milleteknik A-FU122408OP02 8 Output Module PTC Owner’s Manual

June 1, 2024
Milleteknik

milleteknik A-FU122408OP02 8 Output Module PTC

Product Information

Specifications :

  • Name: 8 Output module PTC
  • Item Number: A-FU122408OP02
  • E-Number (sv): 52 137 22
  • Maximum Load per Output: 2.7 A
  • Maximum Load for Entire Board: 10 A

Product Usage Instructions

Mounting in Battery Backup:

  • The card is delivered mounted in its plastic casing for easy installation. If the card comes loose, snap it back into the plastic casing. Mount the card on any card slot in the enclosure, leaving space for cables.
  • Important: Install the board before screwing on wiring or commissioning.

Connections :

  • Power Supply Connection: Connect power (24 V) from the battery backup’s load output to the card’s 24 V input.
  • Alarm Output: Connect between NO and COM.
  • Load Connection: Connect load wiring to P2:1-8 on 8 Output module PTC.

Warning:

  • Maximum Load: 1.85 A per load output. The card’s total load must not exceed 10 A.

  • Connect 8 Output Module PTC to Motherboard: CEO3 V 2.1
    Connection: Follow the provided picture for correct connections. Communication is connected between terminals as indicated.

  • Connect 8 Output Module PTC to Motherboard: CEO3 V5
    Connection: Connect as shown in the picture provided. Communication is connected between terminals as indicated.

FAQ

  • Q: Can the fuses be changed on the board?
    A: No, the fuses are fixed and cannot be changed. Ensure that the maximum load per output does not exceed 2.7 A and the total load for the board does not exceed 10 A.

  • Q: What is the maximum load per load output?
    A: The maximum load per load output is 1.85 A.

NAME, ARTICLE NUMBER AND E-NUMBER

Name Item number E-number (sv)
8 Output module PTC A-FU122408OP02 52 137 22

Product image

IF

Fuse cards, with sum-alarm, are used to protect electronic circuits from damage due to overcurrent or short circuit.

IMPORTANT
Since the fuses are fixed and cannot be changed, the maximum load per output must not exceed 2.7 A. The maximum load for the entire board is 10 A.

What is a PTC fuse?

  • A PTC fuse, where “PTC” stands for “Positive Temperature Coefficient,” is a type of thermal fuse or overcurrent protection device. These fuses are used to protect electrical circuits from overcurrent and short circuits.
  • The fuse works by changing its resistance characteristic when it gets too hot due to high current. When the current becomes too large, the temperature in the fuse increases, causing it to become less conductive and restrict the flow of current. When the temperature in the fuse goes down, the fuse returns to its normal state and allows current to pass as usual.

MOUNTING IN BATTERY BACKUP

  • The card is delivered mounted in it’s plastic casing, for easy installation.
  • If the card has come loose, snap it back into the plastic casing.
  • Mount the card on any card slot in the enclosure, leave space for cables.

IMPORTANT
Install the board before screwing on wiring or commissioning.milleteknik-A-FU122408OP02-8-Output-Module-PTC-fig-
\(2\)

Letter Explanation Comment
A Optional card Optional card comes mounted on plastic housing from factory.

Has it come loose? Snap it back on before mounting the card.
B| Plastic casing| The plastic casing has hooks for attaching slots in the plate.
C| Place for plastic casing| Slits in sheet metal to snap the plastic bracket.

SHORT DESCRIPTION

No On circuit board Explanation
1 J14, J15 Connection to alarm on motherboard.

Bridging connection for alarms from another card.
2| P3:1-3| Alarm output, NC/COM/NO.
3| D19, D16| Indicator diode. Green = ok. REDa.= alarm.
4| S1| Acknowledgment button for alarms.
5| P1| Incoming voltage from motherboard.
6| JU1| Jumper for switching the card to 12 V. Jumpered = 12 V, Not jumpered = 24 V, factory setting.
7| D1-D8| Indicator diode lights up green when there is voltage at the output.
8| P2:1-8| Load output +/-

a.Lights up red until the alarm is acknowledged.

CONNECT 8 OUTPUT MODULE PTC TO MOTHERBOARD: CEO3 V 2.1

Connect the card as shown in the picture + and – from load on motherboard are connected to + and – on the option board.
Communication is connected between terminals as the solid line shows.

  • Connecting the power supply
    Connect power (24 V) from the battery backup’s load output to the card’s 24 V input.

  • Connection of load
    Connect load wiring to P2:1-8 on 8 Output module PTC.

WARNING
Maximum load is 1.85 A per load output and the card’s total load must not exceed 10 A.

No Connections 8 Outoput mod- ule PTC Motherboard
1 Power supply connection P1:1-4 Optional load output.
2 Alarm output: connected between NO and COM P3:1-3 JU3 Connects between

the middle pin and an outer pin.
–| Bridging alarms to the card is not possible as the card has no alarm input.| –| –

CONNECT 8 OUTPUT MODULE PTC TO MOTHERBOARD: CEO 3 V5

Connect the card as shown in the picture + and – from load on motherboard are connected to + and – on the option board.
Communication is connected between terminals as the solid line shows.

  • Connecting the power supply
    Connect power (24 V) from the battery backup’s load output to the card’s 24 V input.

  • Connection of load
    Connect load wiring to P2:1-8 on fuse module for priority load.

WARNING
Maximum load is 1.85 A per load output and the card’s total load must not exceed 10 A.

Connections from battery backup to fuse board

No Connections 8 Outoput module PTC Motherboard
1 Power supply connection: P1:1-4 Optional load output
2 Bridging alarm to motherboard: Bridging of alarms to additional option
cards J14
J15 J27

CONNECT 8 OUTPUT MODULE PTC TO MOTHERBOARD: NEO3

Connect the card as shown in the picture + and – from load on motherboard are connected to + and – on the option board.
Communication is connected between terminals as the solid line shows.

  • Connecting the power supply
    Connect power (24 V) from the battery backup’s load output to the card’s 24 V input.

  • Connection of load
    Connect load wiring to P2:1-8 on 8 Output module PTC.

WARNING
Maximum load is 1.85 A per load output and the card’s total load must not exceed 10 A.

Connections from battery backup to fuse board

No Connections 8 Outoput module PTC Motherboard
1 Power supply connection: P1:1-4 Optional load output.
2 Bridging alarm to motherboard:
Bridging of alarms to/from additional option cards J14
J15 J5

CONNECT 8 OUTPUT MODULE PTC TO MOTHERBOARD: PRO1, 5 A – 10 A

Connect the card as shown in the picture + and – from load on motherboard are connected to + and – on the option board.
Communication is connected between terminals as the solid line shows.

  • Connecting the power supply
    Connect power (24 V) from the battery backup’s load output to the card’s 24 V input.

  • Connection of load
    Connect load wiring to P2:1-8 on 8 Output module PTC.

WARNING
Maximum load is 1.85 A per load output and the card’s total load must not exceed 10 A.

Connections from battery backup to fuse board

No Connections 8 Output control module Motherboard
1 Power supply connection: P1:1-4 Optional load output
2 Bridging alarm to motherboard:
Bridging alarms to/from additional option cards: J14
J15 J13

CONNECT 8 OUTPUT MODULE PTC TO MOTHERBOARD: PRO1, 15 A – 25 A

Connect the card as shown in the picture + and – from load on motherboard are connected to + and – on the option board.
Communication is connected between terminals as the solid line shows.

  • Connecting the power supply
    Connect power (24 V) from the battery backup’s load output to the card’s 24 V input.

  • Connection of load
    Connect load wiring to P2:1-8 on 8 Output module PTC.

WARNING
Maximum load is 1.85 A per load output and the card’s total load must not exceed 10 A.

Connections 15 A and 25 A units

No/letter On circuit board (A) Explanation
A 8 Output modules Optional card.
B 2 Output module Card for connection of load and power supply to 8 Outoput

module PTC.
C| Effect card| Available in 15 A and 25 A units.
D| PRO1| Motherboard in battery backup.
1| P1:1-4| Connect power supply 8 Outoput module PTC from (B).
2| J14| Alarms are connected to load cards.
3, 4, 5| –| Internal power supply and communication between cards.

CONNECT 8 OUTPUT MODULE PTC TO MOTHERBOARD: PRO2 V3, 5 A – 10 A

Connect the card as shown in the picture. + and – from load on motherboard are connected to + and – on the option board.
Communication is connected between terminals as the solid line shows.

  • Connecting the power supply
    Connect power (24 V) from the battery backup’s load output to the card’s 24 V input.

  • Connection of load
    Connect load wiring to P2:1-8 on 8 Output module PTC.

WARNING
Maximum load is 1.85 A per load output and the card’s total load must not exceed 10 A.

Connections from battery backup to fuse board

No Connections 8 Outoput module PTC Motherboard
1 Power supply connection: P1:1-4 Optional load output.
2 Bridging alarm to motherboard: Bridging alarms to additional option cards:

J14
J15| J1

CONNECT 8 OUTPUT MODULE PTC TO MOTHERBOARD: PRO2 V3 15 A – 25 A

Connect the card as shown in the picture + and – from load on motherboard are connected to + and – on the option board.
Communication is connected between terminals as the solid line shows.

  • Connecting the power supply
    Connect power (24 V) from the battery backup’s load output to the card’s 24 V input.

  • Connection of load
    Connect load wiring to P2:1-8 on 8 Output module PTC.

WARNING
Maximum load is 1.85 A per load output and the card’s total load must not exceed 10 A.

Connections 15 A and 25 A units

No/letter On circuit board (A) Explanation
A 8 Outoput module PTC Optional location.
B 2 Output module Card for connection of load and power supply to 8 Outoput

module PTC.
C| Effect card| Available in 15 A and 25 A units.
D| PRO2 v3| Motherboard in battery backup.
1| P1:1-4| Disconnect power supply 8 Outoput module PTC (B).
2| J14| Connect alarm to load card.
3, 4| –| Internal power supply and communication between cards.

CONNECT 8 OUTPUT MODULE PTC TO MOTHERBOARD: PRO3 5 A – 10 A

Connect the card as shown in the picture. + and – from load on motherboard are connected to + and – on the option board.
Communication is connected between terminals as the solid line shows.

  • Connecting the power supply
    Connect power (24 V) from the battery backup’s load output to the card’s 24 V input.

  • Connection of load
    Connect load wiring to P2:1-8 on 8 Output module PTC.

WARNING
Maximum load is 1.85 A per load output and the card’s total load must not exceed 10 A.

Connections from battery backup to fuse board

No Connections 8 Outoput module PTC Motherboard
1 Power supply connection: P3:1-4 Optional load output.
2 Bridging alarm to motherboard: J14 J5

CONNECTION OF ANOTHER 8 OUTOUT MODULE PTC

milleteknik-A-FU122408OP02-8-Output-Module-PTC-fig-
\(12\) Connecting additional option cards to the motherboard

NOTE
For alarm connection use 2A and 2B for connection of newer devices (after approx. 2018). For older devices (before approx. 2018) use 3A-3C.

Connection of additional optional cards

Letter / No Explanation On the card
A 8 Outoput module PTC.
B 8 Outoput module PTC.
C Motherboard, may vary with configuration.
1 A Power supply to 1B from 1A. P1:1-+2
1 B Power supply to 1B from motherboard. P1:3-4
2 A Bridging of alarms from card A to card B. J15
2 B Connection of alarm on C (motherboard) from board A. See table below.
2C Connection of alarm on C (motherboard) from board B. See table below.
3 A Alarm output switches From board A to board B. J14-J15
3 B Alarm output switches From board A to board B. J14-J15

Connection, schematic diagram

Letter / No Explanation
X1 Optional card 1
X2 Optional card 2
X3 Motherboard
X3.1 Connection to motherboard from option board.
X3.2 Connection to motherboard from option board.

Alarms from optional cards are connected on terminal block (on motherboard)

Motherboard| Terminal as an alarm from an optional card must be connected (on motherboard)
---|---
CEO3 v5| J27
NEO3| J5
PRO1| J13
PRO2 v3| J1
Motherboard| Terminal as an alarm from an optional card must be connected (on motherboard)
---|---
PRO3| J5

TECHNICAL DATA – 8 OUTPUT CONTROL MODULE

Info Explanation
Card name: 8 Output control module
Product description 8 Output control module is a protection module with 10

fully protected outputs, of which seven are prioritized and three are non- prioritized.
The product fits in| Battery backups with motherboard: PRO1, PRO2, PRO2 V3, PRO3 and NEO3.
Measure| 120 x 45 mm.
Own consumption| 65mA
Output voltage| 24 V
Fuses| F2A comes with cards.
Indication| Yes, LED on circuit board

Outputs

Info Value
Alarm outputs, number 1
Alarm on changing relay? (Yes No) Yes
Load outputs, number 8
Voltage on load output 27.3V DC
Priority (always voltage) load outputs (Yes/No) Yes
Max load, per output 10 A
Maximum load, total, (must not be exceeded). 16 A
Load output plus (+) fused? (Yes No) Yes
Load output minus (-) secured (Yes/No) No
Fuses on output T2A.
Connection to buzzer? (Yes No) No

Manufactured in Milleteknik’s factory in Partille, Sweden.
This translation is not verified and should be cross referenced with the swedish original before use.

ABOUT TRANSLATION OF THIS DOCUMENT
User manual and other documents are in the original language in Swedish. Other languages may be machine translated and/or not reviewed, errors may occur.

ADDRESS AND CONTACT DETAILS

This installation sheet’s article number: 350-264

031-340 02 30, www.milleteknik.se
Milleteknik AB, Ögärdesvägen 8 B, 433 30 Partille

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Milleteknik User Manuals

Related Manuals