PYLONTECH US3000C Rechargeable Lion Battery Instruction Manual

June 15, 2024
PYLONTECH

Rechargeable Li-ion Battery
US3000C Operation Manual
UL versionPYLONTECH US3000C Rechargeable Lion Battery Information Version: V1.0
5PMPA08-00221

This manual introduces US3000C from Pylontech. Please read this manualbefore you to install the battery and follow the instruction carefully during the installation process. Any confusion, please contact Pylontech immediately for advice and clarification.

Symbols in label, manual and product

| Do not reverse connection the positive and negative.
---|---
| Do not place near open flame.
| Do not place at the children and pet touchable area.
| Warning electric shock.
| Warning Fire.
Do not place near flammable material
| Read the product and operation manual before operating the battery system!
| Grounding.
| Recycle label.
| The certificate label for EMC.
****| Label for Waste Electrical and Electronic Equipment (WEEE) Directive (2012/19/EU)
| The certificate label for Safety by TÜV Rheinland.
| The certificate lablel for Safety by CSA

Safety

The US3000C is operated by authorized person only. Read all safety instructions carefully prior to any work and observe them at all times when working on with the system.
Incorrect operation or work may cause:

  1. Injury or death to the operator or a third party
  2. Damage to the system hardware and other properties belonging to the operator or a third party.

Qualified personnel must have the following skills:

  1. Training in the installation and commissioning of the electrical system, as well as the dealing with hazards
  2. Knowledge of the manual and other related documents
  3. knowledge of the local regulations and directives.

Symbol

Danger| Lethal voltage! Tension mortelle!
Battery strings will produce high voltage DC power and can cause a lethal voltage and an electric shock.
Only qualified person can perform the wiring of the battery strings.
---|---
 Warning| Risk of battery system damage or personal injury
DO not pull out the connectors while the system is working!
De-energize from all multiple power sources and verify that there is no voltage.
Caution| Risk of battery system failure or life cycle reduces.
| Read the product and operation manual before operating the battery system!

Danger
Batteries deliver electric power, resulting in burns or a fire hazard when they are short circuited, or wrongly installed.
Lethal voltages are present in the battery terminals and cables. Severe injuries or death may occur if the cables and terminals are touched.
Do not connect battery with PV solar wiring directly.
It is prohibited to connect the battery and AC power directly.
In case of fire, only dry powder fire extinguisher can be used, liquid fire extinguishers are prohibited.
Warning
Do not open or deform the battery module; It is prohibited to disassemble the battery (QC tab removed or damaged).
For battery installation, the installer shall refer to NFPA70 standard for operation.
Do not expose cable outside
Any foreign object is prohibited to insert into any part of battery.
Do not expose battery to flammable or harsh chemicals or vapors; Keep the battery away from water and fire.
The embedded BMS in the battery is designed for 48VDC, please DO NOT connect battery in series.
Caution
Improper settings or maintenance can permanently damage the battery. Incorrect inverter parameters will lead to the premature aging of battery.
Battery needs to be recharged within 12 hours, after fully discharged.
Do not use cleaning solvents to clean battery.
Do not paint any part of battery, include any internal or external components.
Please contact the supplier within 24 hours if there is something abnormal.
The warranty claims are excluded for direct or indirect damage due to items above.
After unpacking, please check product and packing list first, if product is damaged or lack of parts, please contact with the local retailer.
Please ensured the electrical parameters of battery system are compatible to related equipment, such as charger, inverter or load.
Make sure the settings on inverter are correct for US3000C.
If possible, check the communication between battery system and inverter is working normally
Caution before connecting
Before installation, be sure to cut off the grid power and make sure the battery is in the turned-off mode.
Wiring must be correct, do not mistake the positive and negative cables, and ensure no short circuit with the external device.
Battery system must be well grounding and the resistance must be less than 0.1Ω
Caution in using

If the battery system needs to be moved or repaired, the power must be cut off and the battery is completely shut down.
It is prohibited to connect the battery with different type of battery.
Please do not open, repair or disassemble the battery except staffs from Pylontech or authorized by Pylontech. We do not undertake any consequences or related responsibility which because of violation of safety operation or violating of design, production and equipment safety standards.

Introduction

US3000C lithium iron phosphate battery is the new energy storage products developed and produced by Pylontech, it can be used to provide reliable power for various types of equipment and systems.
US3000C has built-in BMS battery management system, which can manage and monitor cells information including voltage, current and temperature.
3.1 Features

  1. NEW: Build-in soft-start function able to reduce current strike when inverter need to start from battery.
  2. NEW: Dual active protection on BMS level.
  3. NEW: Automatic address setting when connect in multi-group.
  4. NEW: Support wake up by 5~12V signal from RJ45 port.
  5. NEW: Support upgrade battery module from upper controller via CAN or RS485 communication.
  6. NEW: Enable 95% depth of discharge, available for the inverter which completely follow Pylontech latest protocol to operate.
  7. The module is non-toxic, non-polluting and environmentally friendly
  8. Cathode material is made from LiFePO4 with safety performance and long cycle life
  9. Battery management system (BMS)has protection functions including overdischarge, over-charge, over-current and high/low temperature
  10. The system can automatically manage charge and discharge state and balance voltage of each cell
  11. Flexible configuration, multiple battery modules can be in parallel for expanding capacity and power
  12. Adopted self-cooling mode rapidly reduced system entire noise
  13. The module has less self-discharge, up to 6 months without charging it on shelf, no memory effect, excellent performance of shallow charge and discharge
  14. Small size and light weight, standard of 19-inch embedded designed module is comfortable for installation and maintenance
  15. Compatible with the US2000C, US3000, and US2000.

Mixture using master battery priority: US3000C>US2000C>US3000>US2000
For same type of module always use the latest production unit as master.
Mixture using battery deployment option:

Master battery (1st) US3000C/US2000C
Slave 2nd ~8th US3000C/US2000C/US3000/US2000
Slave 9th ~16th US3000C/US2000C

3.2 Specifications

PYLONTECH US3000C Rechargeable Lion Battery -
Specifications

Basic Parameters US3000C
Nominal Voltage (V) 48
Nominal Capacity (Wh) 3552
Usable Capacity (Wh) 3374.4
Dimension (mm) 442420132
Weight (Kg) 32
Discharge Voltage (V) 44.5 ~ 53.5
Charge Voltage (V) 52.5 ~ 53.5
Recommend Charge/Discharge Current(A) 37
Max. Charge/Discharge Current (A) 74-89@60sec
Peak Charge/Discharge Current (A) 90~200@15sec
Communication RS485, CAN
Depth of discharge (%) 95
Configuration (max. in 1 battery group) 16pcs
Working Temperature ( ℃) 0℃~50 ℃ Charge

-10 ℃~50 ℃ Discharge
Shelf Temperature ( ℃)| -20~60
Short current/duration time| <4000A/2ms
Cooling type| Natural
Protective class| I
IP rating of enclosure| IP20
Humidity (% RH)| 5 ~ 95(No Condensation)
Altitude(m)| <4000
Certification| TÜV / CE / UN38.3/UL
Design life (year)| 15+(25℃/77 ℉)
Cycle Life (cycle)*| >8,000 25 ℃
Reference to standards| IEC62619, IEC63056, IEC62040, IEC62477-1, UL1973, UL1642, UL9540A, VDE2510-50, IEC61000-6-2, IEC61000-6-3, UN38.3

  • Cycle Life is defined based on specific operation conditions, for more details please check with Pylontech service team.
    3.3 Equipment interface instruction

PYLONTECH US3000C Rechargeable Lion Battery -
interface

Power Switch
ON: ready to turn on.
OFF: power off. For storage or shipping.
Start
Turn on: press more than 0.5s to start the battery module
Turn off: press more than 0.5s to turn off the battery.
RUN
Green LED lighting to show the battery running status
Alarm
Red LED flashing to show the battery has alarm; lighting to show the battery is under protection.
SOC
6 green LEDs to show the battery’s current capacity.
ADD Switch
Dip1: RS485 baud rate: 1: 9600; 0: 115200. After change, please restart battery.
Dip2: CAN terminal resistance on BMS side. 1: NONE. 0: connected. After change, no restart required. In single group mode, please keep dip2 at 0 position. For multi-groups, please refer to [5.9].
Dip3~4, reversed.
Based on design of BMS, the dip switch is deployed physically reversely.
For instance:

Dip1 Dip2 Dip3 Dip4 The corresponding position of switch Status
0 0 0 0 RS485:115200

CAN terminal resistance: connected
1| 0| 0| 0| | RS485:9600
CAN terminal resistance: connected
0| 1| 0| 0| | RS485: 115200
CAN terminal resistance: NONE

Console
For manufacturer or professional engineer to debug or service.

