milleteknik SIN UPS 300W M SINUS UPS User Manual

June 15, 2024
Milleteknik

milleteknik SIN UPS 300W M SINUS UPS User Manual

milleteknik SIN UPS 300W M SINUS UPS User Manual

ABOUT SINUS UPS FROM MILLETEKNIK

The SIN inverter is an Off-line UPS that steps in and replaces the supply from the mains in the event of a mains failure, until the mains returns (or the batteries are completely discharged). SIN inverters are designed with the latest switching technology and microprocessor monitoring, for: Highest efficiency and operational reliability, providing long life for both electronics and batteries. Well protected with , protection against overtemperature, overload, short circuit. Complete self-test including advanced battery test. The units are installation and service friendly: Compact volume. Modular structure.
The UPS is charged with a built-in power supply and is powered further by batteries in the event of a power failure.

SAFETY – READ THIS FIRST

  • The unit must be installed by a qualified person.
  • It is the installer’s responsibility that the system is suitable for intended use.
  • Documents accompanying the system must be kept in its immediate vicinity.
  • The system should not be connected to the mains during installation.
  • All information is subject to change.

DANGER

Dangerously high voltage.
Wait one (1) minute after power has been disconnected from the unit.

1.1. About translation of this document

User manual and other documents are in the original language in Swedish. Other languages are machine translated and not reviewed, errors may occur.

COMPONENT OVERVIEW

milleteknik SIN UPS 300W M SINUS UPS - COMPONENT
OVERVIEW

Table 1. Component overview

milleteknik SIN UPS 300W M SINUS UPS - Table 1. Component
overview

ENCLOSURES

3.1. Wall mounting
Use four screws suitable for the wall to set up the cabinet.

The distance between the screw head and the wall should be 1.5–2 mm.
Preferably leave a 100 mm air gap around the unit.

milleteknik SIN UPS 300W M SINUS UPS - Preferably leave a 100 mm air gap
around the unit

3.2. Mounting

Use the appropriate screw for mounting on the wall, Screw for mounting on the wall is not included.

CONNECTION 230 V

4.1. In: Battery connection

milleteknik SIN UPS 300W M SINUS UPS - In Battery
connection

Table 2. Overview of incoming mains and battery connection

milleteknik SIN UPS 300W M SINUS UPS - Table 2. Overview of incoming mains
and battery connection

Connect Phase/Neutral/Earth (PE) incoming on motherboard

Table 3. Battery number

milleteknik SIN UPS 300W M SINUS UPS - Table 3. Battery
number

4.2. Load disconnector incoming mains (in: 230 V)

For maximum safety, always disconnect from the mains before installation and service. Connect a load disconnector (circuit breaker) to the incoming cable from the mains. Place it easily accessible and label it clearly. With a load disconnector installed, incoming voltage can be easily interrupted during service and function tests.

OUT: 230 V

Output phase/load to PICTO marked 9 on circuit board overview and 4 on circuit board. Output phase/ load to (EMERGENCY LIGHT) marked 8 on circuit board overview and 5 on circuit board, (only energized in case of mains failure). Output zero, to ZERO, labeled 7 on circuit board overview and 6 on circuit board. Protective earth, PE, marked 6 on circuit board overview and 7 on circuit board.

DESCRIPTION MOTHERBOARD: MINISINUS

Figure 1. Minisinus consists of two cards

milleteknik SIN UPS 300W M SINUS UPS - Figure 1. Minisinus consists of two
cards 2

Table 4. Circuit board overview, explanation

milleteknik SIN UPS 300W M SINUS UPS - Table 4. Circuit board overview,
explanation

milleteknik SIN UPS 300W M SINUS UPS - Table 4. Circuit board overview,
explanation 2

ALARM CONNECTION

Self-test and alarm for mains failure
Total alarm for self-test: Connect total alarm for self-test (Self Diagnosis).
P1:1-3, incorrect charging voltage (over/under voltage), aged battery – when the battery should be replaced, or non functioning inverter to circuit board terminal P1:1-3. Alarm – contact NO and CO. Mains failure: Connect the mains failure alarm P1:1-3, “MAINS ALARM”, an alarm is given immediately in the event of a mains failure.

COMMISSIONING – HOW TO START THE UNIT

After connection, start-up must take place in the following steps:

Table 5. Commissioning – the order

milleteknik SIN UPS 300W M SINUS UPS - Table 5. Commissioning - the
order

CARE INSTRUCTIONS UPS

The unit is maintenance-free when installed in a room temperature indoor environment +15°C— +25°C.
However, the batteries should be changed after 10-12 years to maintain high guaranteed safety. In the extended temperature range +5°C— +15°C/+25°C— +30°C, the batteries will age twice as fast. Further colder or warmer ambient temperature means that reliability is at risk.

9.1. Battery replacement UPS

WARNING
Fuse on the lid does not interrupt current (230 V) but only interrupts voltage to batteries (24 V).

milleteknik SIN UPS 300W M SINUS UPS - Battery replacement
UPS

DIMENSIONING UPS

Dimension the connected load so that it is, in total, as large as the inverter’s maximum rated power (W), preferably less to partly obtain safety margins, and partly to compensate for losses in connections/cabling and the load which means greater actual power consumption from the inverter than the specified rated power of the load. Take temporary starting power into account, so that it does not exceed the specified maximum – short-term – starting power (VA) of the inverter. Back-up load operation should take place within one hour of the grid failure occurring, as the inverter consumes power at idle, which gradually drains the batteries.

ALARM / STATUS ON INDICATOR DIODE

Alarm is shown on the indicator diode on the cabinet door. Mains operation/mains interruption alarm: During normal mains operation, the LED on the front panel is constantly lit. In the event of a mains failure, the inverter starts in battery operation, whereby the LED flashes “1 blink” ORANGE so that when the time for any set time delay of the mains alarm occurs, the LED blinks “2 blinks” ORANGE. In the event of a “mains failure” alarm, the alarm contact switches to contact between NO-CO.

FRONT PANEL AND STATUS INDICATORS

milleteknik SIN UPS 300W M SINUS UPS - FRONT PANEL AND STATUS
INDICATORS

milleteknik SIN UPS 300W M SINUS UPS - FRONT PANEL AND STATUS INDICATORS
2

FAQ UPS

13.1. Control measures in case of alarm UPS – Battery charge, over or under voltage

Over or under voltage is indicated if the device, when the batteries are charged, does not provide the correct charging voltage. Alarms are indicated by flashing on the front panel at the same time as a total alarm is set.
Action in case of alarm: Check charging voltage. Measure voltage to 27.3 V. At two-pole power supply terminal, (red plus, black minus cable).

13.2. Control measures in the event of an alarm UPS – Alarm for aged battery

The batteries’ capacity and aging are tested weekly. If the test shows that the battery capacity has dropped below 60% – 80% of the battery’s original capacity, an alarm is given for an aged battery
Action in case of alarm: Replace batteries.

13.3. Control measures in case of UPS alarm – UPS fault / inverter fault

In the event of an inverter fault, the LED on the front panel flashes at the same time as a total alarm is set.

Action in case of alarm:

  • Check fuses in the unit.
  • Check with a multimeter that the device provides charging output, (230 V ) in mains operation and in battery operation.
  • Batteries have sufficient voltage, (27 V). Measure the battery terminals.

13.4. Control measures in case of alarm UPS – Overvoltage, too high charging current

If the charging voltage in normal operation exceeds 27.9 V, the charging is disconnected.
Check with a multimeter that the device’s charge does not exceed 27.9 V.
Contact support for further assistance with adjusting the voltage of the power supply unit.

13.5. Test load in UPS (part of self-test system)

The unit is tested weekly against an internal test load. This is to check that the output voltage is sufficient for UPS operation and thus that the batteries are not aged.

13.6. Are alarms given when batteries are recharged after a power outage?
No alarms are given when the batteries are charged after a mains failure.

13.7. Technical facts alarm: Incorrect charging voltage
Alarm for incorrect charging voltage is given if the charger’s voltage falls below 26.5 V.
Undervoltage may be natural after prolonged discharge, UPS operation. To ensure that the power supply does not break during recharging, a test is made every 45 minutes that the charging voltage is correct.
Alarms for incorrect charging voltage/broken power supply are displayed on the panel and via potential- free relay switching.

13.8. Technical facts alarm: Overvoltage
If the charging voltage in normal operation exceeds 27.9 V, the charging is disconnected. An alarm is also given on potential-free relay switching.

13.9. Technology facts alarm: Aged battery
Every week, batteries are tested with a high, predetermined and short-term load current across internal load resistors that correspond to the batteries’ rated power. Current battery capacity is measured. The microprocessor takes a “fingerprint” of the current state of the battery in the load test. The value taken is then compared with the programmed battery value. In tests that give an indication of between 20%- 40% of the original battery capacity, an alarm for an aged battery is given. Alarm is also given on potential-free relay switching/Sum-alarm.

13.10. Technology facts alarm: Inverter test
Every week the unit is tested with internal load. If the unit’s inverter does not provide sufficient output voltage, an alarm is given. Alarm is also given on potential-free relay switching.

SIN

14.1. SIN – UPS Product sheet / technical data
Figure 2. UPS SINUS 300W M

14.1.1. Technical specifications
These technical specifications are subject to change without notice.

14.1.2. SINUS UPS name, article number and e-number

milleteknik SIN UPS 300W M SINUS UPS - SINUS UPS name, article number and
e-number

14.1.3. Maximum rated power

milleteknik SIN UPS 300W M SINUS UPS - Maximum rated
power

14.1.4. ABOUT UPS
The UPS are designed with the latest switch technology and microprocessor monitoring, for maximum efficiency and reliability, providing long life for both electronics and batteries. UPS is well protected with protection against overtemperature, overload, short circuit.
– Complete self-test including advanced battery test.
The units are installation and service friendly: – Compact volume.
NOTE! This translation is not verified and the information should always be cross-checked with the swedish original.

14.1.5. Fixed installation
The product is intended for fixed installation. The battery backup must be installed by a qualified installer.

14.2. Areas of use
SINUS UPS is mostly used for camera surveillance, PoE switches and other security systems. Sinus UPS is also used for gates and gate control of smaller and larger industrial and garage doors.

  • Camera surveillance,
  • PoE switches and other security systems.
  • Gate and door control of smaller and larger industrial and garage doors.

14.3. Regulations and certifications

14.3.1. Requirements that the product meets

milleteknik SIN UPS 300W M SINUS UPS - Requirements that the product
meets

14.4. Circuit boards – Technical data

14.4.1. Technical data: CEO 3

milleteknik SIN UPS 300W M SINUS UPS - Technical data CEO
3

milleteknik SIN UPS 300W M SINUS UPS - Technical data CEO 3
2

230 V VOLTAGE IN

milleteknik SIN UPS 300W M SINUS UPS - 230 V VOLTAGE
IN

230 V OUTPUT VOLTAGE

milleteknik SIN UPS 300W M SINUS UPS - 230 V OUTPUT
VOLTAGE

BATTERY CHARGE
I / O according to DIN 41773 Current limitation.

PROTECTION

milleteknik SIN UPS 300W M SINUS UPS - PROTECTION

FUSES MINISINUS V8

milleteknik SIN UPS 300W M SINUS UPS - FUSES MINISINUS
V8

SELF-TEST

milleteknik SIN UPS 300W M SINUS UPS - SELF-TEST

ALARM
All alarms occur on potential-free relay switching.

milleteknik SIN UPS 300W M SINUS UPS - ALARM

14.5. Technical data enclosures

14.5.1. Enclosures – Technical Data M

milleteknik SIN UPS 300W M SINUS UPS - Enclosures - Technical Data
M

14.6. Batteries – recommended, not included
14.6.1. Batteries are not included they are sold separately

Batteries are sold separately.

14.6.2. 14 Ah, 12 V AGM battery

milleteknik SIN UPS 300W M SINUS UPS - 14 Ah, 12 V AGM
battery

*Design life is the shelf life in years for an unused battery. Environmental factors such as heat and load affect the service life. Batteries that have a durability (+10 Design Life) of 10+ years usually need to be replaced after 5-6 years.

14.7. Link to the latest information
Products and software are subject to updates, you will always find the latest information on our website.
Sinus UPS

14.8. Warranty, support, country of manufacture and country of origin

14.8.1. Warranty
The product has a two-year warranty, from the date of purchase (unless otherwise agreed). Support during the warranty period can be reached at support@milleteknik.se or telephone, +46 31-34 00 230. Compensation for travel and / or working hours in connection with locating faults, installing repaired or replaced goods is not included in the warranty. Contact Milleteknik for more information. Milleteknik pro- vides support during the product’s lifetime, however, no later than 10 years after the date of purchase. Switching to an equivalent product may occur if Milleteknik deems that repair is not possible. Support costs may (at Milleteknik’s discretion) occour after the warranty period has expired.

14.8.2. Support
Do you need help with installation or connections? Our support phone is available: Monday-Thursday 08: 00-16: 00 and Fridays 08: 00-15: 00. Telephone support is closed between 11: 30-13: 15.
You will find answers to many questions at: www.milleteknik.se/support
Phone: +46 31-340 02 30
Support is open: Monday-Thursday 08:00-16:00, Fridays 08:00-15:00. Closed 11:30-13:15.

SPARE PARTS
Contacted support for questions about spare parts.

SUPPORT AFTER THE WARRANTY PERIOD
Milleteknik provides support during the life of the product, but no longer than 10 years after the date of purchase. Replacement for an equivalent product may occur if the manufacturer deems that repair is not possible. Costs for support and replacement are added after the warranty period has expired.

QUESTIONS ABOUT PRODUCT PERFORMANCE?
Contact sales: 46 31-340 02 30, e-mail: sales@milleteknik.se

14.8.3. Contact us
Milleteknik AB
Ögärdesvägen 8 B
S-433 30 Partille
Sweden
+46 31-34 00 230
www.milleteknik.se

14.8.4. Country of manufacture
Country of manufacture / country of origin is Sweden. For more information, contact your seller.

14.8.5. Designed and produced by: Milleteknik AB
Designed and produced by Milleteknik AB