower, set the rocker switch to “Man” and set the speed control to desired setting. This will bypass the sensing device and allow full control of the blower. Switching from “Auto” to “Man” or selecting speed may be done anytime.

Mobile Home Installation

Warning: Under no circumstances is this heater to be installed in a makeshift or “temporary” manner. It may be fired only after the following conditions have been met.

  • DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
  • DO NOT INSTALL IN A SLEEPING ROOM.
  • CAUTION: THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL AND CEILING/ ROOF MUST BE MAINTAINED.
  • The stove must be achored to the floor. Use the holes located in the back of the legs.
  • Outside air supply must be used for Mobile Home installations – see Figure 6 on page 16.
  • The services of a competent or certified installer, (certified by the Wood Energy Technical Training program (WETT) – in Canada, Hearth Education Foundation (HEARTH) – in U.S.A.,) are strongly recommended.

Clearances
This heater must be installed with listed double-wall connector and compatible ULC-S629 or UL-103HT listed chimney system.
Clearances to combustible surfaces and materials are shown in Figure 12.
Consult local fire codes and authorities for approval.
NOTE: Install all chimney components to the connector and chimney manufacturer’s installation requirements. Consult your chimney supplier/manufacturer for installation advice.

Firebrick Installation

ITEM  SIZE
A …………1 1/2” X 4 1/2” X 1 1/4” …………………………………… (39 mm x 115 mm x 32 mm)
B …………4” X 4 1/2” X 1 1/4” ………………………………………… (102 mm x 115 mm x 32 mm)
C …………7 1/4” X 4 1/2” X 1 1/4” …………………………………… (184 mm x 115 mm x 32 mm)
D …………9” X 4 1/2” X 1 1/4” ………………………………………… (230 mm x 115 mm x 32 mm)
E …………9” X 4 1/2” w/ corner cut X 1 1/4” …………………….. (230 mm x 115 mm w/ corner cut x 32 mm)

  1. Begin by placing the 2 “E” bricks into the rear corners of the firebox floor (Figure 14). These trimmed bricks will fit around the two bolts coming up in the back corners. Continue by placing 2 “D” bricks beside the “E” bricks and the short “C” brick in the center up against the baffle tube (Figure 15). Eliminate any gaps between the bricks by shifting the bricks in toward the center of the firebox.

  2. On units with an ash dump, place 4 “D” bricks along the front row; 3 bricks on one side of the ash dump and 1 brick on the other side. Use the “A” and “B” bricks to fill in the area around the ash dump (Figure 16).
    • If an ash dump is not installed, use the extra “D” brick instead of the “A” and “B” bricks to fill in this space. Eliminate any gaps between the bricks by shifting the bricks in towards the center of the firebox.

  3. Slip 4 “D” bricks up behind the two protruding brick rail tabs along the rear wall (Figure 17). Eliminate any gaps between the bricks by shifting the bricks in toward the baffle tube.

  4. Place 2 “D” bricks along one of the side walls by slipping them up under the side brick rail tabs (Figure 18) and pushing to the rear, past the back brick. Place two more “D” bricks in the remaining opening at the front of the firebox and eliminate any gaps between the bricks by shifting the bricks toward the rear wall.

  5.  Complete the brick installation by repeating step 4 on the opposite side wall.

Trouble Shooting

Problem Cause Cure
Excessive CreosotBuild-up 1) Wood is too wet
  1. Turning down air control too soon
  2. Draft too low| – Use dry wood
    – Do not turn down until:
    a) there is a good bed of coals
    b) the wood is charred
    – Chimney plugged or restricted, check flue
    – Improper chimney height and/or diameter
    – Provide outside air for combustion
    – Check draft in chimney and system, alter as needed.
    Glass is Dirty| 1) See 1, 2, and 3 above
  3. Door Gasket leakage| – Replace gasket
    – Check door latch
    Low Heat Output| 1) Wood may be wet
  4. Fire too small
  5. Draft too low| – Check wood and use drier wood if required.
    – Build a larger fire
    – Open draft control to increase burn rate.
    – Chimney plugged or restricted Inspect and clean
    Won’t Burn Overnight| 1) Air control set too high
  6. Not enough wood
  7. Draft too high| – Set control lower
    – Unsplit wood is preferred for overnight burns
    – Excessive chimney height and/or diameter, see page 11
    Stove Won’t Burn| 1) Combustion air supply is blocked| – Check outside air supply for obstructions
    – Check that room air cover is removed.
    – Chimney plugged or restricted Inspect and clean

Replacement Parts – Alderlea LE

(WHEN ORDERING, INCLUDE PART NUMBER WITH DESCRIPTION)

ITEM DESCRIPTION PART NO.
1 SIDE CASTING ALT6, MBK 80000076
2 TOP ASSEMBLY (3PCS), ALT6, MBK 80000079
3 DOOR CROWN, ALT6, MBK 80000075
4 AIR CONTROL, PRIMARY 80002215
5 ASHLIP 80000074
6 GLASS CLAMPS (4) 80001555
7 GLASS C/W GASKET 80001525
8 DOOR GASKET KIT 80001503
9L DOOR ASSY (HANDLE ON LEFT) MBK 80000077
9R DOOR ASSY (HANDLE ON RIGHT) MBK 80000736
10L DOOR HANDLE, ALDERLEA (LEFT) 80000013
10R DOOR HANDLE, ALDERLEA (RIGHT) 80000014
11 BAFFLE KIT, SUMMIT LE 80002220
12 BRICK RAILS, SUMMIT LE(2) 80002221
13 PIN, BAFFLE, (10PCS) 80000364
14 GASKET, BAFFLE 80000365
15 FLAME SHIELD, SUMMIT B/LE 80000393
16 CONVECTION AIR DEFLECTOR 80002290
17 GASKET, AIR CONTROL, SECONDARY 80002222
18 AIR CONTROL, SECONDARY 80000841
19 DOOR CATCH 80001500
20 DOOR HINGE 80000889
21 ASH DUMP ASSEMBLY 80002212
22 LEG CASTING ASSY(4) 80000712
23 FIREBRICK SET, SUMMIT LE 80002223
24 MANIFOLD, BOOST, SUMMIT LE 80002224
25 ASH PAN, ALT6 80001501
26 LEG ADAPTER, ALT6 LE 80002292
27 DOOR STOP (LHS 80000233
28 DOOR PIN KIT, ALDERLEA 80000019

All parts may be ordered from your nearest Pacific Energy dealer. Visit www.pacificenergy.net for the location of the dealer nearest you.

© 2019 Copyright Pacific Energy Fireplace Products LTD.
Reproduction, adaptation, or translation without prior written permission is prohibited except as allowed under the copyright laws.

PACIFIC ENERGY FIREPLACE PRODUCTS LTD.
2975 Allenby Rd., Duncan, B.C. V9L 6V8
Phone:250-748-1184
Web site:http://www.pacificenergy.net
Printed in Canada

Documents / Resources

| PACIFIC ENERGY T6 LE Alderlea Wood Stove [pdf] Instruction Manual
T6 LE Alderlea Wood Stove, T6 LE, Alderlea Wood Stove, Wood Stove, Stove
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals