B E G 93541 120-BMS LUXOMAT ALI-2 LC Mini Installation Guide
- June 13, 2024
- B E G
Table of Contents
B E G 93541 120-BMS LUXOMAT ALI-2 LC Mini
Safety instructions
Work on the mains supply may only be carried out by qualified professionals
or by instructed persons under the direction and supervision of qualified
skilled electrical personnel in accordance with electrotechnical regulations.
Disconnect supply before installing! This device is not to be used to isolate
other equipment from the mains supply.
DALI is not SELV – the
installation instructions for low voltage apply. The DALI screw clamps must
not be connected to 230 VAC!
Read this supplementary sheet
and the operating instructions before putting the device into operation.
Knowledge of these documents is part of the intended use!
Operation
DALI-2 multisensory (Input
Device) with multi-directional 120° detection area. Adjustable ball head.
Powered via DALI bus.
Addressable according to IEC 62386 Part 103 (control device). Instance 0
provides information regarding occupancy and movement for the DALI bus
according to IEC 62386 part 303. Instance 1 provides LUX values for the DALI
bus according to IEC 62386 part 304. Parameterization is possible via
mandatory Multimeter-Application-Controller of any manufacturer. This
controller must support IEC 62386 parts 101/103/303/304.
Mounting hints
Remove the detector from the mounting base using a slotted screwdriver.
Fix the mounting socket on a solid plane using two screws (please take care with cable introduction).
The detection range or the detection area can be modified by rotating the detector head vertically and horizontally (detector head horizontal = max. detection range)
Initial operation
General: The device can be put into service directly after mounting, following the software instructions from the relevant controller manufacturer.
Exclude sources of interference
In case the detection area of the detector is too large or areas are being covered that should not be monitored, the range can be reduced or limited by using the enclosed blinds
Self-test cycle
During the first 20 sec after connecting to the DALI bus power, the product will enter a self-test cycle. During this time the device does not respond to movement.
LED function indicators
-
Shortly on:
A Green Movement
B Red –
C White – -
Flashing:
A Green Localization
B Red Initialization
C White Localization
D Red Localization
Technical data
| Settings: via application which supports DALI multisensors (IEC 62386 parts
101, 103, 303, 304).
---|---
| Voltage
7 mA| Typ. power input
0.5 W| Power consumption
| Terminal clamps: for solid one-wire conductors
120°| Detection area horizontal
2 m/3 m/2.5 m| Mounting height min. /max. / recommended
2.5 m 18°C 1 = max. Ø 10 m 2 = max. Ø 4 m
| Range of coverage at
mounting height
Ambient temperature
- across
- towards
105 m2| Monitored surface, when the detector is mounted at 1.1 m
mounting height and for tangential approach
II / IP44| Class /Degree of protection
80 x 70 x 55 mm| Dimensions
-25°C – +50°C| Ambient temperature
0 – 4095 Lux| Measured light output
Wiring diagram
Schematic diagram – when connecting the detector, please respect the labelling of the terminal connections at the device!
U Declaration of conformity
This product respects the directives concerning
- electromagnetic compatibility (2014/30/EU)
- low voltage (2014/35/EU)
- restriction of the use of certain hazardous substances in electrical and electronic equipment (2011/65/EU)
Accessory
Wire basket BSK (Ø 164 x 143 mm), whit
Trouble shooting
-
Power consumption on DALI line too high
Please be aware of the total power consumption of all the DALI units in your system. -
Heat sources in the vicinity
I f , for example, the detector is located in the immediate vicinity of ventilation slits or a projector, the warm air currents can trigger motion detection. Place the detector at a sufficient distance from potential sources of interference such as ventilation slits, projectors, beamers etc.
Customer Support
Brück Electronic GmbH I Gerberstr. 33 I 51789 Lindlar I GERMANY I Phone: +49 (0) 2266 90121-0 I Fax: +49 (0) 2266 90121-50 I info@beg.deIbegluxomat.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>