B E G PSN-230 Power Supply Installation Guide

June 15, 2024
B E G

**B E G PSN-230 Power Supply Installation Guide

**

PSN-230/640/30/KNX REG

                      Code 90214
Safety instructions
Work on the mains supply may only be carried out by qualified professionals

or by instructed persons under the direction and supervision of qualified skilled electrical personnel in accordance with electrotechnical regulations.
| Disconnect supply before installing!
| Observe the country-specific regulations as well as the valid KNX guidelines.
| Read this supplementary sheet before putting the device into operation. Knowledge of this supplement is part of the intended use!
| Operation
| The PSN-230/640/30/KNX REG is a 640 mA KNX power supply with high effi ciency and small dimensions of only 52.5 mm.
| The device has a KNX bus output and an additional output for auxiliary power (30V DC). The wide temperature operating range from -5°C to +50°C can meet all kinds of applications. Integrated LED are used for indication of normal operation, overload conditions and RESET operation.
90214| Device Overview
---|---
1| KNX bus terminals (Red : BUS +V, Black: BUS –V)
2| Auxiliary power terminal (30 V DC)
3| RESET button
4| AC terminals (L, N, )
5| ON (power on, green LED)
6| Reset (red)
7| I > Imax (red)
| Reset / Error
Fig. 1| Reset : To carry out a reset, press the RESET button for at least 20 seconds to reset the KNX power supply.
Fig. 1| Error: If the red LED (I > Imax) lights up when mains voltage is applied, an error has occurred. This means that the KNX output is overloaded or short-circuited. The problem can be solved by removing the cause of the short circuit or by reducing the number of KNX devices connected to the line. Once the fault has been rectified, carry out a reset by pressing the RESET button for approx. 20 seconds.
(L, N, , +V, -V)| AC and auxiliary power terminals
0.5 – 4.0 mm2| Solid wire
0.5 – 2.5 mm2| Stranded wire
12 – 26 AWG| American wire gauge
6.5 mm (0.255”)| Wire stripping length
3 mm| Screwdriver
0.78 Nm (7 lbf in)| Recommended tightening torque
| KNX-BUS terminal
0.6 – 0.8 mm2| Solid wire
20 – 22 AWG| American wire gauge
5 mm (0.196”| Wire stripping length
90214| Mounting
---|---
| Place the power supply onto the DIN rail (TS35/7.5 or TS35/15)
Fig. 1| Connect to KNX. The connection to the KNX BUS line is made with the bus terminal located on the left upper part of the front side.
| Putting into operation
| § Use wires with an adequate cross-section. § Use suitable mounting tools to do the wiring and mounting. § The maximum number of devices connected to the bus is 64. § The maximum length of a line segment is 350 m, measured along the line between the power supply and the farthest bus device. § The maximum distance between two bus devices must not exceed 700 m. § The maximum length of a bus line is 1000 m, keeping into account all segments. § The device does not require any confi guration with the ETS® (Engineering Tool Software) tool. Once the wiring is proper done, the ON LED will light up and the other LEDs remain off to indicate that the device is in operation.
| LED function indicators
Fig. 1| Ready for operation or working normally § LED a/green shines
Resetting § LED b/red shines
Output current too high § LEDs a/green and c/red shine
Short-circuit or bus reverse polarity § LED c/red shines
No mains voltage § all LEDs off
| UK declaration of conformity
| This product respects the directives concerning 1. Electrical Equipment Safety Regulation 2016 2. Electromagnetic Compatibility Regulation 2016 3. The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulation 2012
Contact
B.E.G. UK Ltd., Apex Court – Grove House • Camphill Road • West Byfl eet, Surrey KT14 6SQ
90214| Technical data
---|---
200 – 240 V AC| Input voltage
30 V DC + KNX BUS| Output voltage
0.5 W| Power consumption
200 ms| Mains failure back-up time
| Protections: Short circuit/ Overload (shortcircuit-proof)/ Over voltage
| Cooling: by free air convection
| LED indicator for normal operation, bus reset and bus overload
DIN rail| Installation on DIN TS-35/7.5 or 15
I / IP20| Class / Degree of protection
PC| Housing
90 x 52.5 x 58 mm| Dimensions
-5 °C – +50 °C| Ambient temperature
| Wiring diagram
| Schematic diagram – when connecting the detector, please respect the labelling of the terminal connections at the device.
| Product page on the Internet

Documents / Resources

| B E G PSN-230 Power Supply [pdf] Installation Guide
PSN-230 Power Supply, PSN-230, Power Supply, Supply
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals