MEAN WELL MSP-200 Series 200W Single Output Medical Type Owner’s Manual

June 16, 2024
MEAN WELL

MEAN WELL MSP-200 Series 200W Single Output Medical Type

Owner’s Manual

Product Information

Specifications

  • Product Name: 200W Single Output Medical Type
  • Series: MSP-200
  • Input Voltage: Universal AC input / Full range
  • Power Factor (PF): >0.95
  • Efficiency: Up to 89%
  • Surge Input: Withstands 300VAC for 5 seconds
  • Protections: Short circuit, Overload, Over voltage, Over temperature
  • Cooling: Free air convection
  • Constant Current Limiting Circuit: Built-in
  • Profile: 1U low profile (38mm)
  • Safety Approval: Medical safety approved (MOOP level)
  • Remote ON-OFF Control: Built-in
  • Standby Power: 5V at 0.3A
  • Remote Sense Function: Built-in
  • No Load Power Consumption: <0.95/230VAC, <0.99/115VAC at full load

Product Usage Instructions

1. Installation

To install the product, follow the steps below:

  1. Select a suitable location for the product.
  2. Ensure proper ventilation around the product.
  3. Connect the product to the power source using the provided universal AC input.
  4. If required, use the built-in remote ON-OFF control to turn the product on or off.
  5. Verify that the product is securely installed and connected.
2. Operating Temperature and Humidity

The product can operate within a temperature range of -40°C to +70°C. It is important to refer to the provided Derating Curve for temperature-dependent performance. The working humidity range is 20% to 90% RH non-condensing.

3. Safety

The product has been approved for medical safety standards and complies with ANSI/AAMI ES60601-1, IEC60601-1, EAC TP TC 004, BS EN/EN60601-1, and BS EN/EN62368-1. It is recommended to follow all safety guidelines provided in the user manual.

4. Protection Features

The product is equipped with several protection features:

  • Short Circuit Protection: Automatically activates when a short circuit is detected and recovers automatically after the fault condition is removed.
  • Overload Protection: Activates when the output power exceeds 105-135% of the rated output power.
  • Over Voltage Protection: Shuts down the output voltage and recovers after re-powering.
  • Over Temperature Protection: Activates when the product exceeds the specified temperature range.

FEATURES:

  • Universal AC input / Full range
  • Built-in active PFC function, PF>0.95
  • High efficiency up to 89%
  • Withstand 300VAC surge input for 5 seconds
  • Protections: Short circuit / Overload / Over voltage / Over temperature
  • Cooling by free air convection
  • Built-in constant current limiting circuit
  • 1U low profile 38mm
  • Medical safety approved (MOOP level)
  • Built-in remote ON-OFF control
  • Standby [email protected]
  • Built-in remote sense function
  • No load power consumption<0.5W (Note.6)
  • 5 years warranty

