SURE SA18AZ Vantix Line iM Air Conditioners User Manual

June 13, 2024
SURE

SURE SA18AZ Vantix Line iM Air Conditioners

SURE-SA18AZ-Vantix-Line-iM-Air-Conditioners-fig- \(2\)

Product Information

The Air Conditioners SA18AZ is part of the VantixTM Line iM Air Conditioners. It is a high-efficiency air conditioner with a SEER2 rating of 18. The SA18AZ model is available in four different capacities: 24,000 BTU/HR (2.0 ton), 36,000 BTU/HR (3.0 ton), 48,000 BTU/HR (4.0 ton), and 60,000 BTU/HR (5.0 ton). It uses R-410A refrigerant and operates on a voltage of 208-230/60.

Features and Benefits

  • High efficiency with a SEER2 rating of 18
  • Inverter technology for variable speed operation (V Type)
  • Communicating controls for enhanced performance (C Type)
  • Scroll compressor for reliable and quiet operation
  • Available in multiple capacities to suit different cooling needs

Model Number Identification

The model number SA18AZ contains the following information:

  • S – Sure Comfort
  • A – Air Conditioners
  • 18 – SEER2 rating (18)
  • A – All
  • Z – R-410A refrigerant
  • 24 – Capacity in BTU/HR (24,000)
  • A – 1st Design
  • J – Single-phase, 208-230/60 voltage

Product Usage Instructions

Before using the Air Conditioners SA18AZ, please ensure that you have the necessary clearances for installation:

  • Allow overhang clearance of 60 inches (1524 mm) minimum
  • Allow 6 inches (152 mm) minimum clearance on all sides of the air inlet grille
  • Recommended clearance of 12 inches (305 mm) for all sides of the unit
  • Service panels, inlet connections, and high & low voltage access require a minimum clearance of 24 inches (610 mm)

To operate the Air Conditioners SA18AZ:

  1. Make sure the unit is properly installed and connected to the power supply.
  2. Set the desired temperature on the thermostat or control panel.
  3. The air conditioner will start cooling and maintain the set temperature.
  4. Adjust the fan speed or mode settings as desired for optimal comfort.
  5. Regularly clean or replace the air filters to maintain efficient operation.
  6. If you encounter any issues or need assistance, refer to the user manual or contact customer support.

SA18AZ

  • EcoNet® Enabled
  • Cooling Efficiencies up to: 20.0 SEER2/13 EER2
  • Nominal Sizes: 2 to 5 Tons [7.0 to 17.6 kW]
  • Cooling Capacities: 22.8 to 54 kBTU [6.7 to 15.83 kW]

Proper sizing and installation of equipment is critical to achieve optimal performance. Split system air conditioners and heat pumps must be matched with appropriate coil components to meet Energy Star. Ask your Contractor for details or visit www.energystar.gov.
The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks by Rheem® is under license. Other trademarks and trade names are those of their respective owners.

Features and Benefits

  • EcoNet® Enabled: Automatic system configuration and optimization
  • Diagnostics & Bluetooth Connectivity: With the Sure Comfort Contractor & EcoNet® Apps, built-in technology makes advanced set-up, monitoring, troubleshooting, and repairing the product easier than ever before
  • Brushless DC Condenser Motors (BLDC): Enhances reliability and allows for easier serviceability
  • Swept Wing Fan Technology: Features quieter operation and improved unit acoustics
  • Expanded Valve Space: 3 in. – 4 in. – 5 in. service valve space—provides a minimum working area of 27-square inches for easier access
  • Triple Service Access: 15 in. wide, industry leading corner service access, two fastener, removeable corner and individual louver panels – makes repairs easier and faster

Air Conditioners

SURE-SA18AZ-Vantix-Line-iM-Air-Conditioners-fig-
\(3\)

AVAILABLE MODELS DESCRIPTION
SA18AZ24AJVCA Vantix™ Line 2 ton EcoNet® Enabled Inverter Driven Variable

Speed iM Air Conditioner – 208/230/1/60
SA18AZ36AJVCA| Vantix™ Line 3 ton EcoNet® Enabled Inverter Driven Variable Speed iM Air Conditioner – 208/230/1/60
SA18AZ48AJVCA| Vantix™ Line 4 ton EcoNet® Enabled Inverter Driven Variable Speed iM Air Conditioner – 208/230/1/60
SA18AZ60AJVCA| Vantix™ Line 5 ton EcoNet® Enabled Inverter Driven Variable Speed iM Air Conditioner – 208/230/1/60

STANDARD EQUIPMENT

R-410A Refrigerant

EcoNet® Enabled
Variable Speed Compressor
Compressor Sound Blanket
Variable speed outdoor fan motor
Swept wing fan blade
Field Installed Filter Drier
Front Seating Service Valves
Internal Pressure Relief Valve
Internal Thermal Overload
Low Ambient capability
3-4-5 Expanded Valve Space
Composite Basepan
1″ Screw Control Box Access
15″ Access to Internal Components
Quick release louver panel design
No fasteners to remove along bottom
Optimized Venturi Airflow
Single row condenser coil 1
Powder coated paint
Rust resistant screws
QR code
External gauge ports
Service trays

5 Ton model includes 2 row condenser coil

General Data

GENERAL DATA

MODEL NO.| SA18AZ24AJVCA| SA18AZ36AJVCA| SA18AZ48AJVCA| SA18AZ60AJVCA
Nominal Tonnage| 2.0| 3.0| 4.0| 5.0
Valve Connections|
Liquid Line O.D. – in.| 3/8| 3/8| 3/8| 3/8
Suction Line O.D. – in.| 3/4| 3/4| 7/8| 7/8
Refrigerant (R410A) furnished oz.¹| 210| 212| 222| 252
Compressor Type| Scroll
Outdoor Coil|
Net face area – Outer Coil| 22.2| 22.3| 32.5| 32.5
Net face area – Inner Coil| —| —| —| 32.5
Tube diameter – in.| 0.375| 0.375| 0.375| 0.375
Number of rows| 1| 1| 1| 2
Fins per inch| 20| 20| 22| 20
Outdoor Fan|
Diameter – in.| 24| 24| 26| 26
Number of blades| 3| 3| 3| 3
Motor hp| 1/5| 1/3| 1/2| 1/2
CFM| 3330| 4315| 6240| 6175
RPM| 772| 825| 935| 900
watts| 83| 114| 278| 278
Shipping weight – lbs.| 226| 244| 263| 316
Operating weight – lbs.| 214| 236| 255| 307
Electrical Data
Line Voltage Data (Volts-Phase-Hz)| 208/230-1-60| 208/230-1-60| 208/230-1-60| 208/230-1-60
Maximum overcurrent protection (amps)²| 35| 45| 70| 80
Minimum circuit ampacity³| 21| 29| 46| 48
Compressor|
Rated load amps| 15| 20.1| 32| 34.1
Locked rotor amps| 35| 35| 50| 50

  • Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instructions for information about set length and additional refrigerant charge required.
  • HACR type circuit breaker of fuse.
  • Refer to National Electrical Code manual to determine wire, fuse and disconnect size requirements

Accessories

MODEL NO.| SA18AZ24AJVCA| SA18AZ36AJVCA| SA18AZ48AJVCA| SA18AZ60AJVCA
---|---|---|---|---
EcoNet® Smart Thermostat| CETST800SYS| CETST800SYS| CETST800SYS| CETST800SYS
Compressor Sound Cover| STD| STD| STD| STD
Supply / Return Sensor| RXHT-A02| RXHT-A02| RXHT-A02| RXHT-A02

Weighted Sound Power Level


MODEL

| SOUND POWER LEVEL [DB(A)] LOW SPEED/ HIGH SPEED| FULL OCTAVE LINEAR SOUND POWER LEVEL DB – CENTER FREQUENCY – HZ| SOUND POWER LEVEL [DB(A)] WITH SOUND BLANKET
---|---|---|---
125| 250| 500| 1000| 2000| 4000| 8000
SA18AZ24AJVCA| 58.9| 29| 36.5| 42| 45.7| 42.3| 43.2| 33| ****



Sound Blankets – Standard

68| 47.1| 47.7| 58.8| 57.1| 55.0| 52.7| 45.6
SA18AZ36AJVCA| 57| 29.2| 36.7| 44.9| 45.4| 42.2| 39.4| 32.2
72| 42.9| 52.8| 62.7| 63.6| 58.7| 54.1| 52.4
SA18AZ48AJVCA| 54| 30.6| 39| 42.2| 42.5| 36.5| 35.2| 35
72| 48.2| 55.3| 64.6| 61.7| 56.2| 51.7| 46.2
SA18AZ60AJVCA| 70| 46.6| 50.5| 62.7| 52.9| 49.4| 46| 41.4
76| 50.7| 62.7| 67.7| 65.4| 64.2| 59.2| 54.9

NOTE : Tested in accordance with AHRI Standard 270-08 (not listed in AHRI)

Unit Dimensions

SURE-SA18AZ-Vantix-Line-iM-Air-Conditioners-fig-
\(4\)


MODEL NO.

| OPERATING| SHIPPING
---|---|---
H (Height)| L (Length)| W (Width)| H (Height)| L (Length)| W (Width)
INCHES| mm| INCHES| mm| INCHES| mm| INCHES| mm| INCHES| mm| INCHES| mm
SA18AZ24AJVCA| 39| 990| 33.75| 857| 33.75| 857| 41.56| 1055| 37.64| 956| 37.56| 954
SA18AZ36AJVCA| 39| 990| 33.75| 857| 33.75| 857| 41.56| 1055| 37.64| 956| 37.56| 954
SA18AZ48AJVCA| 51| 1295| 35.75| 908| 35.75| 908| 53.56| 1360| 39.37| 999| 39.64| 1006
SA18AZ60AJVCA| 51| 1295| 35.75| 908| 35.75| 908| 53.56| 1360| 39.37| 999| 39.64| 1006

Designates Metric Conversions

CLEARANCES

SURE-SA18AZ-Vantix-Line-iM-Air-Conditioners-fig-
\(5\)

NOTE : NUMBERS IN () = mm
IMPORTANT: When installing multiple units in an alcove, roof well or partially enclosed area, ensure there is adequate ventillation to prevent re- circulation of discharge air.

Control Wiring

SURE-SA18AZ-Vantix-Line-iM-Air-Conditioners-fig-
\(6\)

Application Guidelines

  1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01 in. wc.
  2. Minimum outdoor operation air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C).
  3. Maximum outdoor operating air temperature is 125°F (51.7°C).
  4. For reliable operation, unit should be level in all horizontal planes.
  5. Use only copper wire for electric connections at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
  6. Do not apply capillary tube indoor coils to these units.
  7. Factory-supplied filter drier must be installed

Refrigerant Line Size Information

18 SEER2 VARIABLE SPEED AIR CONDITIONERS


UNIT SIZE

| ****

ALLOWABLE LIQUID LINE SIZE

| ****

ALLOWABLE VAPOR LINE SIZE

| OUTDOOR UNIT ABOVE OR BELOW INDOOR UNIT EQUIVALENT LENGTH (FEET)
< 25| 26-50| 51-75| 76-100| 101-125| 126-150
MAXIMUM VERTICAL SEPARATION/CAPACITY MULTIPLIER



2 Ton* SEE NOTE 3

| 1/4″| 5/8″| 25/1.00| 50/0.99| 32/0.98| 40/0.97| NR| NR
5/16″| 5/8″| 25/1.00| 50/0.99| 50/0.98| 50/0.97| 50/0.96| 50/0.95
3/8″| 5/8″| 25/1.00| 50/0.99| 50/0.98| 50/0.97| 50/0.96| 50/0.95
1/4″| 3/4″| 25/1.00| 50/1.00| 32/0.99| 40/0.99| NR| NR
5/16″| 3/4″
| 25/1.00| 50/1.00| 50/0.99| 50/0.99| 50/0.99| 50/0.98
3/8″| 3/4″**| 25/1.00| 50/1.00| 50/0.99| 50/0.99| 50/0.99| 50/0.98



3 Ton

| 5/16″| 5/8″| 25/0.99| 50/0.97| 50/0.95| 50/0.93| 37/0.91| NR
3/8″| 5/8″| 25/0.99| 50/0.97| 50/0.95| 50/0.93| 50/0.91| NR
5/16″| 3/4″| 25/1.00| 50/0.99| 50/0.99| 50/0.98| 37/0.97| 22/0.96
3/8″| 3/4″| 25/1.00| 50/0.99| 50/0.99| 50/0.98| 50/0.97| 50/0.96
1/2″| 3/4″| 25/1.00| 50/0.99| 50/0.99| 50/0.98| 50/0.97| 50/0.96



4 Ton

| 3/8″| 3/4″| 25/0.99| 50/0.98| 50/0.97| 50/0.96| 50/0.94| 50/0.93
1/2″| 3/4″| 25/0.99| 50/0.98| 50/0.97| 50/0.96| 50/0.94| 50/0.93
3/8″| 7/8″| 25/1.00| 50/0.99| 50/0.99| 50/0.98| 50/0.98| 50/0.97
1/2″| 7/8″| 25/1.00| 50/0.99| 50/0.99| 50/0.98| 50/0.98| 50/0.97



5 Ton

| 3/8″| 3/4″| 25/0.99| 50/0.97| 50/0.95| 50/0.93| 50/0.91| NR
1/2″| 3/4″| 25/0.99| 50/0.97| 50/0.95| 50/0.93| 50/0.91| NR
3/8″| 7/8″| 25/1.00| 50/0.99| 50/0.98| 50/0.98| 50/0.97| 38/0.96
1/2″| 7/8″| 25/1.00| 50/0.99| 50/0.98| 50/0.98| 50/0.97| 50/0.96

NOTES:

  1. Do not exceed 150 ft linear line length.
  2. Do not exceed 50 ft vertical separation between indoor and outdoor units.
  3. 3/4” suction line should only be used for 2 ton systems if outdoor unit is below or at same level as indoor unit to assure proper oil return.
  4. Always use the smallest liquid line allowable to minimize refrigerant charge.
  5. Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed.
  6. Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.

Designates Metric Conversions

18 SEER2 VARIABLE SPEED AIR CONDITIONERS


UNIT SIZE

| ALLOWABLE LIQUID LINE

SIZE

| ALLOWABLE VAPOR LINE

SIZE

| OUTDOOR UNIT ABOVE OR BELOW INDOOR UNIT EQUIVALENT LENGTH (METERS)
< 8| 8-15| 16-23| 24-30| 31-38| 39-46
MAXIMUM VERTICAL SEPARATION/CAPACITY MULTIPLIER



2 Ton* SEE NOTE 3

| 6.35 [1/4]| 15.88 [5/8]| 8/1.00| 15/0.99| 10/0.98| 10/0.97| NR| NR
7.94 [5/16]| 15.88 [5/8]| 8/1.00| 15/0.99| 15/0.98| 15/0.97| 15/0.96| 15/0.95
9.53 [3/8]| 15.88 [5/8]| 8/1.00| 15/0.99| 15/0.98| 15/0.97| 15/0.96| 15/0.95
6.35 [1/4]| 19.05 [3/4]| 8/1.00| 15/0.99| 10/0.99| 12/0.99| NR| NR
7.94 [5/16]| 19.05 [3/4]
| 8/1.00| 15/0.99| 15/0.99| 15/0.99| 15/0.99| 15/0.98
9.53 [3/8]| 19.05 [3/4]**| 8/1.00| 15/0.99| 15/0.99| 15/0.99| 15/0.99| 15/0.98



3 Ton

| 7.94 [5/16]| 15.88 [5/8]| 8/0.99| 15/0.97| 15/0.95| 15/0.93| 11/0.91| NR
9.53 [3/8]| 15.88 [5/8]| 8/0.99| 15/0.97| 15/0.95| 15/0.93| 15/0.91| NR
7.94 [5/16]| 19.05 [3/4]| 8/1.00| 15/0.99| 15/0.99| 15/0.98| 11/0.97| 7/0.96
9.53 [3/8]| 19.05 [3/4]| 8/1.00| 15/0.99| 15/0.99| 15/0.98| 15/0.97| 15/0.96
12.70 [1/2]| 19.05 [3/4]| 8/1.00| 15/0.99| 15/0.99| 15/0.98| 15/0.97| 15/0.96



4 Ton

| 9.53 [3/8]| 19.05 [3/4]| 8/0.99| 15/0.98| 15/0.97| 15/0.96| 15/0.94| 15/0.93
12.70 [1/2]| 19.05 [3/4]| 8/0.99| 15/0.98| 15/0.97| 15/0.96| 15/0.94| 15/0.93
9.53 [3/8]| 22.23 [7/8]| 8/1.00| 15/0.99| 15/0.99| 15/0.98| 15/0.98| 15/0.97
12.70 [1/2]| 22.23 [7/8]| 8/1.00| 15/0.99| 15/0.99| 15/0.98| 15/0.98| 15/0.97



5 Ton

| 9.53 [3/8]| 19.05 [3/4]| 8/0.99| 15/0.97| 15/0.95| 15/0.93| 15/0.91| NR
12.70 [1/2]| 19.05 [3/4]| 8/0.99| 15/0.97| 15/0.95| 15/0.93| 15/0.91| NR
9.53 [3/8]| 22.23 [7/8]| 8/1.00| 15/0.99| 15/0.98| 15/0.98| 15/0.97| 12/0.96
12.70 [1/2]| 22.23 [7/8]| 8/1.00| 15/0.99| 15/0.98| 15/0.98| 15/0.97| 15/0.97

NOTES:

  1. Do not exceed 46 meters linear line length.
  2. Do not exceed 15 meters vertical separation between indoor and outdoor units.
  3. 19.05mm [3/4 in.] vapor line should only be used for 2 ton systems if outdoor unit is below or at same level as indoor unit to assure proper oil return.
  4. Always use the smallest liquid line allowable to minimize refrigerant charge.
  5. Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed
  6. Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.

Performance Data @ AHRI Standard Conditions – Cooling

DESIGNATED TESTED COMBINATION (DTC)

OUTDOOR UNIT| INDOOR COIL| TOTAL CAPACITY BTU/H [KW]| NET SENSIBLE BTU/H [KW]| NET LATENT BTU/H [KW]| SEER2| EER2| INDOOR CFM [L/S]
SA18AZ24AJVC| SHMVZ2421MEACN| 22,400 [6.6]| 17,200 [5.0]| 5,200 [1.5]| 18.0| 10.5| 825 [389.4]
SA18AZ36AJVC| SHMVZ6021SEACA| 34,600 [10.1]| 25,800 [7.6]| 8,800 [2.6]| 18.0| 10.5| 1,225 [578.1]
SA18AZ48AJVC| SHMVZ6021SEACA| 45,000 [13.2]| 32,600 [9.6]| 12,400 [3.6]| 18.0| 10.5| 1,575 [743.3]
SA18AZ60AJVC| SHMVZ6024SEACN| 55,000 [16.1]| 40,200 [11.8]| 14,800 [4.3]| 18.0| 10.5| 1,650 [778.7]

NOTE : This data includes DTC (Designated Test Combination) ratings and is for reference purposes only. A full listing of official ratings and system match-ups, along with downloadable certificates, can be accessed from the AHRI website: www.ahridirectory.org.
Designates Metric Conversions

Integrated Controls

EcoNet® is smart, technology that allows Heating and Cooling, products to communicate with each other on one integrated network.

THE ECONET® SMART THERMOSTAT

  • BUILT-IN WIFI
  • 4.3″ LCD TOUCH SCREEN
  • LOCAL WEATHER – Current conditions plus 6-day forecast
  • 5 OPERATING MODES – Heat, Cool, Auto, Emergency Heat and Fan Only
  • 7-DAY PROGRAMMABLE SCHEDULE – Offers comfort without thought
  • ONE-TOUCH AWAY – Quickly switch to your energy-saving away preferences
  • VACATION SCHEDULING – Allows you to save while you’re away and come home to comfort
  • STANDBY SCREEN – Displays indoor temperature and current weather

OPERATIONAL FEATURES

  • AUTOMATIC CHANGEOVER – Transitions between heating and cooling automatically to keep the house comfortable
  • INTEGRATED WATER CONTROL – Enables easy water heater management
  • SMOOTH ARRIVAL – Prompts the system to start ahead of schedule to ensure the home is at the desired temperature at the scheduled time
  • HUMIDITY CONTROL – Supports humidifier accessories or over-cool-based dehumidification
  • DETAILED OPERATING STATUS – View pertinent equipment status information and run times
  • CONTINUOUS FAN – Offers 5 speeds (Low, Medium Low, Medium, Medium High, High)
  • SHORT-CYCLE PROTECTION – Avoids damage to equipment from short run cycles

MONITORING & REMOTE CONTROL FEATURES

  • ACTIVE MONITORING – Alerts to problems that need immediate attention
  • REMOTE CONTROL – Allows adjusting of comfort and settings from anywhere using a mobile device
  • SERVICE ALERTS – Sends routine maintenance reminders
  • AIR FILTER MONITORING – Detects when it’s time to replace the air filter
  • ALARM HISTORY – Displays time-stamped alarm codes with clear descriptions

WARRANTY

GENERAL TERMS OF LIMITED WARRANTY

Sure Comfort® will furnish a replacement for any part of this product that fails in normal use and service within the applicable period stated, by the terms of the limited warranty.
For complete details of the Limited and Conditional Warranties, including applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certificate.

Conditional Unit Replacement

  • (Registration Required)………………………………. Ten (10) Years
  • Parts…………………………………………………………Ten (10) Years

Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.
© 2023 Rheem Manufacturing Company. Sure Comfort trademarks are owned by Rheem Manufacturing Company. In keeping with its policy of continuous progress and product improvement, Sure Comfort reserves the right to make changes without notice.

Sure Comfort 5600 Old Greenwood Road Fort Smith, Arkansas 72908 www.surecomfort.com
Sure Comfort Canada 125 Edgeware Road, Unit 1 Brampton, Ontario L6Y 0P5 surecomfort.ca

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>