Pin3 232-TX
Pin4* +5~+12V for wake up
Pin5* GND for wake up
Pin6 232-RX
Pin8 232-GND

*Wake up signal shall ≥0.5Sec, current between 5~15mA. After send wake up signal, the voltage shall disappear for normal operation.
Contact

Pin1 Input, passive signal. On: turn off battery. Off: normal.

Pin2
Pin3| Output1. On: stop charge.| +
Pin4| –
Pin5| Output2. On: stop discharge.| +
Pin6| –
Pin7| Output3. On: BMS error.| +
Pin8| –

Output request signal voltage ≤25V
CAN
500 Kbps. 120Ω recommended. For connection to LV-HUB, inverter, or upper battery.
RS485
9600 or 115200 bps.120Ω recommended. For connection to inverter, or slave battery.
Link Port 0, 1
for communication between multiple parallel batteries.
Definitions of RJ45 Port Pin

PYLONTECH US3000C Rechargeable Lion Battery - Port Pin

| A/CAN| B/RS485
---|---|---
Pin1| These pins shall be NULL.
If not, may influence communication between BMS and inverter.
 Pin2
Pin3
Pin4| CAN-H| CAN-H (single group)
Pin5| CAH-L| CAN-L (single group)
Pin6| CAN-GND| CAN-GND (single group)
 Pin7| NA| 485A
Pin8| NA| 485B

Power Terminals
Power cable terminals: there are two pair of terminals withsame function, one connects to equipment, the other oneparalleling to other battery module for capacity expanding.

Caution
Must keep pressing the “Lock Button” while pulling out the power plug.
LED Status Indicators

Condition RUN ALR 1 2 3 4 5 6
Power off
Power on **** **** **** **** **** **** **** ****
Idle/Normal ****
Charge ****
Discharge ****
Alarm ALR: ****●; Other LEDs are same as above.
System error/Protect ****
/ ON
**** flash, on: 0.3s; off: 3.7s
/ flash, on:0.5s; off: 1.5s

BMS basic function

Protection and alarm Management and monitor
Charge/Discharge End Cells Balance
Charge Over Voltage Intelligent Charge Model
Discharge Under Voltage Charge/Discharge Current Limit
Charge/Discharge Over Current Capacity Retention Calculate
High/Low Temperature(cell/BMS) Administrator Monitor
Short Circuit Operation Record
Power Cable Reverse
Soft start of inverter

Safe handling of lithium batteries guide

4.1 Schematic diagram of solution

PYLONTECH US3000C Rechargeable Lion Battery - diagram

4.2 Danger label

DANGER
DANGER LOW DCVOLTAGE INSIDE
DANGER ARC FLASH & SHOCK HAZAR.

PYLONTECH US3000C Rechargeable Lion Battery - Symbol
11

  • Do not disconnect, disassemble or repair by yourself.
  • Do not drop, deform, impact cut or spearing with a sharp object.
  • Do not place near open flame or incinerate.
  • Do not sit or put heavy things on battery
  • Keep away from moisture or liquid.
  • Keep out of reach of children, animals or insects.
  • Maximum voltage: 54 V
  • In gase of fire, only oy powder fire extinguisher can be used, liquid fire

4.3 Tools

| |
---|---|---
Wire cutter| Crimping modular plier| Screwdriver

NOTE
Use properly insulated tools to prevent accidental electric shock or short circuits. If insulated tools are not available, cover the entire exposed metal surfaces of the available tools, except their tips, with electrical tape.
4.4 Safety gear
It is recommended to wear the following safety gear when dealing with the battery pack

| |
---|---|---
Insulated gloves| Safety goggles| Safety shoes

Installation and operation

5.1 Package items
Unpacking and check the Packing List

  1. For battery module package:
    – Battery ModulePYLONTECH US3000C Rechargeable Lion Battery - Battery
Module– Two 4AWG power cables and one RJ45 communication cablePYLONTECH US3000C Rechargeable Lion Battery - power
cables– 10AWG grounding cablePYLONTECH
US3000C Rechargeable Lion Battery - grounding cable

  2. For External cable kits:
    NOTE
    Power and communication cables to connect to inverter belongs to an External Cable Kit, NOT include in battery carton box. They are in another extra small cable box. If there is anything missed please contact dealer. Two power cables (4 AWG, peak current capacity 120A, constant 100A) and communication cable for each energy storage system

PYLONTECH US3000C Rechargeable Lion Battery - communication
cables

For the external cables, the length shall less than 3 meters.