GTIN CODE

MW Search: https://www.meanwell.com/serviceGTIN.aspx

SPECIFICATION

MODEL| MSP-200-3.3| MSP-200-5| MSP-200-7.5| MSP-200-12| MSP-200-15| MSP-200-24| MSP-200-36| MSP-200-48
---|---|---|---|---|---|---|---|---
OUTPUT| DC VOLTAGE| 3.3V| 5V| 7.5V| 12V| 15V| 24V| 36V| 48V
RATED CURRENT| 40A| 35A| 26.7A| 16.7A| 13.4A| 8.4A| 5.7A| 4.3A
CURRENT RANGE| 0 ~ 40A| 0 ~ 35A| 0 ~ 26.7A| 0 ~ 16.7A| 0 ~ 13.4A| 0 ~ 8.4A| 0 ~ 5.7A| 0 ~ 4.3A
RATED POWER| 132W| 175W| 200.3W| 200.4W| 201W| 201.6W| 205.2W| 206.4W
RIPPLE & NOISE (max.)  Note.2| 80mVp-p| 90mVp-p| 100mVp-p| 120mVp-p| 150mVp-p| 150mVp-p| 250mVp-p| 250mVp-p
VOLTAGE ADJ. RANGE| 2.8 ~ 3.8V| 4.3 ~ 5.8V| 6.8 ~ 9V| 10.2 ~ 13.8V| 13.5 ~ 18V| 21.6 ~ 28.8V| 28.8 ~ 39.6V| 40.8 ~ 55.2V
VOLTAGE TOLERANCE  Note.3| ±2.0%| ±2.0%| ±2.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.3%| ±0.3%| ±0.2%| ±0.2%| ±0.2%
LOAD REGULATION| ±1.5%| ±1.0%| ±1.0%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
SETUP, RISE TIME| 1000ms, 50ms/230VAC          2500ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.)| 16ms/230VAC          16ms/115VAC at full load
INPUT| VOLTAGE RANGE          Note.5| 85 ~ 264VAC          120 ~ 370VDC
FREQUENCY RANGE| 47 ~ 63Hz
POWER FACTOR (Typ.)| PF>0.95/230VAC          PF>0.99/115VAC at full load
EFFICIENCY (Typ.)| 80%| 84%| 86%| 88%| 88%| 88%| 89%| 89%
AC CURRENT (Typ.)| 2.2A/115VAC        1.1A/230VAC
INRUSH CURRENT (Typ.)| 35A/115VAC          70A/230VAC
LEAKAGE CURRENT     Note.7| Earth leakage current < 300μA/264VAC , Touch leakage current < 100μA/264VAC
PROTECTION| OVERLOAD| 105 ~ 135% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE| 3.96 ~ 4.62V| 6 ~ 7V| 9.4 ~ 10.9V| 14.4 ~ 16.8V| 18.8 ~ 21.8V| 30 ~ 34.8V| 41.4 ~ 48.6V| 57.6 ~ 67.2V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION| 5V STANDBY| 5VSB : [email protected] ; tolerance±5%, ripple : 50mVp-p(max.)
REMOTE CONTROL| RC+/RC- : 4 ~10V  or open = power on ; 0 ~ 0.8V  or short = power off
ENVIRONMENT| WORKING TEMP.| -40 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC
(Note 4)| SAFETY STANDARDS| ANSI/AAMI ES60601-1, IEC60601-1, EAC TP TC 004 approved, Design refer to BS EN/EN60601-1, BS EN/EN62368-1
ISOLATION LEVEL| Primary-Secondary: 2×MOOP, Primary-Earth: 1×MOOP
WITHSTAND VOLTAGE| I/P-O/P:4KVAC     I/P-FG:2KVAC     O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃ / 70% RH
EMC EMISSION| Compliance to BS EN/EN55011 (CISPR11) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN60601-1-2, EAC TP TC 020
OTHERS| MTBF| 1609.5K hrs min.      Telcordia SR-332 (Bellcore) ; 186.2K hrs min.      MIL-HDBK-217F (25℃)
DIMENSION| 1999838mm (LWH)
PACKING| 0.77Kg; 18pcs/14.9Kg/0.87CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re- confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. No load power consumption<0.5W when RC+ & RC- (CN100 pin1,2) 0 ~ 8V or short.
7. Touch current was measured from primary input to DC output.
8. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Mechanical Specification

Block Diagram

Derating Curve

Output Derating VS Input Voltage

Function Description of CN100

Pin No. Function Description
1 RC+ Turns the output on and off by electrical or dry contact between pin 2

(RC-). Short: Power OFF, Open: Power ON.
2| RC-| Remote control ground
3| AUX| Auxiliary voltage output, 4.75~5.25V, reference to pin 4(AUXG). The maximum load current is 0.3A. This output has the built-in oring diodes and is not controlled by the “remote ON/OFF control”.
4| AUXG| Auxiliary voltage output ground. The signal return is isolated from the output terminals (+V & -V).
5|  +S| Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
6|  -S| Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.

Function Manual

1.Remote Control

The PSU can be turned ON/OFF by using the “Remote
ON/OFF” function

Between RC-(pin2) and RC+(pin1) Output Status
SW ON (Short) OFF
SW OFF (Open) ON

2. Remote Sense

The remote sensing compensates voltage drop on the load wiring up to 0.5V.

Downloaded from Arrow.com.

File Name:MSP-200-SPEC 2022-09-20

Frequently Asked Questions (FAQ)

Q: What are the dimensions of the product?

A: The dimensions of the product are 199mm (length) x 98mm (width) x 38mm (height).

Q: What is the weight of the product?

A: The weight of the product is 0.77kg.

Q: What is the packaging information?

A: The product is packed in a box with a weight of 14.9kg and a volume of 0.87 cubic feet. Each box contains 18 units.

Q: What is the MTBF (Mean Time Between Failures) of the product?

A: The MTBF of the product is 1609.5K hours minimum according to Telcordia SR-332 (Bellcore) and 186.2K hours minimum according to MIL-HDBK-217F (25).

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>