Faith GLS-15A-WH Non-Tamper Resistant Duplex Receptacle User Manual

June 14, 2024
FAITH

Faith GLS-15A-WH Non-Tamper Resistant Duplex Receptacle

Faith-GLS-15A-WH Non-Tamper-Resistant-Duplex-Receptacle-product

What is a GFCI?

A GFCI receptacle is different from conventio- nal receptacles. In the event of a ground fault, a GFCI will trip and quickly stop the flow of ele- ctricity to prevent serious injury.

Definition of a ground fault:

  • Instead of following its normal safe path, electricity passes through a person’s body to reach the ground. For example, a defective appliance can cause a ground fault.
  • A GFCI receptacle does NOT protect against circuit overloads, short circuits, or shocks. For example, you can still be shocked if you touch bare wires while standing on a non-conducting surface, such as a wood floor.
  • The Tamper Resistant Outlets Built-in Safety Action.
  • Spring-loaded shutter mechanism restricts access to an object in any one side of the outlet.

The GFCI’s features

Procedure : box with two (2) cables (4-6 wires)

  • Detach one cable’s white and hot wires from the receptacle and cap each one separately with a wire connector. Make sure that they are from the same cable.
  • Re-install the receptacle in the electrical box, attach faceplate, then turn the power ON at the service panel.
  • Determine if power is flowing to the rece- ptacle. If so the capped wires are the LOAD wires. If not the capped wires are the LINE wires.
  • Turn the power OFF at the service panel, label the LINE and LOAD wires, then remove the receptacle.
  • Go to step 7B.

Placement in circuit:
The GFCl’s place in the circuit determines if it protects other receptacles in the circuit.

Sample circuit:

Placing the GFCI in position A will also pro- vide protection to ” load side ” receptacles B and C. On the other hand, placing the GFCI in position C will not provide protecti- on to receptacles A or B. Remember that receptacles A, B, and C can be in different rooms.

Should you install it?

  • Comica cal sping cove monal receptacle.

Make sure that you:

  • Understand basic wiring principles and techniques
  • Can interpret wiring diagrams
  • Have circuit wiring experience

LINE vs. LOAD

A cable consists of 2 or 3 wires.

LINE cable:
the GFCI’s LINE terminals only.

LOAD cable:
Delivers power from the GFCI to another receptacle in the circuit. This cable should be connected to the GFCI’s LOAD terminals only. The LOAD terminals are under the yellow sticker. Do NOT remove the sticker at this time.

Turn the power OFF
Plug an electrical device, such as a lamp or radio, into the receptacle on which you are working. Turn the lamp or radio ON. Then, go to the service panel. Find the breaker or fuse that protects that receptacle. Place the breaker in the OFF position or completely remove the fuse. The lamp or radio must turn OFF. Next, plug in and turn ON the lamp or radio at the receptacle’s other outlet to make sure the power is OFF at both outlets. If the power is not OFF, stop work and call an electrician to complete the installation.

Identify cables/wires

Important:

DO NOT install the GFCI receptacle in an electrical box containing (a) more than four (4) wires (not including the grounding wires) or (b) cables with more than two (2) wires (not including the grounding wire). Contact a qualified electrician if either (a) or (b) are true.

  • If you are replacing an old receptacle, pull it out of the electrical box without disconnecting the wires.
  • If you see one cable (2-3 wires), it is the LINE cable. The receptacle is probably in position C (see diagram to the right).Rem- ove the receptacle and go to step 7A.
  • If you see two cables ( 4-6 wires ), the receptacle is probably in position A or B (see diagram to the right) Follow steps a-e of the procedure to the right.

Connect the wires

Connect the wires (choose A or B)… only after reading other side completely

Faith-GLS-15A-WH Non-Tamper-Resistant-Duplex-Receptacle-
fig-6

A: One Cable (2 or 3 wires) entering the box

Connect the LINE cable wires to the LINE terminals:

  • The white wire connects to the WHITE terminal (Silver)
  • The black wire connects to the HOT terminal (Brass)

Connect the grounding wire (only if there is a grounding wire):

  • For a box with no grounding terminal (diagram not shown): Connect the LINE cable’s bare copper (or GREEN) wire directly to the grounding terminal on the GFCI receptacle.
  • Fora box with a grounding terminal (diagram shown above): Connect a 6-inch bare copper (or GREEN) 12 or 14 AWG wire to the grounding terminal on the GFCI, also connect a similar wire to the grounding terminal on the box. Connect the ends of these wires to the LINE cable’s bare copper (or GREEN) wire using a wire connector. If these wires are already in place, check the connections.

Complete the installation:

  • Fold the wires into the box, keeping the grounding wire away from the WHITE and HOT terminals. Screw the receptacle to the box and attach the faceplate.
  • Go to step 8.

B: Two cables (4 or 6 wires) entering the box

Faith-GLS-15A-WH Non-Tamper-Resistant-Duplex-Receptacle-
fig-7

Connect the LINE cable wires to the LINE terminals:

  • The white wire connects to the WHITE terminal (Silver)
  • The black wire connects to the HOT terminal (Brass)

Connect the LOAD cable wires to the LOAD terminals:

  • Remove the YELLOW sticker to reveal the LOAD terminals
  • The white wire connects to the WHITE terminal (Silver)
  • The black wire connects to the HOT terminal (Brass)

Connect the grounding wires as shown above (only if there is a grounding wire):

  • Connect a 6-inch bare copper (or GREEN) 12 or 14 AWG wire to the grounding terminal on the GFCI. If the box has a grounding terminal, also connect a similar wire to the grounding terminal on the box. Connect the ends of these wires to the LINE or LOAD cable’s bare copper (or GREEN) wire using a wire connector. If these wires are already in place, check the connections

Complete the installation:

  • Fold the wires into the box, keeping the grounding wire away from the WHITE and HOT terminals. Screw the receptacle to the box and attach the faceplate.
  • Go to step 8.

Test your work

Why perform this test?

  • If you miswire the GFCI it may not prevent personal injury or death due to a ground fault (electrical shock).
  • If you mistakenly connect the LINE wires to the LOAD terminals the GFCI will not work normally and will provide no power.

Procedure:

  • Turn the power ON at the service panel. Press RESET. The LED indicator starts emitting green light, If no light from function indictor,go to Troubleshooting.
  • Press the RESET button fully, then plug a lamp or radio into the GFC (and leave it plugged-in) to verify that the power is ON. If there is no power, go to Troubleshooting.
  • Press the TEST button in order to trip the GFCI. Indication light will turn off. The GFCI should stop the flow of electricity making the radio or lamp shut OFF, the RESET button should pop-out. If the power stays ON, go to Troubleshooting.
  • If the power goes OFF, you have installed the GFCI receptacle correctly.
  • To restore power, press the RESET button.The LED indication should light up.
  • If you installed your GFCI using set 7B, plug a lamp or radio into the surrounding receptacles to see which one(s), in addition to the GFCI, lost power when you pressed the TEST button,do not plug life saving devices into any receptacles that lost power. Place a GFCI Protected sticker on every receptacle that lost power.
  • Press the TEST button every month to assure proper operation, ther
  • Press the RESET button

TROUBLESHOOTING

Turn the power OFF and check the wire connections against the appropriate wiring diagram in step 7A or 7B. Make sure that there are no loose wires or loose connections. Also, it is possible that you reversed the LINE and LOAD connections ‚then you press The RESET button, it will not work, Start the test from the beginning of step 8 if you rewired any connections to the GFCI.

WARRANTY

LIMITED ONE YEAR WARRANTY AND EXCLUSIONS
This company warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by this company is free of defects in materials and workmanship under normal and proper use for one year from the purchase date. This Co. only obligation is to correct such defects by repair or replacement, at its option, if within such one year period the product is retumed prepaid, with proof of purchase date, and a description of the problem to this Co. This warranty excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improper or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to one year, this company is not liable for incidental, indirect, special, or consequential damages, lost sales or profits or delay or failure to perform this warranty obligation. The remedies, provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.

FAQs

What is the Faith GLS-15A-WH Non-Tamper Resistant Duplex Receptacle?

The Faith GLS-15A-WH is a non-tamper resistant duplex receptacle, commonly used for electrical outlets in homes and buildings.

What is the amperage rating of the Faith GLS-15A-WH receptacle?

The Faith GLS-15A-WH receptacle typically has a 15-ampere (A) rating, suitable for most standard household electrical devices.

Is this receptacle suitable for both residential and commercial use?

Yes, the Faith GLS-15A-WH receptacle is versatile and can be used in both residential and commercial applications.

Is it compatible with standard duplex outlet covers and faceplates?

Yes, the Faith GLS-15A-WH receptacle is designed to be compatible with standard duplex outlet covers and faceplates.

Does it have GFCI (Ground Fault Circuit Interrupter) protection?

No, the Faith GLS-15A-WH receptacle is non-tamper resistant and typically does not include GFCI protection.

Can this receptacle be installed outdoors?

It is not recommended to install the Faith GLS-15A-WH receptacle outdoors, as it may not be designed for outdoor use and exposure to the elements.

Is professional installation required, or can it be installed by DIY enthusiasts?

Installation requirements may vary, but it's generally recommended to have electrical receptacles installed by a qualified electrician for safety.

What is the voltage rating for the Faith GLS-15A-WH receptacle?

The voltage rating for this receptacle is typically 125 volts (V) AC.

Is there a warranty provided for the Faith GLS-15A-WH receptacle?

Please check the product documentation or contact the manufacturer for information about any warranty coverage.

Can it accommodate two plugs simultaneously?

Yes, the Faith GLS-15A-WH receptacle is a duplex receptacle, meaning it can accommodate two plugs at the same time.

Video-Introduction

Download This PDF Link: Faith GLS-15A-WH Non-Tamper Resistant Duplex Receptacle User Manual

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals