POWER-LITE LPE-EP LED Panel Back Up Kit Emergency Installation Guide
- June 15, 2024
- POWER-LITE
Table of Contents
POWER-LITE LPE-EP LED Panel Back Up Kit Emergency Installation Guide
Technical Information
Dimensions | 23510451 mm |
---|---|
Total Weight | 0.72kg |
Supply Voltage | 100-240VAC 50/60Hz |
Power Rating | 10W |
Duration | 3h |
Ambient Temp. | 0° C to +55°C |
Max Case Temp. | 70° C |
Max Battery Temp. | 55° C |
Battery Fuse | Internal |
Battery Pack | 12.6V/4Ah Li-ion |
Charge Current | 400mA |
Recharge Period | 24Hours |
- Following a full discharge, 24 hours should be allowed for the batteries to re-charge.
- The green LED charge indicator signifies that the batteries are charging and willremain illuminated when the luminaire is switched off.
- The batteries have a rated service life of 4 years and should be checked and considered for replacement at that point.
Specifications
- Suitable for use with Mains voltage of 100-240VAC 50/60Hz
- This product mustbe disconnected before insulation resistance testing of the lighting circuit
- Check for electrical cables and pipes before installation
- A record of routine testing should be kept to ensure emergency luminaires are maintained and operated correctly.
- The battery has a 4 year service life provided it is operated and maintained by regular testing, as detailed in this document. Failure to maintain or change the battery may result in reduced duration in emergency mode.
NOTE :
To comply with regulations, Installation must be carried out by suitably
qualified competent person and IN accordance with the current IEE Wiring
Regulations (BS7671) and Building Regulations.
The Emergency pack requires 2 Live feeds, 1 to charge the battery pack and 1 for switching of the product.
Instructions
TurnOFF power supply, ensure all required equipment and tools are present. The
Emergency Pack is supplied pre-wired for easy connection to luminaires and
drivers.
Connecting the Driver (1 &2)
The emergency pack is supplied pre-wired for connection to the LED driver
supplied with the luminaire. Use the UN cable from the emergency pack (1)
as the inputfortheLED driver, and connect the pre-wired connector from output
of the driver to input for emergency pack (2). Remove Safety covers before
installation.
Luminaire Input (3)
Connect the lead from emergency pack to the connector on luminaire.
Indicator LED (4)
Drill a 18mm hole close to the installation location of the luminaire. Feed
the indicator cable through the cut-out, inertinite the housing then push both
into the ceiling until secure.
ENSURE ELECTRICAL SUPPLY AND BATTERY CONNECTION IS DISCONNECTED/ISOLATED BEFORE COMMENCING INSTALLATION OR ANY MAINTENANCE WORK. HIGH VOLTAGE COULD BE PRESENT AT THE OUTPUT CONNECTION IF THE BATTERY IS NOT DISCONNECTED.
WARNING – AVOID RUNNING THE LED MAINS DRIVER AND EMERGENCY PACK WITHOUT THE LOAD CONNECTED. FAILURE TO DO SO MAY RESULT IN DAMAGE TO THE LED EMERGENCY PACK
Battery (5)
Push the battery connector together, ensuring correct polarity. do not force
plug.
NOTE –
the lumin are may illuminate due to any stored battery charge.
Mains Input (6)
The emergency pack requires a permanent, switched live and neutral. Earth is
not required as the.
1800 909 306
nedlandsgroup.com.au
sales@nedlandsgroup.com.au
Documents / Resources
|
POWER-LITE LPE-EP LED Panel Back Up Kit
Emergency
[pdf] Installation Guide
LPE-EP, LPE-EP LED Panel Back Up Kit Emergency, LED Panel Back Up Kit
Emergency, Panel Back Up Kit Emergency, Back Up Kit Emergency, Up Kit
Emergency, Kit Emergency, Emergency
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>