Faith GLS-20A-IV Non-Tamper Resistant Receptacles User Guide

June 14, 2024
FAITH

Faith GLS-20A-IV Non-Tamper-Resistant Receptacles

What is a GFCI?

A GFCI receptacle is different from conventio- nal receptacles. In the event of a ground fault, a GFCI will trip and quickly stop the flow of ele- ctricity to prevent serious injury.

Definition of a ground fault:
Instead of following its normal safe path, elec- tricity passes through a person’s body to reach the ground. For example, a defective appliance can cause a ground fault.

A GFCI receptacle does NOT protect against circuit overloads, short circuits, or shocks. For example, you can still be shocked if you touch bare wires while standing on a non-conducting surface, such as a wood floor.

The Tamper Resistant Outlets Built-in Safety Action. Spring-loaded shutter mechanism restricts access to an object in any one side of the outlet. R

The GFCI’s features

A CAUTION

  • To prevent severe shock or electrocution always turn the power OFF at the service panel before working with wiring.
  • Use this GFCI with copper or copper- clad wire. Do not use it with aluminum wire.
  • Do not install this GFCI receptacle on a circuit that powers life support equi- pment because if the GFCI trips it will shut down the equipment.
  • For installation in wet locations, prote- ct the GFCI receptacle with a weath- erproof cover that will keep both the receptacle and any plugs dry.
  • Must be installed in accordance with national and local electrical codes.

Should you install it?
Installing a GFCI receptacle can be more complicated than installing a conventional receptacle.

Make sure that you:

  • Understand basic wiring principles and techniques
  • Can interpret wiring diagrams
  • Have circuit wiring experience
  • Are prepared to take a few minutes to test your work, making sure that you have wired the GFCI receptacle correctly

LINE vs. LOAD

A cable consists of 2 or 3 wires

LINE cable:
Delivers power from the service panel (breaker panel or fuse box) to the GFCI. If there is only one cable entering the electrical box, it is the LINE cable. This cable should be connected to the GFCI’s LINE terminals only.

LOAD cable:
Delivers power from the GFCI to another receptacle in the circuit. This cable should be connected to the GFCI’s LOAD terminals only. The LOAD terminals are under the yellow sticker. Do NOT remove the sticker at this time

Turn the power OFF

Plug an electrical device, such as a lamp or radio, into the receptacle on which you are working. Turn the lamp or radio ON. Then, go to the service panel. Find the breaker or fuse that protects that receptacle. Place the breaker in the OFF position or completely remove the fuse. The lamp or radio must turn OFF.

Next, plug in and turn ON the lamp or radio at the receptacle’s other outlet to make sure the power is OFF at both outlets. If the power is not OFF, stop work and call an electrician to complete the installation.

Identify cables/wires

Important:

  • DO NOT install the GFCI receptacle in an electrical box containing (a) more than four (4) wires (not including the grounding wires) or (b) cables with more than two (2) wires (not including the grounding wire) Contact a qualified electrician if either (a) or (b) are true.
  • If you are replacing an old receptacle, pull it out of the electrical box without disconnecting the wires.
  • If you see one cable (2-3 wires), it is the LINE cable. The receptacle is probably in position C (see diagram to the right).
  • Remove the receptacle and go to step 7A.
  • If you see two cables (4-6 wires), the receptacle is probably in position A or B (see diagram to the right). Follow steps a-e of the procedure to the right

Procedure : box with two (2) cables (4-6 wires):

  • Detach one cable’s white wire and hot wires from the receptacle and cap each one separately with a wire connector.
  • Make sure that they are from the same cable.
  • Re-install the receptacle in the electrical box, attach faceplate, then turn the power ON at the service panel.
  • Determine if power is flowing to the receptacle. If so, the capped wires are the LOAD wires. If not, the capped wires are the LINE wires.
  • Turn the power OFF at the service panel, label the LINE and LOAD wires, then remove the receptacle.
  • Go to step 7B.

Placement in circuit:
The GFCI’s place in the circuit determines if it protects other receptacles in the circuit.

Sample circuit:

Placing the GFCI in position A will also provide protection to “load side” receptacles B and C. On the other hand, placing the GFCI in position C will not provide protection to receptacles A or B. Remember that receptacles A, B, and C can be in different rooms.

Connect the wires

Connect the wires (choose A or B)… only after reading other side completely

A: One Cable (2 or 3 wires) entering the box

Connect the LINE cable wires to the LINE terminals:

  • The white wire connects to the WHITE terminal (Silver)
  • The black wire connects to the HOT terminal (Brass or Black)

Connect the grounding wire (only if there is a grounding wire):

  • For a box with no grounding terminal (diagram not shown): Connect the LINE cable’s bare copper (or GREEN) wire directly to the grounding terminal on the GFCI receptacle.
  • For a box with a grounding terminal (diagram shown above): Connect a 6-inch bare copper (or GREEN) 12 or 14 AWG wire to the grounding terminal on the GFCI. Also connect a similar wire to the grounding terminal on the box. Connect the ends of these wires to the LINE cable’s bare copper (or GREEN) wire using a wire connector. If these wires are already in place, check the connections.

Complete the installation:

  • Fold the wires into the box, keeping the grounding wire away from the WHITE and HOT terminals. Screw the receptacle to the box and attach the faceplate.
  • Go to step 8.

B: Two cables (4 or 6 wires) entering the box

Connect the LINE cable wires to the LINE terminals:

  • The white wire connects to the WHITE terminal (Silver)
  • The black wire connects to the HOT terminal (Brass or Black)

Connect the LOAD cable wires to the LOAD terminals:

  • Remove the YELLOW sticker to reveal the LOAD terminals
  • The white wire connects to the WHITE terminal (Silver)
  • The black wire connects to the HOT terminal (Brass or Black)

Connect the grounding wires (only if there is a grounding wire):

  • Connect a 6-inch bare copper (or GREEN) 12 or 14 AWG wire to the grounding terminal on the GFCI. If the box has a grounding terminal, also connect a similar wire to the grounding terminal on the box.
  • Connect the ends of these wires to the LINE or LOAD cable’s bare copper (or GREEN) wire using a wire connector. If these wires are already in place, check the connections.

Complete the installation:

  • Fold the wires into the box, keeping the grounding wire away from the WHITE and HOT terminals. Screw the receptacle to the box and attach the faceplate.
  • Go to step 8

Test your work

Why perform this test?

  • If you miswired the GFCI it may not prevent personal injury or death due to a ground fault (electrical shock).
  • If you mistakenly connect the LINE wires to the LOAD terminals, the GFCI will not reset and will not provide power to either the GFCI receptacle face or any receptacles fed from the GFCI.

Procedure:

  • This GFCI is shipped from the factory in the tripped condition and cannot be reset until it is wired correctly and power is supplied to the device. Plug a lamp or radio into the GFCI (and leave it plugged in).
  • Turn the power ON at the service panel. Ensure that the GFCI is still in the tripped condition by pressing the TEST button. If the lamp or radio is OFF, and the GFCI will not reset, go to the Troubleshooting section as the Line and Load connections are reversed.
  • Press the RESET button fully and release. If the Status Indicator Light turns Green and the lamp or radio is ON, the GFCI has been installed correctly. If the Status Indicator Light turns or continuously blinks Red, or the GFCI cannot be reset, go to the Self-Test Operation section.
  • If you installed your GFCI using step 7B, plug a lamp or radio into surrounding receptacles to see which one(s), in addition to the GFCI, lose power when you press the GFCI TEST button.
  • Place a “GFCIPROTECTED OUTLET” sticker on every receptacle that lost power, then press the RESET button to reset the GFCI. DO NOT plug life saving devices into any of the receptacles that lost power.
  • Press the TEST button (then RESET button) every month to assure proper operation. If the Status Indicator Light does not turn Green when the RESET button is depressed and then released, or the GFCI cannot be reset, it must be replaced.

TROUBLESHOOTING

Turn the power OFF and check the wire connections against the appropriate wiring diagram in step 7A or 7B. Make sure that there are no loose wires or loose connections. If the Status Indicator Light is not ON and the device is unable to reset this could be a result of no power available. Start the test from the beginning of step 8 if you rewired any connections to the GFCI.

SELF-TEST OPERATION

  • A Self-Test GFCI receptacle has all the features of a conventional GFCI receptacle. In addition, this receptacle tests itself periodically to confirm the GFCI electronics are functional. The Status Indicator Light will be solid green when the GFCI is powered from Line side and working correctly.
  • Self-Test Indications: If the Status Indicator Light is solid or flashing RED a problem may exist. Press the TEST button to trip the GFCI. If unable to Reset, replace the GFCI. NOTE: The status indicator may flash Red at power “ON” and Reset.

WARRANTY

LIMITED 2 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product
at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for two years from the purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option. For details visit www.leviton.com or call 1-800-824-3005. This warranty excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to two years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.

For Technical Assistance Call

FAQs

What are the Faith GLS-20A-IV-10 Non-Tamper Resistant Receptacles?

The Faith GLS-20A-IV-10 Non-Tamper Resistant Receptacles are electrical outlets designed for various indoor applications that do not feature tamper- resistant safety features.

What is the amperage rating of these receptacles?

The Faith GLS-20A-IV-10 receptacles typically have an amperage rating of 20 amps, suitable for a range of devices and appliances.

Are these receptacles suitable for residential use?

Yes, these receptacles are commonly used in residential settings for powering electrical devices and appliances.

Do they come with GFCI (Ground Fault Circuit Interrupter) protection?

No, the Faith GLS-20A-IV-10 receptacles do not typically include GFCI protection, so they may not be suitable for wet or outdoor locations.

What is the voltage rating of these receptacles?

The voltage rating of the Faith GLS-20A-IV-10 receptacles can vary, but they are often designed for standard 120-volt AC electrical systems.

Are they compatible with standard electrical plugs?

Yes, these receptacles are typically designed to be compatible with standard North American electrical plugs.

Can they be installed in commercial settings?

Yes, these receptacles can be used in commercial settings where tamper- resistant features are not required.

Is professional installation recommended for these receptacles?

Professional installation is often recommended to ensure proper wiring and safety when installing electrical receptacles.

Do they come in a specific color or finish?

The Faith GLS-20A-IV-10 receptacles may come in various colors or finishes, but the specific options may vary.

Are these receptacles compatible with wall plates?

Yes, they are typically compatible with standard wall plates for a clean and finished appearance.

Can they be used for both residential and commercial applications?

Yes, these receptacles are versatile and can be used in both residential and commercial settings where non-tamper-resistant outlets are appropriate.

What is the warranty for the Faith GLS-20A-IV-10 Non-Tamper Resistant Receptacles?

Warranty details may vary, so it's advisable to check the product documentation or contact the manufacturer for warranty information.

Video-Introduction

Download This PDF Link: Faith GLS-20A-IV-10 Outlets Non-Tamper Resistant Receptacles User Guide

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals