ABOUT RELAY CARD NOVA SERIES (PRO3)
With 4 pcs. relay outputs for systems supplied with PRO3 motherboards.
Installation of Relay card NOVA Series on motherboard-PRO3 Relay cards are
mounted on terminals on motherboards
Mounting
No | Explanation |
---|---|
1 | Pin and pin strip for connection. |
2 | Screw to secure mounting. |
Card Description – Relay Card NOVA Series (PRO3)
Relay card – description, connections and alarm outputs.
-
All fault arm relays must be in the drawn state.
Check that there is a gap between CO and NC. Put the measuring instrument on continuity measurement and test closure.
This should then indicate a short circuit. -
All relay outputs are normally live and give an alarm in the event of no voltage.
No .| Terminal no.| The relay is normally energized.| Alarm
type / explanation
---|---|---|---
1.1…1.4| P4:1| –| GND, protective earth
P4:2| –| RX
P4:3| –| TX
P4:4| –| +5V
2| JU5| –| Connection to motherboard.
3| D2-D6| –| Indicator diode, lit green when OK.
4| P5:10-12| NC, COM, NO| Alarm from tamper switch, (optional for NEO and
EN54).
5| P5:7-9| NC, COM, NO| Low system voltage.
6| P5:4-6| NC, COM, NO| Alarm for fuse failure, charger failure over- voltage,
charger failure under voltage, battery not connected, low battery voltage in
case of mains failure and aged battery*.
NOVA only.
7| P5:1-3| NC, COM, NO| Mains failure alarm.
Technical data, alarm card for PRO 3 / NEO3
Info | Explanation |
---|---|
Card name: | PRO 3 |
Version: | 1.2 |
Product description | Motherboard in battery backup with advanced functions and |
communication to superior systems.
Recommended environment| Indoors, class 1. Ambient temperature: + 5 ° C – 40 °
C.
Protection class| IPX0
Recommended installation| NOVA Series (only 5 A and 10 A)
Input voltage| 13.6 VDC, 27.3 VDC
Self-consumption| 40 mA
Alarm via| Alternating relay
Number of alarm outputs| 4 pcs
Certified according to| EN 50131-6, SBF 110: 8, SSF1014, Meets alarm class 4,
SSF 1014, edition 5
Certificate number (SBSC)| 20-117
The product meets the requirements according to| CE directive according to:
765/2008, EMC Directive 2014 / 30EU, Emission: EN61000-6-: 2001, EN55022:
1998: -A1:
2000, A2: 2003 Class B, EN61000-3-2: 2001, Immunity:
EN61000- 6-2: 2005, EN61000-4-2, -3, 4, -5, -6, -11. SS-EN
50 130-4: 2011 Edition 2 & SSF1014 Alarm class 1-4 (Bur- glar alarm).
Producer| Milleteknik AB
Country of origin| Sweden
Manufactured in Milleteknik’s factory in Partille, Sweden.
This translation is not verified and should be cross referenced with the
swedish original before use
Alarm overview
Alarm over- view in alphabetical order| Relay 1
* / Alarm output 1| Relay 2
* / Alarm output 2| Relay 3
/ Alarm output 3| Relay 4
/ Alarm output 4| Communication (P5: 1-9)| Indica tor
LED on main card and LED on door.
---|---|---|---|---|---|---
Network out- ages| X| –| –| –| X| X
Fuse fault| –| X| –| –| X| X
Sabotage switch| –| –| –| X| X| X
---|---|---|---|---|---|---
Fan fault| –| –| –| –| X| –
Charger fault, overvoltage| –| X| –| –| X| X
Charger fault, under voltage| –| X| –| –| X| X
Cell fault or un- connected battery| –| X| –| –| X| X
Low system voltage. | –| –| X| –| X| X
Low battery voltage (<24.0 V DC) or power failure| –| X| –| –| X| X
Overtemperature| –| –| –| –| X| –
Under temperature| –| –| –| –| X| –
Under temperature| –| –| –| –| X| –
Short battery life left| –| –| –| –| X| –
Aged battery| –| X | –| –| X | X **
Overcurrent 100%, minute average| –| –| –| –| X| –
Overcurrent 80%, daily average| –| –| –| –| X| –
Overcurrent 175%, second average| –| –| –| –| X| –
- Alarm on potential-free relay contact.
*** Not on NEO battery backups.
P4
RS-485 on P4: 1-4 | Explanation |
---|---|
P4:1 | GND |
P4:2 | RX |
P4:3 | TX |
P4:4 | +5V |
Address and contact details
Milleteknik AB
Ögärdesvägen 8 B
S-433 30 Partille
+46 31 340 02 30
www.milleteknik.se