BAS Integration Manual
BACnet Snow/Ice
Sensor Interface 681
IS-T-681-BAS Integration
Introduction
The BACnet Snow/Ice Sensor Interface 681 communicates with a Building
Automation System (BAS) using BACnet® MSTP.
This manual provides information about control parameters that can be accessed
by building automation or management systems that use BACnet.
BACnet Protocol Implementation Conformance Statement (PICS)
Vendor Name: tekmar Control Systems Ltd.
Vendor ID: 585
Product Name: BACnet Snow/Ice Sensor Interface 681
Product Model Number: 681
Application Software Version: J1297 Firmware Revision: 0.0.2 BACnet
Protocol Revision: 14
Product Description:
The 681 is an interface that automatically measures the presence of snow or
ice and interfaces with a
Building Automation System through BACnet to operate an automatic snow melting
system.
BACNET STANDARDIZED DEVICE PROFILE
BACnet Application Specific Controller (B-ASC)
SUPPORTED BIBBS (ANNEX K) | NAME |
---|---|
DS-RP-B | Data Sharing-ReadProperty-B |
DS-RPM-B | Data Sharing-ReadPropertyMultiple-B |
DS-WP-B | Data Sharing-WriteProperty-B |
DM-DDB-B | Device Management-Dynamic Device Binding-B |
DM-DOB-B | Device Management-Dynamic Object Binding-B |
DM-DCC-B | Device Management-Device Communication Control-B |
SEGMENTATION CAPABILITY | SUPPORTED | WINDOW SIZE |
---|---|---|
Able to transmit segmented messages | No | |
Able to receive segmented messages | No |
STANDARD OBJECT TYPES SUPPORTED | CREATABLE | DELETABLE |
---|---|---|
Analog Input | No | No |
Analog Value | No | No |
Binary Input | No | No |
Binary Value | No | No |
Device | No | No |
DATALINK LAYER | SUPPORTED |
---|---|
BACnet MSTP | Yes |
NETWORK SECURITY OPTIONS
Non-secure Device| –
DATALINK LAYER OPTION | SUPPORTED |
---|---|
BACnet MSTP | Yes |
DEVICE ADDRESS BINDING OPTION | SUPPORTED |
---|---|
Device Address Binding | NO |
BACnet MSTP Connection
SERVICE NAME | INITIATE | EXECUTE |
---|---|---|
real property | – | Yes |
ReadPropertyMultiple | – | Yes |
DeviceCommunicationControl | – | Yes |
Who-Is | – | Yes |
I-Am | Yes | – |
Who-Has | – | Yes |
I-Have | Yes | – |
Use the 681 terminal block to connect a shielded twisted pair wire from the BACnet RS485 connection point. Wire the A, B & G conductors from the BACnet point to the 681 A, B & Ref terminals.
- And should not be connected to the ground screws in the 681.
STATUS FLAG
In Alarm Flag| F
Fault Flag| F
Overridden Flag| F
Out of Service Flag| F/T
RELIABILITY
No-Fault| 0
No Sensor| 1
Open Loop| 4
Shorted Loop| 5
BACnet Analog Parameters
Analog Input Object = AI
Analog Value Object = AV
Read = R
Read/Write = R/W
OBJECT ID| NAME| DATA
TYPE| READ/
WRITE| STATUS
FLAG| EVENT
STATE| RELIABILITY| OUT OF
SERVICE| UNITS| RANGE/
VALUE
---|---|---|---|---|---|---|---|---|---
Analog Input Objects
1| Outdoor Air
Temperature| AI| R| FFF(F/T)| Normal| 0, 1, 4, 5| False or True| °F (64)| -76
to 266°F
2| Slab
Temperature
| AI| R| FFF(F/T)| Normal| 0, 1| False or True| °F (64)| –
3| Slab Target
Temperature
| AI| R| FFF(F/T)| Normal| 0| False or True| °F (64)| –
4| Error Code| AI| R| FFF(F/T)| Normal| 0| False or True| No Units(95)| See
Error Codes list
Analog Value Objects
1| BAS
Outdoor air temperature| AV| R/W| FFF(F/T)| Normal| –| False or True| °F (64)|
-76 to 266°F
2| Melt Setpoint| AV| R/W| FFF(F/T)| Normal| –| False or true| °F (64)| 32 to
95°F
3| Snow/Ice
Sensitivity| AV| R/W| FFF(F/T)| Normal| –| –| No Units
(95)
| 0 = Auto, 1 = Min,
2 = -2, 3 = -1, 4 = Mid, 5 = +1, 6 = +2, 7 = Max
4| Warm WeatherShut Down| AV| R/W| FFF(F/T)| Normal| –| False or True| °F
(64)| 32 to 95°F
5| Cold WeatherCut Off| AV| R/W| FFF(F/T)| Normal| –| False or True| °F (64)|
-30 to 50°F
BACnet Binary Parameters
Binary Input Object = BI
Binary Value Object = BV
Read = R
Write = W
6| NAME| DATATYPE| READ /
WRITE
| STATUS
FLAG
| EVENT
STATE
| OUT OF
SERVICE
| PRESENT VALUE
---|---|---|---|---|---|---|---
Binary Value Objects
1| Snow Detected| BI| R/W| FFF/(F/T)| Normal| False or True| 0 = False
1 = True
2| Cold Weather Cut Off| BI| R/W| FFF(F/T)| Normal| False or True| 0 = False
1 = True
3| Melt Pending Detected| BI| R/W| FFF(F/T)| Normal| False or True| 0 = False
1 = True
4| Wet Detected| BI| R/W| FFF(F/T)| Normal| False or True| 0 = False
1 = True
5| Sensor Mode| BI| R/W| FFF(F/T)| Normal| False or True| 0 = False
1 = True
6| Melt Pending Detected| BI| R/W| FFF(F/T)| Normal| False or True| 0 = 090
Sensor Configured
1 = 095 Sensor Configured
OBJECT ID| NAME| DATATYPE| READ /
WRITE| STATUS
FLAG| EVENT
STATE| OUT OF
SERVICE| PRESENT VALUE
---|---|---|---|---|---|---|---
Binary Value Objects
1| Outdoor Sensor Enable| BV| R/W| FFF(F/T)| Normal| False or True| 0 =
Interface measures outdoor
1 = BAS sends outdoor temperature
2| Warm Weather Shutdown Type| BV| R/W| FFF(F/T)| Normal| False or True| 0 =
Auto, 1 = Setting
3| Cold Weather Cut
Off Type| BV| R/W| FFF(F/T)| Normal| False or True| 0 = Auto, 1 = Setting
4| Reset Snow Detection Request| BV| R/W| FFF(F/T)| Normal| False or True| 0 =
Do nothing,
1 = Reset Snow
Detection
Refer to the Installation & Operation Manual 681_D for additional information.
BACnet MSTP Troubleshooting
If there is no communication, check the following:
- Check that the polarity on the BACnet MSTP A & B terminals is correct.
- Check that the BACnet MSTP Ref terminal is securely connected.
- Check that the baud rate is the same on both devices.
BACnet MSTP Specification
Communication Protocol | MSTP over RS-485 |
---|---|
Physical Layer | TIA-485 two-wire plus signal ground |
Baud Rate | 9600, 19200, 38400, 57600, 76800, 115200 (default: 76800 bps) |
Recommended Cable | 18 AWG Shielded Twisted pair (STP) |
Maximum Cable Length | 9600 bps: 1200 meters (4000 feet) 19200 bps: 1200 meters |
(4000 feet) 38400 bps: 1200 meters (4000 feet) 57600 bps: 1200 meters (4000
feet) 76800 bps: 1200 meters (4000 feet) 115200 bps: 1000 meters (3280 feet)
Parity| Even (1 stop bit)
Addressing| 0 to 127 (default: 60)
Error Codes
CODE | DESCRIPTION |
---|---|
1 | Setpoint Menu Save Error |
2 | Sensors Menu Save Error |
3 | BAS Menu Save Error |
4 | Outdoor Sensor Error |
5 | Slab Sensor Error |
6 | Snow Sensor Yellow Wire Error |
7 | Snow Sensor Blue Wire Error |
8 | Snow Sensor Brown Wire Error |
9 | Snow Sensor Error |
10 | Snow/Ice Sensor |
Detailed information on how to correct the error is included in the Installation & Operation Manual 681_D available at watts.com/tekmar