This manual introduces LV-Hub from Pylontech. LV-Hub is a communication hub for US2000/US3000 Lithium-Ion Phosphate Battery storage system. Please read this manual before you install the battery and follow the instruction carefully during the installation process.
Introduction
LV-Hub is the CAN/RS485 communication hub for multiple 48V battery groups in
parallel connection.
Fit Description: US2000 / US3000 / US2000C / US3000C / UP5000 / US5000.
LV-Hub-A
No. | Item | Parameter |
---|---|---|
1 | Operating voltage range | 48 Vdc |
2 | Communication | CAN/RS485 |
3 | System Consumption | 2W |
4 | Size | 44219044mm |
5 | Protection degree | IP20 |
6 | Weight | 3.0kg |
7 | Operation Life | 15 years |
8 | Working temperature | -20~60℃ |
9 | Storage temperature | -40~80℃ |
10 | CAN (Max 25 groups) | Baud rate: 500K; terminal resistance: 0/120Ω |
11 | RS485 (Max 5 groups) | Baud rate:9600/115200 |
2.1 Ports:
No. | Part | Silk-screen | Function |
---|---|---|---|
1 | Dry signal | Function reserve | |
2 | Reset Switch | ||
Button | RESET | Press 2 seconds and then system will restart. | |
3 | Dip switch | 1 – 6 | Dip 6: Up: CAN OUT terminal resistance 120D Down: SD |
4 | RJ45 | CAN OUT | CAN output port (only upper port is for using); |
5 | RJ45 | RS232 | Debug |
6 | RJ45 | CAN IN | Connect to port 0 (only for CAN communication); |
7 | LED | STATUS | Please see 2.3. |
8 | LED | NUMBER/BIN 1-4 | Shows linked in battery group quantity with binary |
code. Please see 2.3.
9-16| RJ45| 0; 1; 2; 3; 4; 5; 6; 7.| Only uses 0-5. Please see 3.2.
17| Switch| ON/OFF| Turns the LV-HUB ON/OFF.
18| 48VDC input| 48V DC| Power supply: take 48VDC power from outside (from
AC/DC adaptor).
2.2 Definition of RJ45 Port Pin
No. | CAN OUT | RS485 | RS232 Pin |
---|---|---|---|
1 | — | — | — |
2 | GND | — | — |
3 | — | — | TX |
4 | CANH | — | — |
5 | CANL | — | — |
6 | — | GND | RX |
7 | — | RS485A | — |
8 | — | RS485B | GND |
2.3 LED Indicators Instructions
Status | Only the HUB is turned ON, it lights once. | |
---|---|---|
No battery connected or at least one group is off line. When battery group |
is reduced it will alarm (in red), but when battery group is added in it will
no alarm.
1| 2| 3| 4| Green flash; connected battery groups number
| | | | 1 group
| | | | 2 groups
| | | | 3 groups
| | | | 4 groups
| | | | 5 groups
| | | | 6 groups
| | | | 7 groups
Operation
3.1 Protocol
CAN: CAN-Bus-protocol-PYLON-low-voltage-V1.2-20180408 or above.
RS485: RS485-protocol-pylon-low-voltage-V3.1-20180408 or above.
3.2 Cables Connection for US2000/US3000 under RS485 or CANBUS.
3.2.1 Cables Connection for RS485
- Each battery group can configure maximum 8pcs US2000B Plus or 8pcs US3000.
- LV-Hub-A configures maximum 5 group batteries.
- RS485 communication needn’t additional cable and power just a simple hub is enough.
- When each battery group’s current is >120A, this battery group must configure 2 pair external power cables like the diagram.
- The details of ADD Switch setting also can see the menu of battery.
3.2.2 Cables Connection for CAN (single HUB)
- Each battery group can configure maximum 8pcs US2000B Plus or 8pcs US3000.
- LV-Hub-A configures maximum 5 group batteries.
- When each battery group’s current is >120A, this battery group must configure 2 pair external power cables like the diagram.
- The details of ADD Switch setting also can see the menu of battery.
- When using with SMA SUNNY ISLAND, the ADD on HUB(or master HUB if there are multiple HUBs) must be 000011(for B14V0105 presenting on product label) or 000101 (for B14V0106 presenting on product label).
3.3 Cables Connection for US2000C/US3000C/UP5000 under CANBUS
Note: The cable connection for RS485 do not require a LV-HUB. The specific
cable connection way please refer to the related battery operation manual.
Connect power cable first:
- each pair of cable hold max 100A constant current. Connect enough pairs of cable based on calculation of system current.
- Suitable protection breaker between battery system and inverter is required.
- connect power cable of LV-HUB
- Make sure all dipswitch is X0XX, then turn ON batteries.
- After all batteries running and buzzer of master battery in group1 rings 3 times. Means all groups are online.
- Change the dip switch of master battery in group1 to X1XX. Then connect communication cable between LV-HUB and master battery in group 1.
- Then turn ON LV-HUB.
Below communication cable shall be 8 pin direct-pin cable:
a. Between battery modules
b. Between LV-HUB Port 0 to LV-HUB CAN IN
Below communication cable shall has first 3 pin NULL or use WI0SCAN30RJ1 cable inside external cable kits:
a. Between Group 1 Master Battery A/CAN to LV-HUB Port 1. 3.4 Cables
Connection for Multiple HUBs under CANBUS.
In above picture, all communication cable connect in between shall be 8 pin
direct-pin cable.
Annex 1: Cables Connection for US2000/US3000 under RS485 Annex 2:
Cables Connection for US2000/US3000 under CAN Annex 3: Cables Connection
for CAN (multi HUB) Annex 4: Cables Connection for US2000C/US3000C/UP5000
under CANBUS
Pylon Technologies Co., Ltd.
No. 73, Lane 887, ZuChongzhi Road, Zhangjiang Hi-Tech Park
Pudong, Shanghai 201203, China
T +86-21-51317699 | F +86-21-51317698
E service@pylontech.com.cn
W www.pylontech.com.cn
Pylon Technologies Co., Ltd.
No. 73, Lane 887, ZuChongzhi Road, Zhangjiang Hi-Tech Park
Pudong, Shanghai 201203, China Zip Code: 201203
Tel: 021-51317699
Fax: 021-51317698
Email: service@pylontech.com.cn
Website: http://www.pylontech.com.cn
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>