ALLMATIC BIOS1 Control Unit Installation Guide
- June 14, 2024
- ALLMATIC
Table of Contents
BIOS1 Control Unit
Installation Guide
BIOS1 Control Unit
Introduction
The control unit BIOS1 is particularly indicated for the installation of 1 230
Vac motor with maximum power absorbed of 700W. The control unit equipped with
a display that allows a precise regulation of the thrust and sensitivity. The
control unit can memorize up to 8000 transmitters with the external memory,
with the step by step, partial opening, open and close functions. It is
supplied with inputs for interior and exterior photocell, possibility to
connect the buttons for step by step, partial opening, open, close and stop.
The outputs include a 230 Vac flashing light, courtesy light/zone light/ open
gate light, 24 Vdc accessories power supply.
ATTENTION: DO NOT INSTALL THE CONTROL UNIT WITHOUT READING THE
INSTRUCTIONS FIRST !!!
THE INSTALLATION SHOULD BE PERFORMED ONLY BY QUALIFIED PERSONNEL.
Be sure that the limit switches are connected and correctly adjusted
Configuration
Connections
MOTOR OUTPUT
Connect the common of the motor to the clamp motor COM of the control unit.
Connect the phase 1 of the motor to the clamp motor L1 of the control unit.
Connect the phase 2 of the motor to the clamp L2 of the control unit.
Motor condensers 230 Vac !Risk of electric shock! CAPACITOR
Connect the capacitor to the clamps COND of the control unit. LIMIT
SWITCHES
Connect the NORMALLY CLOSED contact of the limit switches to the control unit
During the learning of the stroke phase the control unit recognize itself the
opening and closing limit switch. POWER SUPPLY
Connect the power supply cable between clamp 1 and 2 of the control unit
Power supply 230 Vac 50 Hz
Do not connect the card directly to the electric network. Put a device
which can ensure the disconnection of each pole from the power supply of the
control unit.
COURTESY LIGHT OUTPUT
Connect the courtesy light to the clamps 3 and 4, 230Vac 100W MAX.
FLASHING LIGHT OUTPUT
Connect the flashing light to the clamps 3 and 5.b
It is possible to light up the action area of the automatism during each
motion. The functioning of the auxiliary light is controlled in the advanced
menu FCY.
Use a flashing light without self flashing card 230Vac 60W MAX PHOTOCELLS
POWER SUPPLY
Connect the clamp 6 of the control unit to the clamp + of the power supply of
the photocells receiver.
Connect the clamp 7 of the control unit to the power supply clamp – of the
photocells receiver and of the transmitter.
Connect the clamp 8 of the control unit to the power supply clamp of the
transmitter of the photocells.
The photocells test is activated in the advanced menu tph.
ATTENTION: the control unit gives a voltage of 24 Vdc and can supply a
maximum power of 4W.
For the safety edge test connect the test device of the safety edge on the
power supply pins of the TX (test activated with low logic signal 0Vdc).
Please refer to the manual of the safety edge. SAFETY EDGE INPUT
Connect the safety edge contacts to the clamps 9 and 10 of the control unti
Select the type of security edge used (mechanical or 8K2) through the menu
EDMX, select the type of functioning through the minuid. If not used set the
DIP switch EDGE ON. OPENING PHOTOCELL INPUT
Connect the NORMALLY CLOSED contact of the photocell (PHOTO 2) between the
clamps 11 and 18 of the control unit.
The functioning of the opening photocell is controlled in the advanced menu
Ph2. If not used set the DIP switch PH2 ON. CLOSING PHOTOCELL INPUT
Connect the NORMALLY CLOSED contact of the photocell (PHOTO 1) between the
clamps 12 and 18 of the control unit.
The functioning of the closing photocell is controlled in the advanced menu
Sph. If not used set the DIP switch PH1 ON. STOP INPUT
Connect the NORMALLY CLOSED contact of the STOP between the clamps 13 and 18
of the control unit.
If not used set the DIP switch STOP ON. OPEN INPUT
Connect the button OPEN between the clamps 14 and 18 of the control unit.
CLOSE INPUT
Connect the button CLOSE between the clamps 15 and 18 of the control unit.
PARTIAL OPENING INPUT
Connect the button PED between the clamps 16 and 18 of the control unit.
STEP BY STEP INPUT
Connect the button SS between the clamps 17 and 18 of the control unit.
ANTENNA
Connect the signal cable of the antenna to the clamp 19 and the ground of the
antenna to the clamp 20 of the control unit.
The presence of the metallic parts or humidity in the walls could have
negative influences on the range of the system. We suggest therefore to not
place the receiving antenna and/or transmitters near big metallic objects,
near the floor or on the ground.
Remote control learning
4.1 Learning of one transmitter
The 1st memorized button performs the STEP by STEP function (opening and
closing of the gate), the 2nd button performs the partial opening, the 3rd
button performs the OPEN function, 4th button performs the CLOSE function. The
control unit exits from the learning phase if no new button or transmitter
command is given in 10 seconds.
Make sure that the board is out of any menus, press the button UP[+] | On the
display will appear and the flashing light lights on
---|---
Press one button of the transmitter| On the display will appear don.
If the transmitter was already memorized will appear Fnd.
After 2 seconds the display will show the memory location of the memorized
transmitter, for example
If you want to memorize another button or a new transmitter repeat the
procedure
4.2 Learning with the hidden button of an already memorized transmitter
With the hidden button of a transmitter it is possible to enter the learning
phase in order to memorize new buttons or new transmitters.
With the automation still, with the aid of a clip press the hidden button of
an already memorized transmitter, the flashing light lights on, now it is
possible to memorize new buttons or transmitters.
4.3 Cancellation of one transmitter
Enter the learning phase with the UP[+] button or with the hidden button of
a memorized transmitter (see 4.1 or 4.2). Press in the same time the hidden
button and 1st button of the transmitter that you want to cancel. The flashing
light bilnks 4 times and on the display will appear
Setting stroke
5.1 Easy settings of the stroke (parameter
Be sure that the limit switches are connected and correctly adjusted
Unlock the gate and move it to the middle of the stroke| |
---|---|---
Press and keep pressed the buttons UP[+] e MENU
for at least 5 seconds.| The gate moves in opening.
If the gate moves in closing press the button DOWN to stop and reverse the
direction of movement and give a step by step command (SS) to resume the
procedure|
When the gate reaches the opening limit switch it
stops by itself| The gate moves in closing|
When the gate reaches the closing limit switch it stops by itself| The gate
moves in opening|
When the gate reaches the opening limit switch it
stops by itself| The gate closes with the settings of slowing down set in the
menu. When the gate is closed the learning phase is ended.|
Warning: in case of intervention of a safety device, the learning is stopped
and will appear on the display the written Press Step by Step button to start
again the learning from the 2nd point. 5.2 Advanced settings of the stroke
(parameter
Be sure that the limit switches are connected and correctly adjusted
In this procedure is necessary to provide the positions of beginning of
slowing down with a step by step command (SS).
Unlock the gate and move it to the middle of the stroke| 1|
---|---|---
Press and keep pressed the buttons UP[+] e MENU for at least 5 seconds.| The
gate moves in opening. If the gate moves in closing press the button DOWN to
stop and reverse the direction of movement and give a step by step command
(SS) to resume the procedure|
When the gate reaches the opening limit switch it stops by itself| The gate
moves in closing|
When the gate reaches the position of beginning of slowing down give a step by
step command (SS)| The gate begins the slowing down|
When the gate reaches the closing limit switch it stops by itself| The gate
moves in opening|
When the gate reaches the position of beginning of slowing down give a step by
step command (SS)| The gate begins the slowing down|
When the gate reaches the opening limit switch it stops by itself| The gate
closes with the settings of slowing down set in this learning. When the gate
is closed the learning phase is ended.|
Warning: in case of intervention of a safety device, the learning is stopped and will appear on the display the written Press Step by Step button to start again the learning from the 2 nd point.
Menu
Entering the menu:
To enter the base menu settings keep pressed the MENU button for at least one
second To enter the advanced menu settings keep pressed the MENU button for at
least five seconds
Navigation into the menu:
It is possible to move from an entry to another one using UP[+] e DOWN[-]
buttons,
To change a parameter keep pressed the MENU button for at least 1 second until
the parameter begins blinking, so release the button.
Use UP[+] and DOWN[-] buttons to change the parameter
At the end keep pressed MENU for al least 1 second until the parameter stops
blinking to save the change.
A quick pressure of the menu button is enough to leave a menu 6.1 Base
settings menu:
MENU| DESCRIPTION| SELECTABLE VALUES min- max|
**DEFAULT| ****UNITS**
---|---|---|---|---
| Auto reclosing time (0 = disabled)| 0-900| 0| s
| Auto reclosing time after transit(0 = disabled)| 0-30| 0| s
| Obstacle sensitivity (0 = disabled 100 = maximum sensitivity)| 0-100| 0| %
| Motor torque (running torque)| 10-100| 100| %
| Slowing down mode
0 = normal
1 = fast with more torque| **** 0-1| 0|
| Step by step configuration
0 = normal (OP-ST-CL-ST-OP-ST…)
1 = alternated STOP (OP-ST-CL-OP-ST-CL…)
2 = alternated (OP-CL-OP-CL…)
3 = condominium – timer
4 = condominium with immediate auto reclosing| 0-4| 0|
| After black-out
0 = no action
1 = closing| 0-1| 0|
| Soft start
0 = disabled
1 = enabled| ****
0-1
| ****
0
|
| Amplitude of slowing down
P = personalized during learning
0…100% = percentage of stroke| 0-100| 15| **** %
| Deceleration ramp amplitude 0 = disabled 1:9 = ramp duration| 0-9| 5|
*ATTENTION!
It is not advisable the disabling of the slowing downs and, if possible, use
the “soft start” function.
MENU| DESCRIPTION| SELECTABLE VALUES min- max|
**DEFAULT| ****UNITS**
---|---|---|---|---
| First coupling between Bluetooth device and control unit| | |
| Electrical brake activation time
0 = disabled
1 – 100= enabled| 0-100| 0| x0.01 s
| Functioning of PHOTO1 moving from closed
0 = Check PHOTO1
1 = The gate opens also with PHOTO1 busy| 0-1| 1|
| Functioning of PHOTO2
0 = Enabled in opening and closing OP/CL
1 = Enabled only in opening OP| 0-1| **** 0|
| Photocells test
0 = disabled
1 = enabled PHOTO1
2 = enabled PHOTO2
3 = enabled PHOTO1 and PHOTO2| 0-3| 0|
| Safety edge type
0 = contact (NC)
1 = resistive (8k2)| 0-1| 0|
| Operation mode of safety edge
0= working only in closing with inversion of movement
1 = stops the automation (both opening and closing) and free the obstacle
(short inversion)| 0-1| 0|
| Safety edge test
0 = disabled
1 = enabled| 0-1| 0|
| Partial opening| 0-100| 30| %
| Auto reclosing time from partial opening (0 = disabled)| 0-900| 20| s
| Blinker output mode
0 = Fix
1 = Blinking| 0-1| 1|
| Pre-flashing time (0 = disabled)| 0-10| 0| s
| Courtesy light settings
0 = At the end of movement for a TCY time
1 = On if the gate is not closed + TCY time
2 = On if courtesy light timer (TCY) not expired
3 = Open gate light on/off
4 = Open gate light with proportional flashing| 0-4| 0|
| Courtesy light time| 0-900| 0| s
| Dead-man
0 = disabled
1 = enabled| 0-1| 0|
| Setting threshold of cycles for assistance request. Once limit is reached
the next cycles will be done with fast blinking (only if FPr enabled) (0 =
disabled)| 0-100| 0| x1000
cicli
| Continuous blinking for assistance request (done only with closed gate).
0 = disabled
1 = enabled| ****
0-1
| ****
0
|
| Viewing of the memory location for a single transmitter| 0-999| |
| Cancellation of a single transmitter| 0-999| |
| Restore default settings, enter to modify the parameter and then keep
pressed the MENU button, a count down appears that ends with don on the
display| | |
| Cancelling all transmitters, enter to modify the parameter and then keep
pressed the MENU button, a count down appears that ends with don on the
display| | |
6.3 Menu description:
6.3.1 Base settings menu
Auto reclosing time
Active when the gate is in the completely open position, the gate
automatically closes after **seconds. In this phase the display shows with
the blinking dash, that during the last 10 seconds will be replaced by the
count down.
Auto reclosing time after transit
If in the opening phase or in the completely open position the beam of the
photocells is obscured and freed, the gate automatically closes after seconds
when the completely open position is reached, In this phase the display shows
with the blinking dash, that during the last 10 seconds will be replaced by
the count down.
SEI Obstacle sensitivity
Adjust the obstacle sensitivity to ensure a correct functioning of the
gate, it must stop if there is an obstacle but also it must ensure the
complete movement in the worst conditions (exp. winter, hardening of motors,
etc). After the adjustment of this parameter it is recommended to perform a
complete movimentation (opening and closing) before trying the obstacle
detection. The intervention of the obstacle sensitivity stops the gate and
makes a short inversion of the movement.
Obstacle sensitivity
Adjust the obstacle sensitivity to ensure a correct functioning of the
gate, it must stop if there is an obstacle but also it must ensure the
complete movement in the worst conditions (exp. winter, hardening of motors,
etc). After the adjustment of this parameter it is recommended to perform a
complete movimentation (opening and closing) before trying the obstacle
detection. The intervention of the obstacle sensitivity stops the gate and
makes a short inversion of the movement.
Motor torque
Adjust the motor torque to ensure a correct functioning of the gate, it is
possible to adjust the percentage of torque between 10% to 100%. After the
adjustment of this parameter it is recommended to perform a complete
movimentation (opening and closing) to ensure a correct functioning of the
gate.
Slowing down mode
The control unit has 2 different type of slowing downs : standard or with
higher torque and speed, for heavier gates.
Step by step configuration (SS)**
-
****= 0 Normal (OP-ST-CL-ST-OP-ST…)
Typical functioning of Step by Step. During the movement a SS command stops the gate. -
****= 1 Alternated STOP (OP-ST-CL-OP-ST-CL…)
Alternated functioning with STOP during the opening. During the opening phase a SS command stops the gate. -
****= 2 Alternated (OP-CL-OP-CL…)
The user cannot stop the gate during the movement with a SS command.
A SS command during the movement inverts the movement. -
****= 3 Condominium – timer
A SS command only opens the gate. When the gate is completely open, if the command persist the control unit will wait until the opening of the contact before beginning the countdown of the automatic reclosing (if enabled), on other SS command in this phase will restart the countdown of the automatic reclosing. -
****= 4 Condominium with immediate auto reclosing
Like condominium – timer (previous point) but during the countdown a SS command will close the gate.
After black-out
When the control unit turns on after a black-out,
- = 0 No action – when the control unit turns on the gate doesn’t move until the first command, the first movement is a slow opening.
- = 1 Closing– turning on the control unit it will perform a slow closing.
Soft start
The movement begins with reduced torque, used in light gates.
Amplitude of slowing down
With this parameter it is possible to adjust the amplitude of the slowing down
and eventually disable it (LSI=0). If you need more precise or different
slowing down between opening and closing it is possible to set the parameter
LSI on P (personalized) and perform an advanced learning of strokes (5.2)
providing also the beginning of slowing downs during the learning.
Deceleration ramp amplitude
With this parameter it is possible to define the amplitude of the
deceleration ramp and possibly its exclusion (SLr = 0).
It allows performing a deceleration from cruising speed to the retarding
speed, more or less evident depending on the installation requirements.
*ATTENTION!
It is not advisable the disabling of the slowing downs and, if possible,
use the “soft start” function.
6.3.2 Advanced menu
Bluetooth
Item of the menu needed to the first coupling between an Android device and
the control unit. Refer to the Help of the Android application for the
connection procedure.
Electrical brake
Short reverse movement with reduced torque to reduce the inertia of the gate.
The operation is performed at each stop of the movement except for fast
movement after the intervention of a safety devices.
Functioning of closing photocell PHOTO1 moving from closed position
The closing photocell has the following functioning
- Closing: immediate inversion of movement
- Opening from an intermediate position: no intervention
- Opening from closed position:
♦ . = 0 The gate doesn’t move if PHOTO1 beam is cut
♦ . = 1 The gate moves while PHOTO1 beam is cut
Functioning of opening photocell PHOTO2
The opening photocell has the following functioning
- Opening: stops the movement and waits until the beam is freed, then moves in opening.
- Closing:
♦ . = 0 Stops the movement and waits until the beam is freed, then moves in opening
♦ . = 1 No intervention
Photocells test
Enabling this function, before each movement starting from still gate, the
control unit performs a functional check of the photocells. The check will not
be performed in case of fast movement after the intervention of a safety
devices. Follow paragraph 3.6 for the connections of the photocells.
Safety edge type
The control unit can work with two different type of safety edge:
- = 0 Mechanical with normally closed contact
- = 1 Resistive 8k2
Operation mode of safety edge
To allow the installation of the safety edges in both the directions of
movements, it is possible to choose 2 different functioning:
- = 0 Only in closing with total inversion of movement
- = 1 Both directions of movements, stop and short inversion to free the obstacle
Safety edge test
Enabling this function the control unit performs a functional check of the
safety edge. This function is used if the edge connected to the control unit
has an electronic self test (exp. radio edge R.CO.O). Connect the test contact
of the edge to the power supply of the transmitter of the photocells
(paragraph 3.6) ad enable the self test with low voltage 0Vdc (for the
compatibility follow the instruction of the manual of the safety edge).
Partial opening
Partial opening can be performed only starting from closed. The parameter
sets the opening like a percentage of the total stroke of the first wing.
Auto reclosing time from partial opening
Active when the gate is in the partial opening, the gate automatically
closes after . seconds. In this phase the display shows with the blinking
dash, that during the last 10 seconds will be replaced by the count down.
Flashing light output mode
It is possible to choose 2 different functioning for the blinker output:
- = 0 Fixed blinker output. It will be necessary to connect a self flashing blinker (B.RO LIGHT 230 Vac)
- = 1 Flashing light blinker output. It will be necessary to connect a fix light blinker (B.RO LIGHT FIX 230 Vac)
Pre-flashing time
Pre-flashing before each movement in both directions, ** seconds of pre-
flashing
Courtesy light settings**
The control unit has 4 different functioning’s for courtesy light:
- . = 0 the light switches off at the end of a movement after seconds
- = 1 the light switches off only with closed gate after seconds
- = 2 lighted on for seconds from the beginning of a movement, independently of the condition of the gate (the light could switch off before the end of movement)
- = 3 open gate light – the light switches off immediately when the gate reaches the closed position
- = 4 open gate light with proportional blinking:
♦ opening – slow blinking
♦ closing – fast blinking
♦ opened – light on
♦ closed – light off
♦ stopped – 2flash + long wait + 2flash + long wait +…
Courtesy light timer
Courtesy light activation timer
Dead man
During dead man functioning mode the gate moves only with a permanent
command.
The enabled commands are OPEN and CLOSE. SS and PED are disabled. During dead
man functioning all the automatic movements are disabled, like short or total
inversions. All safety devices are disabled except for STOP.
Setting threshold of cycles for assistance request
It is possible to set a number of cycles before the request of assistance.
Once the limit is reached the next cycles will be done with fast blinking
(only if enabled)
Continuous flashing light for assistance request
Once limit is reached the flashing light will blink also with the gate
closed to show the request of assistance.
Viewing of the memory position for a single transmitter
With the item of the menu it is possible to view the memory location in which
a transmitter is memorized.
To perform the function, move to and then confirm by pressing the button MENU.
Keep pressed MENU button untill the display will show then release the button.
At this point press a button of the memorized transmitter (it does not active
any command). The display shows:
- the memory location for 2 seconds, if is memorized;
- the written for 2 seconds, if is not memorized.
After 2 seconds the display returns to the screenl and it will be possible to
perform this function with another transmitter.
To exit from the function, press MENU button. Otherwise after 15 seconds
without transmission, the control unit exits from the function and shows the
written
Cancellation of a single transmitter
With the item of the menu it is possible to delete a single transmitter
from the memory.
To perform the function, move to trace. and then confirm by pressing the
button MENU. Keep pressed MENU button until the display will show , then
release the button. Select the memory location of the transmitter. Press and
keep pressed MENU button until the display will show release the button.
To exit from the function, press MENU button. If the display shows the written
, there are problems with the memory (for example empty position or
disconnected memory).
Restore default settings
With this parameter it is possible to restore the default settings of the
control unit. The reset will restore all the parameters of the base and
advanced menu, but doesn’t modify the learnt strokes, the directions of motors
and the transmitters.
Move to then keep pressed MENU button until the display shows 0, release the
button. Press again and keep pressed MENU button, the display will show a
count down ,don’t release the button until the display show’s
Erasing of all transmitters
With this parameter it is possible to erase all the transmitters learnt.
Move to ****then keep pressed MENU button until the display shows 0, release
the button. Press again and keep pressed MENU button, the display will show a
count down ,don’t release the button until the display show’s
Display and control unit state
7.1 Input LED and safety devices
7.2 Normal functioning:
| Standby – Gate closed or after the switch on of the control unit
---|---
| Opening phase
| Closing phase
| Gate closed by user during opening
| Gate closed by user during closing
| Gate stopped by an external event (photocells, stop)
| Gate opened without automatic reclosing
| Gate opened in partial opening position without automatic reclosing
| Gate opened waiting for auto reclosing, last 10 seconds the dash will be
replaced by the countdown
| Gate opened in partial opening position waiting for auto reclosing, last 10
seconds the dash will be replaced by the countdown
| During the normal functioning and out from any menu, the pression of the
DOWN[-] button lets you see the number of cycles done, you will see units with
dots on the bottom of display and thousand without dot, another pression of
DOWN[-] or MENU button let you to leave the cycles visualization
| Visualized during the learning of transmitters
| Visualized when memorized a new transmitter or at the and of a reset
| Visualized when memorized a button of a transmitter already memorized
| Visualized when a transmitter is erased
| Visualized during the learning of strokes to indicate that the control unit
is opening the gate and waiting for the command of opening mechanical stop
| Visualized during the learning of strokes to indicate that the control unit
is closing the gate and waiting for the command of closing mechanical stop
| Visualized during the learning of strokes if there is an intervention of
safety devices
| Visualized when the control unit waits a transmitter signal, during the
function of viewing of the memory location.
| Visualized when the transmitter is not stored on the memory, during the
function of viewing of the memory location.
| Visualized when the control unit exits from the function of viewing of the
memory location for inactivity.
| Visualized during the first coupling with the Bluetooth device.
| Visualized when the control unit is connected to a Bluetooth device
| Visualized when Bluetooth device is disconnecting from the control unit.
7.3 Errors:
| Impact sensor intervention
---|---
| Safety edge intervention
| Limit switches error (both opening and closing electrical limit switches
busy in the same time)
| Malfunctioning of photocells
| Thermically intervention to preserve the control unit
| Memory error
| Full memory
| Memory error during functions viewing memory location or cancellation of a
single transmitter
The visualization of an error on the display persist until another command is given
Technical features
POWER SUPPLY AND CONSUMPTION
Power supply voltage | 230 Vac – 50/60 Hz |
---|
Absorption from line (Standby) Standard configuration (2 couple of photocells,
RX radio safety edge)| 45 mA @ 230 Vac
Line fuse| F6.3A
MOTOR POWER SUPPLY
Number of motors | 1 |
---|---|
Motor power supply voltage | 230 Vac – 50/60 Hz |
Maximum power absorbed from motors | 700W |
ACCESSORIES POWER SUPPLY
Accessories power supply voltage | 24 Vdc |
---|---|
Maximum current absorbed from accessories | 170 mA |
Maximum power absorbed from accessories | 4 W |
Accessories fuse | F 0.5 A |
Blinker output | 230 Vac 60W max |
Courtesy light output / open gate light | 230 Vac 100W max |
FUNCTIONALITY
433 MHz radio receiver | Rolling code |
---|---|
Maximum transmitters | 1000 (up to 8000) |
Safety edge input | NC / 8k2 |
DISPOSAL OF THE PRODUCT
This product is an integral part of the automation, and therefore, they must
be disposed of together. As for the installation operations, at the end of the
life of this product, the dismantling operations must be performed by
qualified personnel. This product is made from different types of materials:
some can be recycled, others must be disposed of. Please inform yourselves on
the recycling or disposal systems provided for by the laws in force in your
area, for this category of product.
CAUTION! – some parts of the product can contain polluting or dangerous
substances which, if dispersed in the environment, may cause serious harm to
the environment and human health.
As indicated by the symbol at the side, it is forbidden to throw this product
into domestic refuse. Therefore, follow the “separated collection”
instructions for disposal, according to the methods provided for by local
regulations in force, or redeliver the product to the retailer at the moment
of purchase of a new, equivalent product.
CAUTION! – the regulations in force at local level may envisage heavy
sanctions in case of abusive disposal of this product.
GUARANTEE – In compliance with legislation, the manufacturer’s guarantee
is valid from the date stamped on the product and is restricted to the repair
or free replacement of the parts accepted by the manufacturer as being
defective due to poor quality materials or manufacturing defects. The
guarantee does not cover damage or defects caused by external agents, faulty
maintenance, overloading, natural wear and tear, choice of incorrect product,
assembly errors, or any other cause not imputable to the manufacturer.
Products that have been misused will not be guaranteed or repaired. Printed
specifications are only indicative. The manufacturer does not accept any
responsibility for range reductions or malfunctions caused by environmental
interference. The manufacturer’s responsibility for damage caused to persons
resulting from accidents of any nature caused by our defective products, are
only those responsibilities that come under Italian law.
ALLMATIC S.r.l
32026 Borgo Valtellina – Bellion – Italy
Via dell’Artigiano, n°1 – Z.A.
Tel. 0437 751175 – 751163 ran
http://www.allmatic.com
E-mail: info@allmatic.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>