tekmar 681 BACnet Snow/Ice Sensor Interface User Manual

June 6, 2024
tekmar

BAS Integration Manual
BACnet Snow/Ice
Sensor Interface 681
IS-T-681-BAS Integration

Introduction

The BACnet Snow/Ice Sensor Interface 681 communicates with a Building Automation System (BAS) using BACnet® MSTP.
This manual provides information about control parameters that can be accessed by building automation or management systems that use BACnet.

BACnet Protocol Implementation Conformance Statement (PICS)

Vendor Name: tekmar Control Systems Ltd.
Vendor ID: 585
Product Name: BACnet Snow/Ice Sensor Interface 681
Product Model Number: 681
Application Software Version: J1297 Firmware Revision: 0.0.2 BACnet Protocol Revision: 14
Product Description:
The 681 is an interface that automatically measures the presence of snow or ice and interfaces with a
Building Automation System through BACnet to operate an automatic snow melting system.

BACNET STANDARDIZED DEVICE PROFILE

BACnet Application Specific Controller (B-ASC)

SUPPORTED BIBBS (ANNEX K) NAME
DS-RP-B Data Sharing-ReadProperty-B
DS-RPM-B Data Sharing-ReadPropertyMultiple-B
DS-WP-B Data Sharing-WriteProperty-B
DM-DDB-B Device Management-Dynamic Device Binding-B
DM-DOB-B Device Management-Dynamic Object Binding-B
DM-DCC-B Device Management-Device Communication Control-B
SEGMENTATION CAPABILITY SUPPORTED WINDOW SIZE
Able to transmit segmented messages No
Able to receive segmented messages No
STANDARD OBJECT TYPES SUPPORTED CREATABLE DELETABLE
Analog Input No No
Analog Value No No
Binary Input No No
Binary Value No No
Device No No
DATALINK LAYER SUPPORTED
BACnet MSTP Yes

NETWORK SECURITY OPTIONS

Non-secure Device| –

DATALINK LAYER OPTION SUPPORTED
BACnet MSTP Yes
DEVICE ADDRESS BINDING OPTION SUPPORTED
Device Address Binding NO

BACnet MSTP Connection

SERVICE NAME INITIATE EXECUTE
real property Yes
ReadPropertyMultiple Yes
DeviceCommunicationControl Yes
Who-Is Yes
I-Am Yes
Who-Has Yes
I-Have Yes

Use the 681 terminal block to connect a shielded twisted pair wire from the BACnet RS485 connection point. Wire the A, B & G conductors from the BACnet point to the 681 A, B & Ref terminals.

  • And should not be connected to the ground screws in the 681.

STATUS FLAG

In Alarm Flag| F
Fault Flag| F
Overridden Flag| F
Out of Service Flag| F/T

RELIABILITY

No-Fault| 0
No Sensor| 1
Open Loop| 4
Shorted Loop| 5

BACnet Analog Parameters

Analog Input Object = AI
Analog Value Object = AV
Read = R
Read/Write = R/W

OBJECT ID| NAME| DATA
TYPE| READ/
WRITE| STATUS
FLAG| EVENT
STATE| RELIABILITY| OUT OF
SERVICE| UNITS| RANGE/
VALUE
---|---|---|---|---|---|---|---|---|---
Analog Input Objects
1| Outdoor Air
Temperature| AI| R| FFF(F/T)| Normal| 0, 1, 4, 5| False or True| °F (64)| -76 to 266°F
2| Slab

Temperature

| AI| R| FFF(F/T)| Normal| 0, 1| False or True| °F (64)| –
3| Slab Target

Temperature

| AI| R| FFF(F/T)| Normal| 0| False or True| °F (64)| –
4| Error Code| AI| R| FFF(F/T)| Normal| 0| False or True| No Units(95)| See Error Codes list
Analog Value Objects
1| BAS
Outdoor air temperature| AV| R/W| FFF(F/T)| Normal| –| False or True| °F (64)| -76 to 266°F
2| Melt Setpoint| AV| R/W| FFF(F/T)| Normal| –| False or true| °F (64)| 32 to 95°F
3| Snow/Ice
Sensitivity| AV| R/W| FFF(F/T)| Normal| –| –| No Units

