milleteknik 24 V FLX M UPS Battery Box
TECHNICAL SPECIFICATIONS: THE UPS BATTERY BOX
The battery box is made for two 45 Ah batteries and can be connected to the UPS in FLX L housing. See This battery box fits the following UPSs [4] UPSs this battery box fits.
Manufacturer support
Manufacturers provide support for the life of the product, however, for a
maximum of 10 years after the date of purchase. Switching to an equivalent
product may occur if the manufacturer deems that repair is not possible.
Support costs will be added after the warranty period has expired.
About translation of this document
User manual and other documents are in the original language in Swedish. Other
languages are machine translated and not reviewed, errors may occur.
Product life cycle, environmental impact and recycling
The product is designed and constructed for a long service life, which reduces
the environmental impact. The product’s service life depends on, among other
things, environmental factors, mainly ambi-ent temperature, unforeseen load on
components such as lightning strikes, external damage, handling errors, and
more. Products are recycled by being handed over to the nearest recycling
station or sent back to the manufacturer. Contact your distributor for more
information. Costs that arise in connection with recycling are not reimbursed.
THIS BATTERY BOX FITS THE FOLLOWING UPSS
UPS | Item number |
---|---|
SIN 600W FLX L | FL01U0021FP006 |
SIN 1100W FLX L | FL01U0031FP011 |
SIN 1500W FLX L | FL01U0031FP015 |
TEL-1200W-STS-SIN2* | 5144 |
*Not sold directly by Milleteknik .
BATTERIES – PLACEMENT AND CONNECTION
Placement of batteries
No | Explanation |
---|---|
1 | Insert the battery on the left first (I). |
2 | Then insert the battery on the right (I). |
3 | In the battery box, batteries are inserted in the same way as in battery |
backup (II).
Connection battery box with battery backup
The picture shows a battery backup with extra battery box with 2 batteries.
The picture also gives an overview of connection points for battery cables and
battery fuses.
Table 1. Overview of incoming mains and battery connection
No. / letter | Explanation |
---|---|
I, III | Battery wiring for automatic fuse. |
II | Battery wiring from motherboard. |
IV | Battery wiring, on Battery connector, from battery box, must be connected |
with opposite battery connector in UPS.
4,5| Battery fuse (automatic fuse)
T3| Internal emergency stop.
T2| Phase, mains, incoming.
T1| Neutral mains, incoming.
PE| Incoming protective earth.
Table 2. Battery number
B1, B2 | Explanation |
---|---|
B1+ | + from circuit board/battery connector to battery |
B1- | – from fuse to battery. |
B2+ | + from fuse to battery. |
B2- | – from circuit board/battery connector to battery. |
TEKNISKA DATA UPS
System voltage: | 24 V. |
---|---|
Battery type: | AGM lead acid. |
Enclosure: | Powder coated sheet. |
Mounting: | Wall or 19 “rack. |
Country of manufacture | Sweden |
TECHNICAL DATA ENCLOSURES
Enclosures – Technical Data FLX M
Info | Explanation |
---|---|
Name | FLX M |
Enclosure class | IP 32 |
Measure | Height: 224 mm, width 438 mm, depth 212 mm |
Height units | 5 HE |
Mounting | Wall or 19 “rack |
Ambient temperature | + 5 ° C – + 40 ° C. For best battery life: + 15 ° C to + |
25 ° C.
Environment| Environmental class 1, indoors. 20% ~ 90% relative humidity
Material| Powder coated sheet
Color| Black
Cable entries, number| 4 Knockout for Battery connector
Info| Explanation
---|---
Batteries that fit| 2 pcs 12 V, 45 Ah.
BATTERIES – RECOMMENDED, NOT INCLUDED
Batteries are not included they are sold separately
Batteries are sold separately.
45 Ah, 12 V AGM battery
Fits in | Number of batteries |
---|---|
Battery box 24V FLX M | 2 |
Battery type | V |
--- | --- |
Maintenance-free AGM, lead-acid battery. | 12 V |
*Table 3. 10+ Design life battery**
Article number| E-number| Article name| Terminal|
Measure. Height width depth| Weight per piece| Make
---|---|---|---|---|---|---
MT113-12V45-01| 5230546| UPLUS 12V 45Ah
10+ Design Life battery
| M5 Bult| 197x165x170 mm| 14.5 kg| UPLUS
Design life is the shelf life in years for an unused battery. Environmental factors such as heat and load affect the service life. Batteries that have a durability (+10 Design Life) of 10+ years usually need to be replaced after 5-6 years.
MAINTENANCE
The system with the exception of batteries is maintenance-free when installed
in an indoor environment.
Check the fan annually. The fan should rotate smoothly without any noise.
Clean the fan from dust and dirt. The fan must be replaced if it does not
rotate smoothly or is so dirty that it cannot be completely cleaned. If the
fan does not work well, the air flow in the unit will be obstructed, which
leads to an increase in heat in the enclosure, which can lead to a
deterioration of the battery capacity and to a significantly shorter battery
replacement interval.
About batteries
Batteries generate electricity through a chemical process and there is thus a
natural degradation of capacity. The biggest factor in battery life is
temperature. The higher the temperature, the shorter the battery life. The
date of manufacture stamped on the battery and the service life (as stated by
the battery manufacturer). An ideal temperature is 20 °C both in operation and
in storage. Higher ambient temperature greatly reduces the service life. Thus,
actual lifespan varies when used. Batteries should be replaced after half
specified (from the battery manufacturer) lifetime for safe operation.
Batteries purchased through the manufacturer of the battery backup have a
lifespan (from the battery manufacturer) of between 10-12 years with
recommended replacement after 5-6 years.
Battery Change
- If possible, disconnect mains (voltage) when replacing the battery.
- Disconnect battery cables. Note how battery cables are mounted before removing them.
- Remove battery fuse between batteries.
- Insert and fasten the new batteries.
- Connect the battery cables in the same way as before.
- Connect battery fuse between batteries.
- Switch on mains voltage. The indicator LED may not be green (up to 72 hours), until the batteries are charged.
- In order for the system to measure the capacity of new batteries, the device needs to clear previous battery capacity. Dip-switch 8 performs a software reset which, among other things, resets alarms. See Resetting data after battery change (Dip-switch 8)
- Test the system by briefly disconnecting the mains voltage, (= the load is driven by the batteries), and then switch on the mains voltage again.
Battery recycling
All batteries must be recycled. Return to manufacturer or return to
recycling station.