HYTRONIK HBHC25-W PIR Standalone Motion Sensor Instruction Manual
- June 13, 2024
- HYTRONIK
Table of Contents
- Technical Specifications
- Download the App
- Installation
- Dimming Interface Operation Notes
- Detection Pattern & Optional Accessories
- Placement Guide and Typical Range
- HBHC25/H (High-bay)
- Additional Information / Documents
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
HYTRONIK HBHC25-W PIR Standalone Motion Sensor
Technical Specifications
Operation frequency| 2.4 GHz – 2.483 GHz|
---|---|---
Transmission power| 4 dBm
Range (Typical indoor)| 10~30m|
Protocol| 5.0 SIG Mesh
Operating voltage| 220~240VAC 50/60Hz|
Stand-by power| <1W
DALI Channel 1| 50mA, Max. 25 LED drivers|
DALI Channel 2| 30mA, Max. 15 LED drivers
Sensor principle| PIR detection|
Detection range (Max.)*
HBHC25
| Installation Height : 6m
Detection Range (Ø) :9m
Detection range (Max.)*
HBHC25/R
| Installation Height : 6m
Detection Range(Ø) :10m
|
Detection range (Max.) HBHC25/W| Installation Height : 6m Detection Range(Ø)
:18m
Detection range (Max.) HBHC25/H| Installation height:15m (forklift)
12m (person) Detection range (Ø):24m
|
Detection range (Max.)* HBHC25/RH| Installation height:20m (forklift)
12m (person) Detection range (Ø):40m
Detection angle| 360O|
Operation temperature| Ta:-20OC~+50OC
IP rating| IP20|
EMC standard (EMC)| EN55015, EN61000, EN61547
Safety standard (LVD)| EN60669-1/-2-1
AS/NZS60669-1/-2-1
|
RED| EN300328, EN301489-1/-17
Certification| CB, CE , EMC, RED, RCM|
Download the App
Free App for set-up and commissioning
Bluetooth 5.0 SIG meh
Smartphone app for both iOS & Android platform
Koolmesh Pro app for iPad
Web app/platform: www.iot.koolmesh.com
Installation
Mechanical Structure & Dimensions
- Ceiling (drill hole φ66~68mm)
- Carefully prize off the cable clamps.
- Make connections to the pluggable terminal blocks.
- Insert plug connectors and secure using the provided cable clamps, then clip terminal covers to the base.
- Fit detection blind (if required) and desired lens.
- Clip fascia to body.
- Bend back springs and insert into ceiling.
HBHC25
HBHC25/R
HBHC25/W
HBHC25/H
HBHC25/RH
Wire Preparation
0.75 – 2.5mm
Pluggable screw terminal. It is recommended to make
connections to the terminal before fitting to the sensor.
- 200 metres (total) max. for 1mm² CSA (Ta = 50℃)
- 300 metres (total) max. for 1.5mm² CSA (Ta = 50℃)
Wiring Diagram
Dimming Interface Operation Notes
Switch-Dim
The provided Switch-Dim interface allows for a simple dimming method using
commercially available non-latching (momentary) wall switches. Detailed Push
switch configurations can be set on Kool mesh app.
Switch Function | Action | Descriptions |
---|---|---|
Push switch | Short press (<1 second) |
- Short press has to be longer than 0.1s, or it will be invalid.
|
- Turn on/off
- Recall a scene
- Turn on only
- Exit manual mode
- Turn off only
- Do nothing
Double push|
- Turn on only
- Exit manual mode
- Turn off only
- Do nothing
- Recall a scene
Long press (≥1 second)|
- Dimming
- Colour tuning
- Do nothing
Simulate sensor| /|
- Upgrade a normal on/off motion sensor to a Bluetooth controlled motion sensor
Detection Pattern & Optional Accessories
HBHC25 (Low-bay)
HBHC25: Low-bay flat lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-6m)
A: Tangential movement
B: Radial movement
Mount height | Tangential (A) | Radial (B) |
---|---|---|
2.5m | max 50m2 (Ø = 8m) | max 13m2 (Ø = 4m) |
3m | max 64m2 (Ø = 9m) | max 13m2 (Ø = 4m) |
4m | max 38m2 (Ø = 7m) | max 13m2 (Ø = 4m) |
5m | max 38m2 (Ø = 7m) | max 13m2 (Ø = 4m) |
6m | max 38m2 (Ø = 7m) | max 13m2 (Ø = 4m) |
Optional Accessory — Ceiling/Surface Mount Box: HA03
Optional Accessory — Blind Insert for Blocking Certain Detection Angles
Blind Option 1 — Aisle Detection
Blind Option 2 — 180º Detection
HBHC25/R (Reinforced Low-bay)
HBHC25/R: Low-bay convex lens detection pattern for single person @ Ta = 20ºC (Recommended ceiling mount installation height 2.5m-6m)
A: Tangential movement
B: Radial movement
Mount height | Tangential (A) | Radial (B) |
---|---|---|
2.5m | max 79m2 (Ø = 10m) | max 20m2 (Ø = 5m) |
3m | max 79m2 (Ø = 10m) | max 20m2 (Ø = 5m) |
4m | max 64m2 (Ø = 9m) | max 20m2 (Ø = 5m) |
5m | max 50m2 (Ø = 8m) | max 20m2 (Ø = 5m) |
6m | max 50m2 (Ø = 8m) | max 20m2 (Ø = 5m) |
Optional Accessory — Ceiling/Surface Mount Box: HA03
Optional Accessory — Blind Insert for Blocking Certain Detection Angles
Blind Option 1 — Aisle Detection
Blind Option 2 — 180º Detection
HBHC25/W (Wide range Low-bay)
Mount height | Tangential (A) | Radial (B) |
---|---|---|
2.5m | max 254m² (Ø = 18m) | max 28m² (Ø = 6m) |
3m | max 254m² (Ø = 18m) | max 28m² (Ø = 6m) |
4m | max 154m² (Ø = 14m) | max 28m² (Ø = 6m |
5m | max 113m² (Ø = 12m) | max 28m² (Ø = 6m |
6m | max 79m² (Ø = 10m) | max 13m² (Ø = 4m) |
A: Tangential movement
B: Radial movement
Placement Guide and Typical Range
Smart Phone to Device Range
The smart device with the App installed will have a typical range of 10m, but
varies from device to device. During commissioning, the installer will need to
be in range of the devices when searching for devices to add to the network.
Once the devices have been added to the network via the App, the devices will
start communicating within the wireless mesh.
This means that once the network is complete, all devices are accessible from
the smart device when in a 20m range of a single point.
Big and small silicon gasket used to make IP54 degree protection when HBHC25 series device mounted into HA03 housing for ceiling mount
Small silicon water-proof gasket dimension(size:mm)
Big silicon water-proof gasket dimension(size:mm)
HBHC25/H (High-bay)
HBHC25/H: High-bay lens detection pattern for forklift @ Ta = 20ºC (Recommended ceiling mount installation height 10m-15m)
A : Tangential movement
B : Radial movement
Mount height | Tangential (A) | Radial (B) |
---|---|---|
10m | max 380m2 (Ø = 22m) | max 201m2 (Ø = 16m) |
11m | max 452m2 (Ø = 24m) | max 201m2 (Ø = 16m) |
12m | max 452m2 (Ø = 24m) | max 201m2 (Ø = 16m) |
13m | max 452m2 (Ø = 24m) | max 177m2 (Ø = 15m) |
14m | max 452m2 (Ø = 24m) | max 133m2 (Ø = 13m) |
15m | max 452m2 (Ø = 24m) | max 113m2 (Ø = 12m) |
HBHC25/H: High-bay lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-12m)
A : Tangential movement
B : Radial movement
Mount height | Tangential (A) | Radial (B) |
---|---|---|
2.5m | max 50m2 (Ø = 8m) | max 7m2 (Ø = 3m) |
6m | max 104m2 (Ø = 11.5m) | max 7m2 (Ø = 3m) |
8m | max 154m2 (Ø = 14m) | max 7m2 (Ø = 3m) |
10m | max 227m2 (Ø = 17m) | max 7m2 (Ø = 3m) |
11m | max 269m2 (Ø = 18.5m) | max 7m² (Ø = 3m) |
12m | max 314m2 (Ø = 20m) | max 7m² (Ø = 3m) |
Optional Accessory — Ceiling/Surface Mount Box: HA03
Optional Accessory — Blind Insert for Blocking Certain Detection Angles
Blind Option 1 — Aisle Detection
Blind Option 2 — 180º Detection
HBHC25/RH (Reinforced High-bay with 3-Pyro)
HBHC25/RH: Reinforced high-bay lens detection pattern for forklift @ Ta = 20ºC
(Recommended ceiling mount installation height 10m-15m)
A: Tangential movement
B: Radial movement
Mount height | Tangential (A) | Radial (B) |
---|---|---|
10m | max 346m2 (Ø = 21m) | max 177m2 (Ø = 15m) |
11m | max 660m2 (Ø = 29m) | max 177m2 (Ø = 15m) |
12m | max 907m2 (Ø = 34m) | max 154m2 (Ø = 14m) |
13m | max 962m2 (Ø = 35m) | max 154m2 (Ø = 14m) |
14m | max 1075m2 (Ø = 37m) | max 113m2 (Ø = 12m) |
15m | max 1256m2 (Ø = 40m) | max 113m2 (Ø = 12m) |
20m | max 707m2 (Ø = 30m) | max 113m2 (Ø = 12m) |
HBHC25/RH: Reinforced high-bay lens detection pattern for single person @ Ta =
20OC
(Recommended ceiling mount installation height 2.5m-12m)
A : Tangential movement
B : Radial movement
Mount height | Tangential (A) | Radial (B) |
---|---|---|
2.5m | max 38m2 (Ø = 7m) | max 7m2 (Ø = 3m) |
6m | max 154m2 (Ø = 14m) | max 7m2 (Ø = 3m) |
8m | max 314m2 (Ø = 20m) | max 7m2 (Ø = 3m) |
10m | max 531m2 (Ø = 26m) | max 13m2 (Ø = 4m) |
11m | max 615m2 (Ø = 28m) | max 13m2 (Ø = 4m) |
12m | max 707m2 (Ø = 30m) | max 13m2 (Ø = 4m) |
Optional Accessory — Ceiling/Surface Mount Box: HA03
Additional Information / Documents
- To learn more about detailed product features/functions, please refer to www.hytronik.com/download ->knowledge ->Introduction of App Scenes and Product Functions
- Regarding precautions for Bluetooth product installation and operation, please kindly refer to www.hytronik.com ->download/knowledge ->Bluetooth Products – Precautions for Product Installation and Operation
- Data sheet is subject to change without notice. Please always refer to the most recent release on www.hytronik.com/products/bluetooth technology ->Bluetooth Sensors
- Regarding Hydronic standard guarantee policy, please refer to www.hytronik.com/download ->knowledge ->Hydronic Standard Guarantee Policy
www.hytronik.com
Subject to change without notice.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>