(95)

| 0 = Auto, 1 = Min,
2 = -2, 3 = -1, 4 = Mid, 5 = +1, 6 = +2, 7 = Max
4| Warm WeatherShut Down| AV| R/W| FFF(F/T)| Normal| –| False or True| °F (64)| 32 to 95°F
5| Cold WeatherCut Off| AV| R/W| FFF(F/T)| Normal| –| False or True| °F (64)| -30 to 50°F

BACnet Binary Parameters
Binary Input Object = BI
Binary Value Object = BV
Read = R
Write = W

6| NAME| DATATYPE| READ /

WRITE

| STATUS

FLAG

| EVENT

STATE

| OUT OF

SERVICE

| PRESENT VALUE
---|---|---|---|---|---|---|---
Binary Value Objects
1| Snow Detected| BI| R/W| FFF/(F/T)| Normal| False or True| 0 = False
1 = True
2| Cold Weather Cut Off| BI| R/W| FFF(F/T)| Normal| False or True| 0 = False
1 = True
3| Melt Pending Detected| BI| R/W| FFF(F/T)| Normal| False or True| 0 = False
1 = True
4| Wet Detected| BI| R/W| FFF(F/T)| Normal| False or True| 0 = False
1 = True
5| Sensor Mode| BI| R/W| FFF(F/T)| Normal| False or True| 0 = False
1 = True
6| Melt Pending Detected| BI| R/W| FFF(F/T)| Normal| False or True| 0 = 090 Sensor Configured
1 = 095 Sensor Configured

OBJECT ID| NAME| DATATYPE| READ /
WRITE| STATUS
FLAG| EVENT
STATE| OUT OF
SERVICE| PRESENT VALUE
---|---|---|---|---|---|---|---
Binary Value Objects
1| Outdoor Sensor Enable| BV| R/W| FFF(F/T)| Normal| False or True| 0 = Interface measures outdoor
1 = BAS sends outdoor temperature
2| Warm Weather Shutdown Type| BV| R/W| FFF(F/T)| Normal| False or True| 0 = Auto, 1 = Setting
3| Cold Weather Cut
Off Type| BV| R/W| FFF(F/T)| Normal| False or True| 0 = Auto, 1 = Setting
4| Reset Snow Detection Request| BV| R/W| FFF(F/T)| Normal| False or True| 0 = Do nothing,
1 = Reset Snow
Detection

Refer to the Installation & Operation Manual 681_D for additional information.

BACnet MSTP Troubleshooting

If there is no communication, check the following:

  • Check that the polarity on the BACnet MSTP A & B terminals is correct.
  • Check that the BACnet MSTP Ref terminal is securely connected.
  • Check that the baud rate is the same on both devices.

BACnet MSTP Specification

Communication Protocol MSTP over RS-485
Physical Layer TIA-485 two-wire plus signal ground
Baud Rate 9600, 19200, 38400, 57600, 76800, 115200 (default: 76800 bps)
Recommended Cable 18 AWG Shielded Twisted pair (STP)
Maximum Cable Length 9600 bps: 1200 meters (4000 feet) 19200 bps: 1200 meters

(4000 feet) 38400 bps: 1200 meters (4000 feet) 57600 bps: 1200 meters (4000 feet) 76800 bps: 1200 meters (4000 feet) 115200 bps: 1000 meters (3280 feet)
Parity| Even (1 stop bit)
Addressing| 0 to 127 (default: 60)

Error Codes

CODE DESCRIPTION
1 Setpoint Menu Save Error
2 Sensors Menu Save Error
3 BAS Menu Save Error
4 Outdoor Sensor Error
5 Slab Sensor Error
6 Snow Sensor Yellow Wire Error
7 Snow Sensor Blue Wire Error
8 Snow Sensor Brown Wire Error
9 Snow Sensor Error
10 Snow/Ice Sensor

Detailed information on how to correct the error is included in the Installation & Operation Manual 681_D available at watts.com/tekmar

S-T-681-BAS Integration 2139
Tel: 1-800-438-3903
Fax: 250-984-0815
tekmarControls.com
© 2021 tekmar

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals