BEGA 51013.4 Ceiling Luminaire LED For Indoor Use Instruction Manual
- June 13, 2024
- BEGA
Table of Contents
BEGA 51013.4 Ceiling Luminaire LED For Indoor Use
Product Information
Product Name | 51 013.4 K3 |
---|---|
Lamp Module Connected Wattage | 26.4 W |
Luminaire Connected Wattage | 29.5 W |
Colour Temperature | 3000 K |
Colour Rendering Index (CRI) | > 90 |
Module Luminous Flux | 3970 lm |
Luminaire Luminous Flux | 2455 lm |
Luminaire Luminous Efficiency | 83.2 lm / W |
Product Usage Instructions
Installation:
- Avoid touching the light output opening of the LED directly during installation or relamping.
- To remove the synthetic cover, turn it anti-clockwise as far as it will go while simultaneously pushing the synthetic cover up against the luminaire fitting.
Safety:
- The installation and operation of this luminaire are subject to national safety regulations.
- Installation and commissioning should only be carried out by a qualified electrician.
- The manufacturer does not accept liability for damage caused by improper use or installation.
- If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Overvoltage Protection:
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547. For additional protection against
transients, it is recommended to use separate overvoltage protection
components. These can be found on our website at
www.bega.com.
Spares:
- Synthetic cover: 15 000 633 71 001 760 L13
- Shield: 75 001 903 .1K 3
- LED unit 3000 K: 15 000 633 71 001 760 L13
Ceiling luminaire for indoor use
DIMENSIONS
Instructions for use
Application
Ceiling luminaire · indoor luminaire impact resistant synthetic diffuser and
metal housing for non-glare light deflected downwards.
Product description
- Ceiling luminaire »STUDIO LINE« Aluminium luminaire housing, Colour velvet black finish, Inside hue matt brass Metal luminaire mounting plate, finish colour white Impact resistant synthetic diffuser, white, with bayonet closure 2 mounting holes ø 5.5 mm Distance apart 230 mm 2 cable entries for through-wiring for mains cable up to ø 10,5 mm max. 5 x 1.5@ Connection terminal 2.5@
- Earth conductor connection LED power supply unit 220-240 V x 0/50-60 Hz
- DALI-controllable Basic insulation is provided between the mains and control cables BEGA Thermal Switch® Temporary thermal shutdown to protect temperature-sensitive components
- Safety class I
- Impact strength IK10
- Protection against mechanical impacts < 20 joule
- Safety mark
- Conformity mark
- Weight : 2.6 kg
Lamp
-
Module connected wattage : 26.4 W
-
Luminaire connected wattage: 29.5 W
-
Rated temperature: ta = 25 °C
-
Ambient temperature: ta max = 40 °C
51 013.4 K3
-
Colour temperature: 3000 K
-
Colour rendering index: CRI > 90
-
Module luminous flux: 3970 lm
-
Luminaire luminous flux: 2455 lm
-
Luminaire luminous efficiency: 83,2 lm / W
Installation
LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
- Before installing onto the ceiling the luminaire mounting plate must be inserted into the luminaire housing. Thereby pass the mains supply cable through the grommet into luminaire mounting plate.
- Fix monting plate inside the luminaire housing with enclosed or any other suitable fixing material on to the mounting surface.
- Dismantle the mains supply cable approx. 60 mm.
- Pull silicone sleeves over the wires and make earth and electrical connection to the terminals. For digital control please use the connecting terminal DA, DA.
- In case this terminal is not used the luminaire will be operated at full light output.
- In order to securely install the synthetic cover in the fitting, the top opening of the synthetic cover must be inserted into the luminaire housing at an angle.
- Make sure that at least one of the recesses in the edge of the synthetic cover matches the position of one of the lugs on the fitting see drawing.
IMPORTANT:
Turn the synthetic cover upwards into the fitting as far as it will go. Now
secure the synthetic cover in the fitting by turning it clockwise. Only then
is the synthetic cover held securely in place and resistant to vibration. The
synthetic cover is removed by turning it anti-clockwise as far as it will go
while simultaneously pushing the synthetic cover up against the luminaire
fitting.
Safety
The installation and operation of this luminaire are subject to national
safety regulations. Installation and commissioning may only be carried out by
a qualified electrician. The manufacturer accepts no liability for damage
caused by improper use or installation. If subsequent modifications are made
to the luminaire, the person responsible for these modifications shall be
considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547. To achieve an additional
protection against e. g. transients, etc. we recommend separate overvoltage
protection components.
You can find them on our website at www.bega.com.
Cleaning Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacement of the LED unit
- The designation of the LED unit is noted on a label in the luminaire.
- The light colour and light output of BEGA replacement units correspond to those of the LED units originally fitted. The LED unit can be replaced by qualified persons using standard tools.
- Disconnect from main supply.
- Unscrew synthetic diffuser from luminaire housing by turning it counter-clockwise. Disassemble LED unit.
- Assemble LED replacement unit.
- Note installation instructions of the LED unit. Screw in synthetic diffuser by turning it clockwise.
- A damaged synthetic diffuser must be replaced.
Spares
- Synthetic cover: 15 000 633
- Shield: 71 001 760 L13
- LED unit 3000 K: 75 001 903 .1K 3
BEGA Gantenbrink-Leuchten KG Postfach 31 60 58689 Menden info@bega.com www.bega.com