Technical Specifications

Operation frequency| 2.4 GHz – 2.483 GHz|
---|---|---
Transmission power| 4 dBm
Range (Typical indoor)| 10~30m|
Protocol| 5.0 SIG Mesh
Operating voltage| 220~240VAC 50/60Hz|
Stand-by power| <1W
DALI Channel 1| 50mA, Max. 25 LED drivers|
DALI Channel 2| 30mA, Max. 15 LED drivers
Sensor principle| PIR detection|
Detection range (Max.)*

HBHC25

| Installation Height : 6m

Detection Range (Ø) :9m

Detection range (Max.)*

HBHC25/R

| Installation Height : 6m

Detection Range(Ø) :10m

|
Detection range (Max.) HBHC25/W| Installation Height : 6m Detection Range(Ø) :18m
Detection range (Max.)
HBHC25/H| Installation height:15m (forklift)

12m (person) Detection range (Ø):24m

|
Detection range (Max.)* HBHC25/RH| Installation height:20m (forklift)

12m (person) Detection range (Ø):40m

Detection angle| 360O|
Operation temperature| Ta:-20OC~+50OC
IP rating| IP20|
EMC standard (EMC)| EN55015, EN61000, EN61547
Safety standard (LVD)| EN60669-1/-2-1

AS/NZS60669-1/-2-1

|
RED| EN300328, EN301489-1/-17
Certification| CB, CE , EMC, RED, RCM|

Download the App

Free App for set-up and commissioning

Bluetooth 5.0 SIG meh

Smartphone app for both iOS & Android platform

  • for iOS

  • for Android

Koolmesh Pro app for iPad

  • for iPad

Web app/platform: www.iot.koolmesh.com

  • for Web
    Download the App

Installation

Mechanical Structure & Dimensions

Installation

  1. Ceiling (drill hole φ66~68mm)
  2. Carefully prize off the cable clamps.
  3. Make connections to the pluggable terminal blocks.
  4. Insert plug connectors and secure using  the provided cable clamps, then clip terminal covers to the base.
  5. Fit detection blind (if required) and desired lens.
  6. Clip fascia to body.
  7. Bend back springs and insert into ceiling.

HBHC25

Installation

HBHC25/R

Installation

HBHC25/W

Installation

HBHC25/H

Installation

HBHC25/RH

Installation

Wire Preparation

0.75 – 2.5mm

Pluggable screw terminal. It is recommended to make
connections to the terminal before fitting to the sensor.

  1.  200 metres (total) max. for 1mm² CSA (Ta = 50℃)
  2.  300 metres (total) max. for 1.5mm² CSA (Ta = 50℃)

Wiring Diagram

Wiring Diagram

Dimming Interface Operation Notes

Switch-Dim
The provided Switch-Dim interface allows for a simple dimming method using commercially available non-latching (momentary) wall switches. Detailed Push switch configurations can be set on Kool mesh app.

Switch Function Action Descriptions
Push switch Short press (<1 second)
  • Short press has to be longer than 0.1s, or it will be invalid.

|

  • Turn on/off
  • Recall a scene
  • Turn on only
  • Exit manual mode
  • Turn off only
  • Do nothing

Double push|

  • Turn on only
  • Exit manual mode
  • Turn off only
  • Do nothing
  • Recall a scene

Long press (≥1 second)|

  • Dimming
  • Colour tuning
  • Do nothing

Simulate sensor| /|

  • Upgrade a normal on/off motion sensor to a Bluetooth controlled motion sensor

Detection Pattern & Optional Accessories

HBHC25 (Low-bay)

HBHC25: Low-bay flat lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-6m)

A: Tangential movement

HBHC25 \(Low-bay\)

B: Radial movement

HBHC25 \(Low-bay\)

Mount height Tangential (A) Radial (B)
2.5m max 50m2 (Ø = 8m) max 13m2 (Ø = 4m)
3m max 64m2 (Ø = 9m) max 13m2 (Ø = 4m)
4m max 38m2 (Ø = 7m) max 13m2 (Ø = 4m)
5m max 38m2 (Ø = 7m) max 13m2 (Ø = 4m)
6m max 38m2 (Ø = 7m) max 13m2 (Ø = 4m)

Optional Accessory — Ceiling/Surface Mount Box: HA03

Optional Accessory

Optional Accessory — Blind Insert for Blocking Certain Detection Angles

Blind Option 1 — Aisle Detection

Optional Accessory --- Blind Insert for Blocking Certain Detection
Angles

Blind Option 2 — 180º Detection

Optional Accessory --- Blind Insert for Blocking Certain Detection
Angles

HBHC25/R (Reinforced Low-bay)

HBHC25/R: Low-bay convex lens detection pattern for single person @ Ta = 20ºC (Recommended ceiling mount installation height 2.5m-6m)

A: Tangential movement

HBHC25 \(Low-bay\)

B: Radial movement

HBHC25 \(Low-bay\)

Mount height Tangential (A) Radial (B)
2.5m max 79m2 (Ø = 10m) max 20m2 (Ø = 5m)
3m max 79m2 (Ø = 10m) max 20m2 (Ø = 5m)
4m max 64m2 (Ø = 9m) max 20m2 (Ø = 5m)
5m max 50m2 (Ø = 8m) max 20m2 (Ø = 5m)
6m max 50m2 (Ø = 8m) max 20m2 (Ø = 5m)

Optional Accessory — Ceiling/Surface Mount Box: HA03

Optional Accessory

Optional Accessory — Blind Insert for Blocking Certain Detection Angles

Blind Option 1 — Aisle Detection

Optional Accessory --- Blind Insert for Blocking Certain Detection
Angles

Blind Option 2 — 180º Detection

Optional Accessory --- Blind Insert for Blocking Certain Detection
Angles

HBHC25/W (Wide range Low-bay)

Mount height Tangential (A) Radial (B)
2.5m max 254m² (Ø = 18m) max 28m² (Ø = 6m)
3m max 254m² (Ø = 18m) max 28m² (Ø = 6m)
4m max 154m² (Ø = 14m) max 28m² (Ø = 6m
5m max 113m² (Ø = 12m) max 28m² (Ø = 6m
6m max 79m² (Ø = 10m) max 13m² (Ø = 4m)

A: Tangential movement

HBHC25 \(Low-bay\)

B: Radial movement

HBHC25 \(Low-bay\)

Placement Guide and Typical Range

Smart Phone to Device Range

Placement Guide and Typical Range

The smart device with the App installed will have a typical range of 10m, but varies from device to device. During commissioning, the installer will need to be in range of the devices when searching for devices to add to the network.
Once the devices have been added to the network via the App, the devices will start communicating within the wireless mesh.
This means that once the network is complete, all devices are accessible from the smart device when in a 20m range of a single point.

Big and small silicon gasket used to make IP54 degree protection when HBHC25 series device mounted into HA03 housing for ceiling mount

Small silicon water-proof gasket dimension(size:mm)

Placement Guide and Typical Range

Big silicon water-proof gasket dimension(size:mm)

Placement Guide and Typical Range

HBHC25/H (High-bay)

HBHC25/H: High-bay lens detection pattern for forklift @ Ta = 20ºC (Recommended ceiling mount installation height 10m-15m)

A : Tangential movement

HBHC25/H \(High-bay\)

B : Radial movement

HBHC25/H \(High-bay\)

Mount height Tangential (A) Radial (B)
10m max 380m2 (Ø = 22m) max 201m2 (Ø = 16m)
11m max 452m2 (Ø = 24m) max 201m2 (Ø = 16m)
12m max 452m2 (Ø = 24m) max 201m2 (Ø = 16m)
13m max 452m2 (Ø = 24m) max 177m2 (Ø = 15m)
14m max 452m2 (Ø = 24m) max 133m2 (Ø = 13m)
15m max 452m2 (Ø = 24m) max 113m2 (Ø = 12m)

HBHC25/H: High-bay lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-12m)

A : Tangential movement

HBHC25/H \(High-bay\)

B : Radial movement

HBHC25/H \(High-bay\)

Mount height Tangential (A) Radial (B)
2.5m max 50m2 (Ø = 8m) max 7m2 (Ø = 3m)
6m max 104m2 (Ø = 11.5m) max 7m2 (Ø = 3m)
8m max 154m2 (Ø = 14m) max 7m2 (Ø = 3m)
10m max 227m2 (Ø = 17m) max 7m2 (Ø = 3m)
11m max 269m2 (Ø = 18.5m) max 7m² (Ø = 3m)
12m max 314m2 (Ø = 20m) max 7m² (Ø = 3m)

Optional Accessory — Ceiling/Surface Mount Box: HA03

Optional Accessory

Optional Accessory — Blind Insert for Blocking Certain Detection Angles

Blind Option 1 — Aisle Detection

Optional Accessory --- Blind Insert for Blocking Certain Detection
Angles

Blind Option 2 — 180º Detection

Optional Accessory --- Blind Insert for Blocking Certain Detection
Angles

HBHC25/RH (Reinforced High-bay with 3-Pyro)

HBHC25/RH: Reinforced high-bay lens detection pattern for forklift @ Ta = 20ºC
(Recommended ceiling mount installation height 10m-15m)

A: Tangential movement

HBHC25/H \(High-bay\)

B: Radial movement

HBHC25/H \(High-bay\)

Mount height Tangential (A) Radial (B)
10m max 346m2 (Ø = 21m) max 177m2 (Ø = 15m)
11m max 660m2 (Ø = 29m) max 177m2 (Ø = 15m)
12m max 907m2 (Ø = 34m) max 154m2 (Ø = 14m)
13m max 962m2 (Ø = 35m) max 154m2 (Ø = 14m)
14m max 1075m2 (Ø = 37m) max 113m2 (Ø = 12m)
15m max 1256m2 (Ø = 40m) max 113m2 (Ø = 12m)
20m max 707m2 (Ø = 30m) max 113m2 (Ø = 12m)

HBHC25/RH: Reinforced high-bay lens detection pattern for single person @ Ta = 20OC
(Recommended ceiling mount installation height 2.5m-12m)

A : Tangential movement

HBHC25/H \(High-bay\)

B : Radial movement

HBHC25/H \(High-bay\)

Mount height Tangential (A) Radial (B)
2.5m max 38m2 (Ø = 7m) max 7m2 (Ø = 3m)
6m max 154m2 (Ø = 14m) max 7m2 (Ø = 3m)
8m max 314m2 (Ø = 20m) max 7m2 (Ø = 3m)
10m max 531m2 (Ø = 26m) max 13m2 (Ø = 4m)
11m max 615m2 (Ø = 28m) max 13m2 (Ø = 4m)
12m max 707m2 (Ø = 30m) max 13m2 (Ø = 4m)

Optional Accessory — Ceiling/Surface Mount Box: HA03

Optional Accessory

Additional Information / Documents

  1. To learn more about detailed product features/functions, please refer to www.hytronik.com/download ->knowledge ->Introduction of App Scenes and Product Functions
  2. Regarding precautions for Bluetooth product installation and operation, please kindly refer to www.hytronik.com ->download/knowledge ->Bluetooth Products – Precautions for Product Installation and Operation
  3. Data sheet is subject to change without notice. Please always refer to the most recent release on www.hytronik.com/products/bluetooth technology ->Bluetooth Sensors
  4. Regarding Hydronic standard guarantee policy, please refer to www.hytronik.com/download ->knowledge ->Hydronic Standard Guarantee Policy

www.hytronik.com
Subject to change without notice.

Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

HYTRONIK User Manuals

Related Manuals