Milleteknik CEO3 5 Output Module User Manual

May 15, 2024
Milleteknik

TECHNICAL SPECIFICATIONS5 OUTPUT MODULE

CEO3 5 Output Module

5 Output module is a fuse module with five fully fused outputs. When ordering, check that the card fits the battery backup the card is to be installed in.

MOUNTING IN BATTERY BACKUP

The card is delivered mounted in it’s plastic casing, for easy installation.
If the card has come loose, snap it back into the plastic casing.
Mount the card on any card slot in the enclosure, leave space for cables.

Important
Install the board before screwing on wiring or commissioning.

Letter Explanation Comment
A Optional card Optional card comes mounted on plastic housing from factory.

Has it come loose? Snap it back on before
mounting the card.
B| Plastic casing| The plastic casing has hooks for attaching slots in the
plate.
C| Place for plastic casing| Slits in sheet metal to snap the plastic bracket.

CARD DESCRIPTION 5 OUTPUT MODULE

Milleteknik CEO3 5 Output Module - commissioning1

Circuit Board Overview – 5 Output module

Nr On circuit boards Explanation
1 D1-D4 Green indicator LED, illuminates with a solid green light when the

fuse is ok.
2| F1-F5| Fuses
---|---|---
3| J22, J23| Incoming voltage from motherboard, 24 V.
4| D29| Red indicator LED, illuminates with a solid green light when a fuse is broken.
5| D30| Green indicator LED, illuminates with a solid green light when the fuse is ok.
6| J6| Connection to alarm on motherboard.
7| J7| Bridging connection for alarms from another card.
8.1| P3: 1-3| Alarm output, NC.
8.2| P3:2| Alarm output, Com,
8.3| P3:3| Alarm output, NO,
9| P2: 1-10| Load output +/-
10| JU4| Jumper for setting the voltage in the card. Unbuilt = 24 V (factory setting). Built = 12 V. The card must have the same voltage as the motherboard.

Use the supplied cable
Use the cable that comes with the box to connect the card.

CONNECT 5 OUTPUT MODULE FOR MOTHERBOARD: CEO3 V2.1
Connect the card as shown in the illustration.

Milleteknik CEO3 5 Output Module - Connect

+ and – from load on motherboard is connected to + and – on the option card.
Communication is connected between terminals as the solid line shows.
Connections from battery backup to security card

Nr Couplings 5 Output module Motherboard
1 Power supply connection: IN 12 V / 24 V Load output 1
2 Alarm output: switched between NO and Com. J6 JU3 – connect middle pin

and one outer pin.

CONNECT 5 OUTPUT MODULE FOR MOTHERBOARD: CEO3 V5

Connect the card as shown in the illustration.

Milleteknik CEO3 5 Output Module - Connect1

+ and – from load on motherboard is connected to + and – on the option card.
Communication is connected between terminals as the solid line shows.
Connections from battery backup to security card

Nr Couplings 5 Output module Motherboard
1 Power supply connection: IN 12 V / 24 V Load output 1
2 Connection to alarm on motherboard or bridging of alarm to another 5 Output
module J6

J7

| J27

CONNECT 5 OUTPUT MODULE FOR MOTHERBOARD: NEO3
Connect the card as shown in the illustration.

Milleteknik CEO3 5 Output Module - Connect2

+ and – from load on motherboard is connected to + and – on the option card.
Communication is connected between terminals as the solid line shows.
Connections from battery backup to security card

Nr Couplings 5 Output module Motherboard
1 Power supply connection: IN 12 V / 24 V Load output 1
2 Connection to alarm on motherboard:
bridging of alarms to / from additional option cards J6

J7

| J5

CONNECT 5 OUTPUT MODULE FOR MOTHERBOARDS: PRO1 5 A AND 10 A

Connect the card as shown in the illustration.

Milleteknik CEO3 5 Output Module - Connect3

+ and – from load on motherboard is connected to + and – on the option card.
Communication is connected between terminals as the solid line shows.
Connections from battery backup to security card

Nr Couplings 5 Output module Motherboard
1 Power supply connection: IN 12 V / 24 V Load output 1
2 bridging of alarms for motherboards:

bridging of alarms from / to additional option cards

| J7

J6

| J13

CONNECT 5 OUTPUT MODULE FOR MOTHERBOARD: PRO2 V3 15 A AND 25 A

Connect the card as shown in the illustration.

Milleteknik CEO3 5 Output Module - Connect4

Connections 15 A and 25 A units

No. / letter On circuit boards Explanation
A 5 Output module Option card (A).
B 2 Output module Connect power supply (24 V) to 5 Output module (A).
C Power card Available in 15 A and 25 A units.
D PRO1 Motherboard
1 IN 24 V Connect power supply from 2 output module (B).
2 J7 Connect alarm to load card.
3, 4 Internal power supply and communication between cards.

CONNECT 5 OUTPUT MODULE FOR MOTHERBOARD: PRO2 V3 15 A AND 25 A

Connect the card as shown in the illustration.

Connections 15 A and 25 A units

No. / letter circuit board Explanation
C Power card Available only on 15 A and 25 A units.
D Motherboard PRO2 v3
2 J7 Connect alarm to load card.
1 IN 24 V Connect power supply from 2 output modules.
A 5 Output module Option card.
B 2 Output module Connect power supply (24 V) to 5 Output module.
3, 4 Internal power supply and communication between cards.

CONNECT 5 OUTPUT MODULE FOR MOTHERBOARD: PRO3
Connect the card as shown in the illustration.

Milleteknik CEO3 5 Output Module - Connect7

+ and – from load on motherboard is connected to + and – on the option card.
Communication is connected between terminals as the solid line shows.
Connections from battery backup to security card

Nr Couplings 5 Output module Motherboard
1 Power supply connection: IN 12 V / 24 V Load output 1
2 Connection to alarm on motherboard:

bridging of alarms to / from additional option cards.

| J7

J6

| J5

IF THE CARD LACKS A WHITE (JST) CONTACT OR IF THE ALARM IS TO BE GIVEN VIA RELAY SWITCHING

Connect the card as shown in the picture.

+ and – from load on motherboard are connected to + and – on the option board.
Communication is connected between terminals as the solid line shows.
Connections from battery backup to fuse board

No Connections 5 Output module Motherboard
1 Power supply connection: IN 12 V / 24 V Load output 1
3 Alarm output: P3:1-2 J15

CONNECTION OF ADDITIONAL 5 OUTPUT MODULE

Connection of additional option cards to motherboards

Milleteknik CEO3 5 Output Module - Connect9

Note
For alarm connection use 2A and 2B for connection of newer devices (after approx.
2018). For older devices (before approx. 2018) use 3A-3C.
Connection of additional option cards

Letter / No. Explanation On the card
A 5 Output module.
B 5 Output module.
C Motherboard, varies with configuration.
1 A Power supply from 1B. IN 24 V
1 B Power supply from C (motherboard). IN 24 V
2 A Bridging of alarm to card B. J7
2 B Connection of alarm on C (motherboard) from card A See table below.
3 A Jumper between cards A and B. P3: 1-3
3 B Alarm output switches on C (motherboard). P3: 1-3
3 C Alarm output is connected to C (motherboard). P3: 1-3
P3 Explanation
--- ---
P3:1 NC
P3:2 Com
P3:3 NO

Alarms from optional cards are connected on terminal block (on motherboard)

Motherboard| Terminal as an alarm from an optional card must be connected (on motherboard)
---|---
CEO3 v5| J27
Motherboard| Terminal as an alarm from an optional card must be connected (on motherboard)
---|---
NEO3| J5
PRO1| J13
PRO2 v3| J1
PRO3| J5

TECHNICAL DATA – 5 OUTPUT MODULE

Info Explanation
Short name: 5 Output module
Product description 5 Output module is a fuse module with five fully fused

outputs.
The product fits in| Battery backups with motherboards: PRO1, PRO2, PRO2 V3, PRO3 and NEO3.
Measure| 85 x 37 mm
Own consumption| 35 mA
Tension| 12 V or 24 V
Fuses| On load outputs.
Indication| Yes, LED on circuit board

Outputs

Info Explanation
Alarm outputs, number 1
Alarm on alternating relay? (Yes No) Yes, sum alarm in case of fuse fault
Alarm output protocol (communication protocol)
Info Explanation
--- ---
Load outputs, number 5
Voltage at load output 27.3 V DC
Voltage limit, upper, on load output 27.9 V DC

Voltage limit, lower, on load output. For battery operation and disconnected mains voltage.| 20 V DC
Priority (always voltage) load outputs (Yes / No)| Yes
Maximum load, per output| 10 A
Maximum load, total, (must not be exceeded).| 16 A
Load output plus (+) secured? (Yes No)| Yes
Load output minus (-) secured (Yes / No)| No
Connection to buzzer? (Yes No)| No

Manufactured in Milleteknik’s factory in Partille, Sweden.
This translation is not verified and should be cross referenced with the swedish original before use.

ABOUT TRANSLATION OF THIS DOCUMENT

User manual and other documents are in the original language in Swedish.
Other languages are machine translated and not reviewed, errors may occur.

ADDRESS AND CONTACT DETAILS

Milleteknik AB
Ögärdesvägen 8 B
S-433 30 Partille| Sweden
+46 31 340 02 30
info@milleteknik.se
---|---

Milleteknik AB, Ögärdesvägen 8 B, 433 30 Partille

www.milleteknik.se
www.milleteknik.com
2023-11-29

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals