Milleteknik CEO3 5 Output Module User Manual
- May 15, 2024
- Milleteknik
Table of Contents
TECHNICAL SPECIFICATIONS5 OUTPUT MODULE
CEO3 5 Output Module
5 Output module is a fuse module with five fully fused outputs. When ordering, check that the card fits the battery backup the card is to be installed in.
MOUNTING IN BATTERY BACKUP
The card is delivered mounted in it’s plastic casing, for easy installation.
If the card has come loose, snap it back into the plastic casing.
Mount the card on any card slot in the enclosure, leave space for cables.
Important
Install the board before screwing on wiring or commissioning.
Letter | Explanation | Comment |
---|---|---|
A | Optional card | Optional card comes mounted on plastic housing from factory. |
Has it come loose? Snap it back on before
mounting the card.
B| Plastic casing| The plastic casing has hooks for attaching slots in the
plate.
C| Place for plastic casing| Slits in sheet metal to snap the plastic bracket.
CARD DESCRIPTION 5 OUTPUT MODULE
Circuit Board Overview – 5 Output module
Nr | On circuit boards | Explanation |
---|---|---|
1 | D1-D4 | Green indicator LED, illuminates with a solid green light when the |
fuse is ok.
2| F1-F5| Fuses
---|---|---
3| J22, J23| Incoming voltage from motherboard, 24 V.
4| D29| Red indicator LED, illuminates with a solid green light when a fuse is
broken.
5| D30| Green indicator LED, illuminates with a solid green light when the
fuse is ok.
6| J6| Connection to alarm on motherboard.
7| J7| Bridging connection for alarms from another card.
8.1| P3: 1-3| Alarm output, NC.
8.2| P3:2| Alarm output, Com,
8.3| P3:3| Alarm output, NO,
9| P2: 1-10| Load output +/-
10| JU4| Jumper for setting the voltage in the card. Unbuilt = 24 V (factory
setting). Built = 12 V. The card must have the same voltage as the
motherboard.
Use the supplied cable
Use the cable that comes with the box to connect the card.
CONNECT 5 OUTPUT MODULE FOR MOTHERBOARD: CEO3 V2.1
Connect the card as shown in the illustration.
+ and – from load on motherboard is connected to + and – on the option card.
Communication is connected between terminals as the solid line shows.
Connections from battery backup to security card
Nr | Couplings | 5 Output module | Motherboard |
---|---|---|---|
1 | Power supply connection: | IN 12 V / 24 V | Load output 1 |
2 | Alarm output: switched between NO and Com. | J6 | JU3 – connect middle pin |
and one outer pin.
CONNECT 5 OUTPUT MODULE FOR MOTHERBOARD: CEO3 V5
Connect the card as shown in the illustration.
+ and – from load on motherboard is connected to + and – on the option card.
Communication is connected between terminals as the solid line shows.
Connections from battery backup to security card
Nr | Couplings | 5 Output module | Motherboard |
---|---|---|---|
1 | Power supply connection: | IN 12 V / 24 V | Load output 1 |
2 | Connection to alarm on motherboard or bridging of alarm to another 5 Output | ||
module | J6 |
J7
| J27
–
CONNECT 5 OUTPUT MODULE FOR MOTHERBOARD: NEO3
Connect the card as shown in the illustration.
+ and – from load on motherboard is connected to + and – on the option card.
Communication is connected between terminals as the solid line shows.
Connections from battery backup to security card
Nr | Couplings | 5 Output module | Motherboard |
---|---|---|---|
1 | Power supply connection: | IN 12 V / 24 V | Load output 1 |
2 | Connection to alarm on motherboard: | ||
bridging of alarms to / from additional option cards | J6 |
J7
| J5
–
CONNECT 5 OUTPUT MODULE FOR MOTHERBOARDS: PRO1 5 A AND 10 A
Connect the card as shown in the illustration.
+ and – from load on motherboard is connected to + and – on the option card.
Communication is connected between terminals as the solid line shows.
Connections from battery backup to security card
Nr | Couplings | 5 Output module | Motherboard |
---|---|---|---|
1 | Power supply connection: | IN 12 V / 24 V | Load output 1 |
2 | bridging of alarms for motherboards: |
bridging of alarms from / to additional option cards
| J7
J6
| J13
–
CONNECT 5 OUTPUT MODULE FOR MOTHERBOARD: PRO2 V3 15 A AND 25 A
Connect the card as shown in the illustration.
Connections 15 A and 25 A units
No. / letter | On circuit boards | Explanation |
---|---|---|
A | 5 Output module | Option card (A). |
B | 2 Output module | Connect power supply (24 V) to 5 Output module (A). |
C | Power card | Available in 15 A and 25 A units. |
D | PRO1 | Motherboard |
1 | IN 24 V | Connect power supply from 2 output module (B). |
2 | J7 | Connect alarm to load card. |
3, 4 | – | Internal power supply and communication between cards. |
CONNECT 5 OUTPUT MODULE FOR MOTHERBOARD: PRO2 V3 15 A AND 25 A
Connect the card as shown in the illustration.
Connections 15 A and 25 A units
No. / letter | circuit board | Explanation |
---|---|---|
C | Power card | Available only on 15 A and 25 A units. |
D | Motherboard | PRO2 v3 |
2 | J7 | Connect alarm to load card. |
1 | IN 24 V | Connect power supply from 2 output modules. |
A | 5 Output module | Option card. |
B | 2 Output module | Connect power supply (24 V) to 5 Output module. |
3, 4 | – | Internal power supply and communication between cards. |
CONNECT 5 OUTPUT MODULE FOR MOTHERBOARD: PRO3
Connect the card as shown in the illustration.
+ and – from load on motherboard is connected to + and – on the option card.
Communication is connected between terminals as the solid line shows.
Connections from battery backup to security card
Nr | Couplings | 5 Output module | Motherboard |
---|---|---|---|
1 | Power supply connection: | IN 12 V / 24 V | Load output 1 |
2 | Connection to alarm on motherboard: |
bridging of alarms to / from additional option cards.
| J7
J6
| J5
–
IF THE CARD LACKS A WHITE (JST) CONTACT OR IF THE ALARM IS TO BE GIVEN VIA RELAY SWITCHING
Connect the card as shown in the picture.
+ and – from load on motherboard are connected to + and – on the option
board.
Communication is connected between terminals as the solid line shows.
Connections from battery backup to fuse board
No | Connections | 5 Output module | Motherboard |
---|---|---|---|
1 | Power supply connection: | IN 12 V / 24 V | Load output 1 |
3 | Alarm output: | P3:1-2 | J15 |
CONNECTION OF ADDITIONAL 5 OUTPUT MODULE
Connection of additional option cards to motherboards
Note
For alarm connection use 2A and 2B for connection of newer devices (after
approx.
2018). For older devices (before approx. 2018) use 3A-3C.
Connection of additional option cards
Letter / No. | Explanation | On the card |
---|---|---|
A | 5 Output module. | – |
B | 5 Output module. | – |
C | Motherboard, varies with configuration. | – |
1 A | Power supply from 1B. | IN 24 V |
1 B | Power supply from C (motherboard). | IN 24 V |
2 A | Bridging of alarm to card B. | J7 |
2 B | Connection of alarm on C (motherboard) from card A | See table below. |
3 A | Jumper between cards A and B. | P3: 1-3 |
3 B | Alarm output switches on C (motherboard). | P3: 1-3 |
3 C | Alarm output is connected to C (motherboard). | P3: 1-3 |
P3 | Explanation | |
--- | --- | |
P3:1 | NC | |
P3:2 | Com | |
P3:3 | NO |
Alarms from optional cards are connected on terminal block (on motherboard)
Motherboard| Terminal as an alarm from an optional card must
be connected (on motherboard)
---|---
CEO3 v5| J27
Motherboard| Terminal as an alarm from an optional card must
be connected (on motherboard)
---|---
NEO3| J5
PRO1| J13
PRO2 v3| J1
PRO3| J5
TECHNICAL DATA – 5 OUTPUT MODULE
Info | Explanation |
---|---|
Short name: | 5 Output module |
Product description | 5 Output module is a fuse module with five fully fused |
outputs.
The product fits in| Battery backups with motherboards: PRO1, PRO2, PRO2 V3,
PRO3 and NEO3.
Measure| 85 x 37 mm
Own consumption| 35 mA
Tension| 12 V or 24 V
Fuses| On load outputs.
Indication| Yes, LED on circuit board
Outputs
Info | Explanation |
---|---|
Alarm outputs, number | 1 |
Alarm on alternating relay? (Yes No) | Yes, sum alarm in case of fuse fault |
Alarm output protocol (communication protocol) | – |
Info | Explanation |
--- | --- |
Load outputs, number | 5 |
Voltage at load output | 27.3 V DC |
Voltage limit, upper, on load output | 27.9 V DC |
Voltage limit, lower, on load output. For battery operation and disconnected
mains voltage.| 20 V DC
Priority (always voltage) load outputs (Yes / No)| Yes
Maximum load, per output| 10 A
Maximum load, total, (must not be exceeded).| 16 A
Load output plus (+) secured? (Yes No)| Yes
Load output minus (-) secured (Yes / No)| No
Connection to buzzer? (Yes No)| No
Manufactured in Milleteknik’s factory in Partille, Sweden.
This translation is not verified and should be cross referenced with the
swedish original before use.
ABOUT TRANSLATION OF THIS DOCUMENT
User manual and other documents are in the original language in Swedish.
Other languages are machine translated and not reviewed, errors may occur.
ADDRESS AND CONTACT DETAILS
Milleteknik AB
Ögärdesvägen 8 B
S-433 30 Partille| Sweden
+46 31 340 02 30
info@milleteknik.se
---|---
Milleteknik AB, Ögärdesvägen 8 B, 433 30 Partille
www.milleteknik.se
www.milleteknik.com
2023-11-29
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>