SN of RJ45cable| Mark| Pin|
---|---|---|---
WI0SCAN30RJ1| With blue mark: Battery-Inverter| Pin1~3: NULL
Pin4~8: pin to pin| For connection to inverter
WI0SCAN35RJ3| With silver mark: Battery-Battery| Pin1~8: pin to pin| For parallel connection between master batteries

5.2 Installation location
Make sure that the installation location meets the following conditions:

  1. The area is completely waterproof
  2. The floor is flat and level.
  3. There are no flammable or explosive materials.
  4. The ambient temperature is within the range from 0°C to 50°C.
  5. The temperature and humidity are maintained at a constant level.
  6. There is minimal dust and dirt in the area.
  7. The distance from heat source is more than 2 meters.
  8. The distance from air outlet of inverter is more than 0.5 meters.
  9. The installation areas shall avoid of direct sunlight.
  10. There are no mandatory ventilation requirements for battery module, but please avoid of installation in confined area. The aeration shall avoid of high salinity, humidity or temperature.

Caution
If the ambient temperature is outside the operating range, the battery pack stops operating to protect itself. The optimal temperature range for the battery pack to operate is 0°C to 50°C. Frequent exposure to harsh temperatures may deteriorate the performance and life of the battery pack.
5.3 Grounding
Grounding cables shall be 10AWG or higher yellow-green cables. After connection, the resistance from battery grounding point to Ground connection point of room or installed place shall smaller than 0.1Ω.

  1. based on metal directly touch between the module’s surface and rack’s surface. If using painted rack the corresponding place shall remove the painting.
  2. install a grounding cable to the grounding point of the modules.

Warning
Grounding is necessary.

5.4 Put into cabinet or racks
Put battery modules into cabinet and connect the cables:

PYLONTECH US3000C Rechargeable Lion Battery - cabinet

  1. Put the battery into the cabinet
  2. Drive the 4 pcs screws
  3. Connect the cables between battery modules
  4. Connect the cables to inverter

PYLONTECH US3000C Rechargeable Lion Battery - inverter

5.5 Put into bracket

PYLONTECH US3000C Rechargeable Lion Battery - bracket

  1. Dismantle the 2 holders of battery.PYLONTECH US3000C Rechargeable Lion Battery - Dismantle
  2. Put the battery into 2 pcs of bracket.PYLONTECH US3000C Rechargeable Lion Battery - bracket 2
  3. Use 4 location holes, stack the batteries together. And connect the 4 locker together.PYLONTECH US3000C Rechargeable Lion Battery - location hole
  4. Maximum 4 in stack.PYLONTECH US3000C Rechargeable Lion Battery - stack

NOTE
All the installation and operation must follow local electric standard.
After installation, do not forget to register online for full warranty: http://www.pylontech.com.cn/service/support
**
Warning
The power cables’ current capacity is 120A max. If the battery string’s design current over 100A, it must configure 2 pare external power cables to extend current capacity.
Follow local electric safety and installation policy, a suitable manual disconnecting device (breaker, etc.) between battery system and inverter could be required.
5.6 Suitable breaker**

  1. The rated voltage shall ≥60V DC. Do NOT use AC breaker.
  2. The type of breaker shall be type C (recommended) or type D.
  3. The rated current shall match with system design: shall consider the DC current on inverter side. the number of power cable: for instance, if only one pair of 4awg cable, the rated current of breaker shall be 125A or smaller.
  4. The Icu required: the short circuit current for calculation of each module is 2500A. for instance:

| Icu of breaker
---|---
1~4 modules| Must ≥10kA
5~8 modules| Must ≥20kA

5.7 Power on
Double check all the power cable and communication cable.

  1. Switch on all the battery modules:PYLONTECH US3000C Rechargeable Lion Battery - Power
  2. The one with empty Link Port 0 is the Master Battery Module, others are slaves (1 master battery configure with maximum 15 slave batteries):PYLONTECH US3000C Rechargeable Lion Battery - Master Battery
  3. Press the red SW button of master battery to power on, all the battery LED light will be on one by one from the Master battery:PYLONTECH US3000C Rechargeable Lion Battery - SW button

Note:

  1. After the battery module powered on, the soft-start function takes 3sec to active. After soft-starts battery ready to output high power.
  2. During capacity expansion or replacement, when parallel different SOC/voltage of module together, please maintain the system in idle for ≥15mins or till the SOC LEDs becomes similar (≤1dot difference) before normal operation.

5.8 Power off

  1. Turn external power source off.
  2. Press red SW switch of master battery. Then all batteries will off.
  3. Switch Power switch OFF.

5.9 Multi-group mode
By RS485: DO NOT need LV-HUB.
Connect power cable first:

  1. each pair of cable hold max 100A constant current. Connect enough pairs of cable based on calculation of system current.

  2. Suitable protection breaker between battery system and inverter is required.PYLONTECH US3000C Rechargeable Lion Battery - protection breaker

  3. Make sure all dip switch of master batteries are R0XX, then turn ON batteries.
    R: is the baud rate of RS485 needed, all master batteries shall be the same.

  4. After all batteries running and buzzer of master battery in group1 rings 3 times. Means all groups are online.

The interruption of each RS485 command shall at least ≥1s.
Multiple Battery Groups RS485 Communication Cable Connection
Max 6 groups

  1. The A/CAN of 1% group/master battery connects to inverter or EMS(pin: 7A, 8B, DO NOT connect other pins)
  2. The B connect to A of next group; the B/RS485 of last group master battery is empty.

PYLONTECH US3000C Rechargeable Lion Battery -
interruption

By CAN:
Connect power cable first:

  1. each pair of cable hold max 100A constant current. Connect enough pairs of cable based on calculation of system current.
  2. Suitable protection breaker between battery system and inverter is required.
  3. connect power cable of LV-HUBPYLONTECH US3000C Rechargeable Lion Battery - power cable
  4. Make sure all dipswitch is X0XX, then turn ON batteries.
  5. After all batteries running and buzzer of master battery in group1 rings 3 times. Means all groups are online.
  6. Change the dip switch of master battery in group1 to X1XX. Then connect communication cable between LV-HUB and master battery in group 1.
  7. Then turn ON LV-HUB.
    Detailed information please refer to manual of LV-HUB.

PYLONTECH US3000C Rechargeable Lion Battery - LV HUB

Trouble shooting

– Communication related problem
Unable to communicate with inverter on compatible list.
Possible conditions:

  1. RS485: baud rate. Check the dip switch1, set to correct one, and restart. All master battery shall be the same.
  2. CAN: terminal resistance. Check the dip switch2, set to 0 and retry.
  3. CAN: pin. Try connect the CAN-H, L, GND only and do not connect other pins to inverter.

– Functional related problem

  1. Whether the battery can be turned on or not
  2. If battery is turned on, check the red light is off, flashing or lighting
  3. If the red light is off, check whether the battery can be charged/discharged or not.

Possible conditions:

  1. Battery cannot turn on, switch ON and press the red SW the lights are all no lighting or flashing.
    a) Capacity too low, or module over discharged.
    solution: use a charge or inverter to provide 48-53.5V voltage. If battery can start, then keep charge the module and use monitor tools to check the battery log.
    If battery terminal voltage is ≤45Vdc, please use ≤0.05C to slowly charge the module to avoid affect to SOH.
    If battery terminal voltage is >45Vdc, it can use ≤0.5C to charge.
    If battery cannot start, turn off battery and repair.

  2. The battery can turn on, but red light is lighting, and cannot charge or discharge. If the red light is lighting, that means system is abnormal, please check values as following
    b) Temperature: Above 60 ℃ or under -10 ℃, the battery could not work.
    Solution: to move battery to the normal operating temperature range between 0 ℃ and 50 ℃
    c) Current: If current exceeds 90A, battery protection will turn on.
    Solution: Check whether current is too large or not, if it is, change the settings on power supply side.
    d) High Voltage: If charging voltage above 54V, battery protection will turn on.
    Solution: Check whether voltage is too high or not, if it is, to change the settings on power supply side. And discharge the module.
    e) Low Voltage: When the battery discharges to 44.5V or less, battery protection will turn on.
    Solution: Charge the battery till the red light turns off.
    f) Cell voltage high. The module voltage is lower than 54V, SOC LED does not all on. When discharge the module protection disappear.
    Solution: keep charge the module by 53-54V or keep the system cycle. The BMS can balance the cell during cycling.

  3. Unable to charge and discharge with red LED on. The temperature is 0~50 degree. Use charger to charge, not possible. Use load to discharge, not possible.
    g) Under permanent protection. The single cell voltage has been higher than 4.2 or lower than 1.5 or temperature higher than 80 degrees.
    Solution: Switch off the module and contact your local distributor for repair.

  4. Unable to charge and discharge without red LED on. The temperature is 0~50 degree. Use charger to charge, not possible. Use load to discharge, not possible.
    h) Fuse broken.
    Solution: Switch off the module and contact your local distributor for repair.

  5. Buzzer rings and all LED flash
    a) High voltage protection.
    Cell voltage higher than 4V or module voltage higher than 55.5V.
    Solution: Battery system requires properly established communication with inverter and correctly settings on inverter to run safely. Check the setting of the inverter or charger, the charge voltage shall be 53.2~52.5Vdc; Check the communication between battery system and inverter whether established or not; Check the ADD switch on battery module whether is set correctly or not;
    Under this condition, the BMS remains functional without damage. Just leave the module switched OFF and wait for the battery voltage drop down naturally(15mins) then restart. If then no alarm comes out, this means the module is ready for work Buzzer rings and ALM solid red

  6. b) Reverse connection of cables.
    Solution: Power off all battery and inverters. Disconnect breaker. Check the cable connection and disconnect all power cables. Check the power port damaged or not. Then try turn on the single module, without any cable connected. If no alarm, then it is reverse connection of cables. Switch off the module and contact your local distributor.
    c) MOSFAIL.
    Solution: Power off all battery and inverters. Disconnect breaker. Check the cable connection and disconnect all power cables. Check the power port damaged or not. Check the setting of inverter or charger, check the communication between inverter and battery system.
    Try turn on the single module, without any cable connected. If still buzzer rings. Then switch off the module and contact your local distributor.

  7. After switch On, the module turns on directly
    d) BMS failure.
    Solution :Switch off the module and contact your local distributor.
    Excluding the points above, if the faulty still cannot be located, turn off battery and contact your local distributor.

Emergency Situations

  1. Leaking Batteries
    If the battery pack leaks electrolyte, avoid contact with the leaking liquid or gas. If one is exposed to the leaked substance, immediately perform the actions described below.
    a) Inhalation: Evacuate the contaminated area and seek medical attention.
    b) Contact with eyes: Rinse eyes with flowing water for 15 minutes and seek medical attention.
    c) Contact with skin: Wash the affected area thoroughly with soap and water and seek medical attention.
    Ingestion: Induce vomiting and seek medical attention.

  2. Fire
    NO WATER! Only dry powder fire or carbon dioxide extinguisher can be used; if possible, move the battery pack to a safe area before it catches fire.

  3. Wet Batteries
    If the battery pack is wet or submerged in water, do not let people access it, and then contact Pylontech or an authorized dealer for technical support.
    Cut off all power switch on inverter side.

  4. Damaged Batteries
    Damaged batteries are dangerous and must be handled with the utmost care. They are not fit for use and may pose a danger to people or property.
    If the battery pack seems to be damaged, pack it in its original container, and then return it to Pylontech or an authorized dealer.

Danger
Damaged batteries may leak electrolyte or produce flammable gas.

Remarks

Recycle and disposal
In case a battery (normal condition or damaged) needs disposal or needs recycling, it shall follow the local recycling regulation (i.e. Regulation (EC) Nº  1013/2006 among European Union) to process, and using the best available techniques to achieve a relevant recycling efficiency.

Storage, Maintenance and Expansion

  1. It is required to charge the battery at least once every 12 months, for this charge maintenance make sure the SOC is charged to higher than 90%
  2. Every year after installation. The connection of power connector, grounding point, power cable and screw are suggested to be checked. Make sure there is no loose, no broken, no corrosion at connection point. Check the installation environment such as dust, water, insect etc. make sure it is suitable for IP20 battery system.
  3. If the battery is stored for long time, it is required to charge them every six months, and the SOC should be higher than 90%.
  4. A new battery module can be added onto an existing system at any time. Please make sure the new battery is acting as the master. The new module, due to a higher SOH may have a difference on SOC with existing system, but it will not affect the parallel connection system performance.

Pylon Technologies Co., Ltd.
5/F, No.71-72, Lane 887, ZuChongzhi Road,
China (Shanghai) Pilot Free Trade
Zone, Pudong, Shanghai 201203, China
T+86-21-51317699 | F +86-21-51317698
Eservice@pylontech.com.cn
Wwww.pylontech.com.cn

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

PYLONTECH User Manuals

Related Manuals