Safety instructions
Work on the mains supply may only be carried out by qualified professionals or by instructed persons under the direction and supervision of qualified skilled electrical personnel in accordance with electrotechnical regulations
Disconnect supply before installing! This device is not to be used to isolate other equipment from the mains supply.
DALI is not SELV – the installation instructions for low voltage apply. The DALI screw clamps must not be connected to 230VAC!
After inserting the connection cables, plug on the supplied cover.
Read this supplementary sheet and the operating instructions before putting
the device into operation. Knowledge of these documents is part of the
intended use!
Oeration
Occupancy detector with integrated DALI application controller for energy-
efficient lighting control. DALI-2 certified product. Integrated DALI power
supply. DALI interface for controlling digital, dimmable ECGs in broadcast
mode. Manual switching or dimming via conventional pushbuttons. Bidirectional
IR communication enables fast integration into the project management function
of the B.E.G. One app.
Complete range of functions can only be activated using the BLEIR-Adapter and a compatible Smartphone or Tablet (Android, iOS). Factory setting 10 min follow-up time and 500 lux brightness set value. Single master version, not networkable. Detection area can be extended with slave devices.
Number of DALI participants can be determined quickly and reliably via the B.E.G. Online DALI Line Planner. For a reliable calculation, it is recommended to always use 80% of the guaranteed output current as a basis.
Mounting
Range of coverage/Product Code
| 1| 2| 3
---|---|---|---
2.50m| Ø 24.00m| Ø 8.00m| Ø 6.40m
5.00m| Ø 48.00m| Ø 16.00m| –
Mounting hints
Overview
Fig. 1a : Device is inserted into false ceiling
Fig. 1b: The device is attached to a flush-mounted box
Fig. 1c : Device is mounted on SM adapter
When replacing the cover, please take care that the opening for light sensor 1 is placed on the same
Fig. 2: Blinds (e) are clipped to restrict detection area.
Fig. 3 : Light sensor 1 for point light measurement, light sensor 2 for ambient light measurement.
Exclude sources of interference
In case the detection area of the detector is too large or areas are being covered that should not be monitored, the range can be reduced or limited by using the enclosed blinds.
LED function indicators
Process | Indication |
---|---|
Initialization time | Red flashes for 60s |
Load factory settings | Running light for 30s, then: Red flashes for 30s |
Read out device (send IR) | Red flickers |
Motion detection | Red flashes for each detected motion |
Brightness set value exceeded | Green flashes 2x per 1s |
Light calibration active | Green flashes every 10s |
Semi-automatic mode active | White lights up permanently |
Corridor mode active | White flashes every 3s |
Error detected ( device or bus) | Red/green/ white flash simultaneously |
Accessory
93067 | BLE-IR-Adapter |
---|---|
92094 | IR-PD-DALI |
92652 | IR-PD-DALI-LD |
92122 | IR-PD-DALI-E |
92112 | IR-PD-DALI-Mini |
92199 | Wire basket BSK / white |
93465* | SM socle mounting set IP54 PD4N H / white |
93732* | Iens PD4N, Cover ring / traffic white |
93073* | Corridor lens PD4N type A / white |
93164* | Wall holder PD2N/4N Typ A / white |
93192* | SM socket for Wall holder / white |
Technical date
230 V AC ±10% 50 Hz | Voltage |
---|---|
Ø 106 x 95 mm | Dimensions |
ca. 2 W | Power consumption |
max. 8 | Slave devices |
horizontal 360° | Detection area |
30 m x 19 m | Reichweite bei |
- quer
- frontal
- sitzende Tätigkeit
450 m² / 2,5 m| Monitored area (tangential movement)
2 m / 10 m / 2,5 m| Mounting height min./max./ recommended
| Terminal clamps: for solid one-wire conductors
IP20 / II| Degree/Class of protecti
25°C – +50 °C| Ambient temperature
PC| Housing material
Channel 1 (lighting control)
80mA max. 125mA | DALI output |
---|---|
DT0, DT5, DT6, DT7 | Supported control gear |
– (Single Master) | Supported control devices |
1 min – 150 min | Follow-up time |
10 – 30 % / 1 – 60 min / ∞ / OFF | Orientation light |
10 – 2500 Lux | Brightness set value |
Mixed light measuring |
Factory settings
10 min| Follow-up time
500 Lux| Brightness set value
Wiring diagram
EU Declaration of conformity
This product respects the directives concerning
- Electrical Equipment Safety Regulation 2016
- Electromagnetic Compatibility Regulation 2016
- The Restriction of the Use of Certain Hazardous Substances
in Electrical and Electronic Equipment Regulation 2012
Contact
- B.E.G. UK Ltd., Apex Court –
- Grove House • Camphill Road •
- West Byfleet, Surrey KT14 6SQ
Product page on the internet
LUXOMAT® PD4N-M-DACO DALI-2 93460
Documents / Resources
| B E
G 93460 LUXOMAT PD4N-M-DACO
Dali-2
[pdf] Instruction Manual
93460, 93460 LUXOMAT PD4N-M-DACO Dali-2, 93460 Dali-2, LUXOMAT PD4N-M-DACO
Dali-2, PD4N-M-DACO Dali-2, LUXOMAT Dali-2, Dali-2
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>